Roberts Gorden 75 Critical Considerations 3.1 Basic Information, Manufactured Units, Ventilation

Page 12

UHA LOW PROFILE UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL

SECTION 3: CRITICAL CONSIDERATIONS 3.1 Basic Information

UHA[X][S] heaters have automatic ignition burners for ON/OFF operation only.

3.2 Manufactured Units

Gas-fired, power-vented unit heater with tubular heat exchanger. Units shall have a minimum of 82% thermal efficiency. The standard unit shall consist of

anon-separated combustion design with an aluminized heat exchanger. Design and heat exchanger alternatives shall be offered as follows:

Separated Combustion: A separated combustion unit shall consist of an enclosed sealed burner box to which combustion air is vented through a piece of internal flexible air duct. This duct terminates at an exterior cabinet flange to which a vent ran to the outside of the heated space should be attached.

Stainless Steel Heat Exchanger: A stainless steel heat exchanger unit shall consist of heat exchanger tubes, heat exchanger tube supports, heat exchanger tube plates and a vent box produced of 409 stainless steel.

3.3Location and Suspension All models:

• Must be installed indoors.

Must be installed in a level position with horizontal discharge.

May be mounted on a shelf of non-combustible material using shelf mounting brackets.(See Page 11, Figure 6 and Page 12, Figure 7 for details.)

May be suspended from above (See Page 11, Figure 5) or from wall brackets of sufficient strength to support the heater as listed in the Dimension Data Table on Page 49, Section 15.1. Drop rods must be a minimum of 3/8" diameter mild steel. Four suspension points (3/8" nuts) are located on top of the heater.

Must be installed in a manner which allows access to all serviceable components. See Page 7, Figure 4 for details.

3.4 Minimum Required Installation Clearances

Clearances around the heater and vent must be as indicated on Page 7, Figure 4; Page 17, Figure 9 through Page 20, Figure 14 to ensure access for servicing, and correct operation.

3.5 Clearances to Combustibles

WARNING

Fire Hazard

Some objects can catch fire or explode when placed close to heater.

Keep all flammable objects, liquids and vapors the required clearances to combustibles away from heater.

Failure to follow these instructions can result in death, injury or property damage.

Clearances must be as indicated on Page 7, Figure 4. If clearances to combustibles are not indicated, then installation clearances apply.

3.6 Ventilation

WARNING

Carbon Monoxide Hazard

Heaters may be installed vented or unvented.

Vented heaters must be vented outdoors.

Unvented heaters must be installed in buildings with ventilation rates as per section 6.4.

Failure to follow these instructions can result in death or injury.

It is important to ensure that there is adequate air space around the heater to supply air for combustion, ventilation and distribution in accordance with local and national code on Page 14, Section 6.

6

Image 12
Contents Blackheat Page Roberts-Gordon LLC Page Table of Figures Page Heater Safety Manpower RequirementsSafety Labels and Their Placement UHA 30 45 Label Placement UHA 60 75 Label Placement UHA 100 125 Label Placement Installer Responsibility Wall TagCorrosive Chemicals National Standards and Applicable CodesMinimum Required Installation Clearances Critical Considerations 3.1 Basic InformationManufactured Units Clearances to CombustiblesGas Supply Electrical SupplyVent National Standards and Applicable Codes High Altitude Major Components 5.1 General Shelf Mounting and SuspensionWall Mounting Suspension Methods Wall Shelf Mounting and Hanging Suspension Vertical Louvers Optional Vent Installation VentingChanging Vent and Air Intake Orientation United States RequirementsStandard Vented Heaters Models Uhax 30 Separated Combustion Heaters Models Uhaxs 30Unvented Operation Horizontal VentingVertical Venting Length RequirementsMaximum Vent Lengths Vent MaterialVent and Roof Detail Standard Vented Heater Common Vertical Vent Termination Concentric Vent Box Vertical Separated Combustion Installation Unvented InstallationAIR Supply Building VentilationGAS Piping ConnectionsWiring Positioning ThermostatsFan Control Low Voltage Thermostat with One HeaterLow Voltage Thermostat with Multiple Heaters 30 Low Voltage Thermostat with Multiple Heaters 60 Internal Wiring Diagram TransformerLadder Wiring Diagram FlameElectrical Connection to the Heater Operation and Maintenance Pressure Regulator Gas Outlet Outlet Pressure Pressure Switch Check Gas RateTurning Off the Heater Complete Start-Up Instruction to the UserUser Instructions User InstructionsHeater Operation Lighting Instructions 11.4.1 To Turn On HeaterSimple Troubleshooting Simple Troubleshooting Burner FaultsTo Turn the Heater Off Servicing Maintenance Checklist Venting and Air Intake PipeVicinity of the Heater Vehicles and OtherWhen installed Wall Tag Combustion Air IntakePipe Heat ExchangerTroubleshooting 13.1 General Troubleshooting For Automatic Ignition Burner Systems Conduct start-up procedure as shown on Page 29, SectionTroubleshooting for Flame Supervision System Troubleshooting for Gas Valves Troubleshooting for Flue BlowerReplacement Parts Burner ComponentsBurner Compartment Burner InjectorsIgnition Electrode and Flame Probe Louver and Louver Springs Re-usedFlue Blower Vertical Installation Axial Fan/Guard/Motor Assembly Ignition ControlFan Removal and Replacement To Replace the Fan AssemblyLimit Switches Removal and Replacement Specifications 15.1 Dimension Data Model UhaxsGeneral Technical Data Table All Models Technical Data Table All ModelsWarranty is Void if Roberts Gordon will not PAY forRoberts-Gordon Limitations on Authority RepresentativesPage Owner Warranty Registration Card Page Page Some objects can catch fire or explode when placed
Related manuals
Manual 60 pages 21.77 Kb

60, 30, 45, 125, 100 specifications

Roberts Gordon is a recognized leader in the manufacturing of innovative heating solutions, with a diverse product line including the 100, 125, 75, 45, and 60 series of radiant tube heaters. Each model is designed to meet specific heating needs while emphasizing efficiency, durability, and performance.

The Robert Gordon 100 series is known for its high efficiency and ability to provide consistent warmth in large industrial spaces. It features advanced infrared technology, which heats objects and surfaces directly, resulting in quicker temperature increases and enhanced comfort. This model is equipped with modulating burners that allow for optimal gas usage and can be easily integrated into existing systems.

The 125 series builds upon the efficiency of the 100 model while offering increased heating capacity. Its robust design ensures it can handle the demands of larger applications, such as warehouses and manufacturing facilities. With enhanced control options, users can tailor the heating output to match specific operational requirements, reducing energy consumption.

The 75 series offers a compact solution for smaller commercial spaces, providing a reliable heating source without taking up excessive floor space. Its lightweight design facilitates easy installation, while the modular approach allows for scalability to meet changing heating demands. This series emphasizes sustainability, utilizing advanced combustion technologies that minimize emissions.

For smaller applications, the 45 series stands out with its efficient heating capabilities in confined spaces. This series features simple, yet effective controls, enabling straightforward operation. The robust construction ensures durability, making it well-suited for different commercial environments, including retail settings or small workshops.

Finally, the 60 series combines the best features of the range with energy conservation as a primary focus. Its innovative design incorporates smart technology to monitor energy usage and optimize performance. The heaters are equipped with the latest in safety features, providing peace of mind for users.

Overall, Roberts Gordon’s radiant tube heaters showcase a commitment to high-quality heating solutions that cater to a variety of industrial and commercial applications. With energy efficiency, superior durability, and advanced heating technologies as core characteristics, Roberts Gordon remains a trusted choice for businesses looking to enhance their heating performance.