
Maintenance and Troubleshooting
Alarm Response/Reset
The failure recovery process is a logical sequence of events to restore connectivity. With monitoring and corrective action at each step, the process includes:
Providing power to the Broadmore 1750 and control station
Establishing connectivity between the Broadmore 1750 and control station
Loading the Broadmore 1750 configuration
Establishing ATM connectivity
Establishing individual circuit connectivity
Alarm Response/Reset
Alarms are designed into the Broadmore 1750 to provide the initial indication of a communications problem and to help isolate the problem. For example, a major alarm from a SAM identifies the specific module that will focus response efforts. The following flowchart approach to troubleshooting is based upon the initial alarm indication. The alarm response is a
1.Troubleshoot to isolate the cause.
2.Complete corrective action to eliminate the alarm condition.
3.Return system to full operation and document the events.
Alarms are designed as
Flowchart
The
CAUTION! SOME STEPS IN THE FOLLOWING FLOWCHART MAY CAUSE DISRUPTION IN SERVICE.
Broadmore 1750 - Release 4.6 |