Roberts Gorden HE-60, HE-80 United States Requirements, Canadian Requirements, Unvented Operation

Page 42

HE-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL

8.1.1 United States Requirements

Vent must terminate at least 3' (.9 m) above any forced air inlet located within 10' (3.1 m).

Vent must terminate at least 4' (1.2 m) below, 4'

(1.2 m) horizontally from, or 1' (.3 m) above any door, operable window, or gravity air inlet into any building.

8.1.2 Canadian Requirements

The vent shall not terminate within 6' (1.8 m) of a mechanical air supply inlet to any building.

The vent shall not terminate within 3' (.9 m) of a

window or door that can be opened in any building, any non-mechanical air supply inlet to any building, or of the combustion air inlet of any other appliance.

8.2 Unvented Operation

Sufficient ventilation must be provided in the amount of 4 cfm per 1000 Btu/h firing rate (United States); 3 cfm per 1000 Btu/h firing rate (Canada).

Use of optional outside combustion air is not recommended with unvented heaters.

If exhaust fans are used to supply ventilation air, an interlock switch must be used to prevent the heater from coming on when the fans are off. This may be done using a pressure switch.

8.3 Horizontal Venting

In noncombustible walls only, vent terminal (P/N 02537801-1P) may be used.

For 4'' (10 cm) vents in either combustible or noncombustible walls, use Tjernlund VH1-4 (P/N 90502100) or equivalent, insulated vent terminal. Follow the manufacturer's instructions for proper installation.

For 6'' (15 cm) common vents in either combustible or noncombustible walls, use Tjernlund VH1-6 (P/N 90502101) or equivalent, insulated vent terminal.

Follow the manufacturer's instructions for proper installation.

8.4 Vertical Venting

For 4'' (10 cm), an approved vent cap (P/N 90502300) must be used.

For 6'' (15 cm) common vent, an approved vent cap (P/N 90502302) must be used.

For common vertical venting of more than two heaters, See Page 40, Section 8.11.

A vent shall not extend less than 2' (.6m) above the highest point where it passes through a flat roof of a building.

8.5 Unvented Operation Tube Termination

Turndown type vent terminal with a screen must be installed at the exhaust end of the tube. Vent terminal design shall not incorporate backdraft flap.

FIGURE 22: Tube Termination

8.6 Length Requirements

The maximum vent length allowed is 45' (13.7 m). The maximum outside air supply duct length allowed is 45' (13.7 m).

The total vent length, plus outside air duct length, plus any extensions to minimum heat exchanger lengths, cannot exceed 65' (19.8 m).

Vent length should be limited to less than 20' (6 m). If using vent lengths greater than 20' (6 m), condensation will form in the vent pipe. Insulation and additional sealing measures (high temperature silicone at all seams) are required. Optional heat exchanger beyond minimum lengths is considered as vent length for length determination.

Subtract 15' (4.6 m) of maximum allowed vent or duct length per vent elbow if more than two are used.

36

Image 42
Contents Vantage Page Roberts-Gordon LLC Page Table of Figures Page Safety Labels and Their Placement Heater SafetyManpower Requirements California PropositionTop and Bottom Panel Label Placement Side and Back Panel Label Placement Installer Responsibility Wall TagNational Standards and Applicable Codes Page Standard Reflector Inches CentimetersModel InchesC D Unapproved TUBE, Opposite 45 Reflector Venting National Standards and Applicable Codes Major Components Standard Parts List Contents of Heater Burner CartonComponent Package Guide Heater Installation Typical Suspension Details Critical Hanger Placement Outdoor Installation Outdoor MountingStainless steel reflector packages Linear Heater Layout Overview Burner Tube Installation Tube Clamp Package InstallationCoupling and Tube Assembly 1 Coupling and Tube Assembly2 Coupling and Tube Assembly Turbulator InstallationHanger Burner Tube Reflector 1 Reflector, U-Clip and Reflector Support Installation Description Part Number Reflector Support PackageBurner Installation Optional Heater Accessories Tube, Standard Tube heater Layout Overview Elbow Package Configuration .2.1 Elbow Installation 2 Elbow Installation3 Reflector Joint Installation 4 Reflector Joint Installation 5 Reflector Joint Detail Reflector Joint Detail2 Side Reflector Installation Scr ews 2 Frame Shield Installation Distance a Extension2 Grille End Cap Installation 3 Grille InstallationOutdoor Vent Cap Installation Unvented Operation United States RequirementsCanadian Requirements Horizontal VentingVenting Options Horizontal Ventilation 4 10 cm Pipe Vertical Ventilation 4 10 cm PipeCommon Sidewall Venting TOP ViewCommon Vertical Venting Outside Combustion Air SupplyVertical Outside Air Supply for Single Heater Installation Horizontal Outside Air Supply for Single Heater InstallationVertical Outside Air Supply for Double Heater Installation Horizontal Outside Air Supply for Double Heater InstallationGAS Piping Incorrect Positions Wrong Installation Correct PositionsWiring Line Voltage Thermostat WiringLow Voltage Thermostat with One Burner Page Internal Wiring For External Thermostat ConnectionLadder Diagram Sequence of Operation Operation and MaintenancePre-Season Maintenance and Annual Inspection To Shut Off HeaterVehicles and Other Installation Code and Annual InspectionsMaintenance Checklist Vicinity of the Heater ObjectsTubes Safety LabelsReflector Support Straps Gas LineTroubleshooting Honeywell SmartValve II Troubleshooting LED Status IndicatesTroubleshooting Flow Chart Yes Manifold Gas Pressure Setting Natural Gas LP GasReplacement Parts Motor and Blower Assembly Blower Inlet Gasket Door Switch Description Part Number GAS Pressure AT Manifold General SpecificationsDimensions Pipe ConnectionWarranty is Void if ROBERTS-GORDON LLC will not PAY forLimitations on Authority Representatives Page Page Page
Related manuals
Manual 2 pages 4.23 Kb

HE-125, HE-150, HE-100, HE-40, HE-175 specifications

Roberts Gordon is renowned for its innovative heating solutions, and among its standout offerings are the HE-125, HE-175, HE-100, HE-150, and HE-40 heaters. These products exemplify cutting-edge technology and efficiency designed for commercial and industrial applications.

The HE-125 and HE-175 variants are among the top-rated infrared heaters available. They utilize advanced infrared technology to provide direct heating to objects, reducing the need to heat the entire ambient air volume. This method results in energy savings while delivering consistent warmth where it's needed most. The HE-125 model has a heating capacity of 125,000 BTU, while the HE-175 pushes this to 175,000 BTU, making them suitable for larger spaces like warehouses and manufacturing facilities.

The HE-100 and HE-150 heaters are designed for flexibility and efficiency in a range of operational environments. These models support a wide range of input fuels including natural gas and propane, making them an adaptable choice for various setups. The HE-100 has an output of 100,000 BTU, and the HE-150 follows with 150,000 BTU. Both units are engineered with robust construction materials, ensuring durability and longevity, while also featuring advanced safety systems to prevent overheating and other hazards.

In contrast, the HE-40 heater stands out for smaller spaces, making it an ideal option for garages, workshops, or smaller commercial environments. With a capacity of 40,000 BTU, it effectively delivers consistent warmth without the excessive energy consumption associated with larger units.

All Roberts Gordon models prioritize energy efficiency, often meeting or exceeding current energy codes. They incorporate advanced control systems that allow precise temperature regulation, further optimizing energy use. Additionally, the heaters are designed with minimal maintenance needs, featuring durable components that ensure long-term reliability and performance.

With a legacy of quality and innovation, Roberts Gordon continues to set the standard in infrared heating technology. The HE series exemplifies a commitment to efficiency, safety, and versatility, making them suitable for a wide range of commercial and industrial applications. Whether heating a vast warehouse or a small workshop, these heaters provide reliable performance tailored to user needs.