Roberts Gorden 125 Venting, Changing Vent and Air Intake Orientation, United States Requirements

Page 20

UHA LOW PROFILE UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL

SECTION 6: VENTING

WARNING

Carbon Monoxide Hazard

Heaters may be installed vented or unvented.

Vented heaters must be vented outdoors.

Unvented heaters must be installed in buildings with ventilation rates as per section 6.4.

Failure to follow these instructions can result in death or injury.

6.1 Changing Vent and Air Intake Orientation

The heater is sold with rear horizontal vent and air intake connections as standard (only separated combustion models have air intake connection). If vertical vent and air intake connections are required, follow the instructions on Page 46, Section 14.6.

6.2 Venting

This heater must be vented in accordance with the rules contained in this manual and with the following national codes and any state, provincial or local codes which may apply: United States: Refer to NFPA54/ANSI Z223.1 - latest revision, National Fuel Gas Code; Canada: Refer to CSA B149.1 Natural Gas and Propane Installation Code.

Any portion of vent pipe passing through a combustible wall must have a listed thimble to conform with the above codes.

The heater may be installed unvented in certain circumstances according to building ventilation codes. Refer to the above codes and Page 15, Section 6.4 for further information. Unvented operation also requires compliance with the clearances to combustibles given on Page 7, Figure 4.

The bottom of the vent or air intake terminal shall not be located less than 1' (.3 m) above grade level.

The vent shall not terminate less than 7' (2.1 m) above grade where located adjacent to public walkways.

Vent terminal must be installed at a height sufficient to prevent blockage by snow and building materials protected from degradation by flue gasses.

Vent terminal must be beyond any combustible overhang.

Secure all joints with corrosion resistant #8 x 3/8"

sheet metal screws.

For single wall venting, pressure sensitive aluminum tape or silicone sealant must be used to seal all joints.

Aluminum tape shall have a minimum temperature rating of 400° F (204° C) and meet SMACNA AFTS- 100-73 standards. High temperature silicone sealant must have a minimum temperature rating of 480° F (250° C).

6.2.1 United States Requirements

Vent must terminate at least 3' (.9 m) above any forced air inlet located within 10' (3.1 m).

Vent must terminate at least 4' (1.2 m) below,

4' (1.2 m) horizontally from, or 1' (.3 m) above any door, operable window, or gravity air inlet into any building.

NFPA 54/ANSI Z223.1 - latest revision, National Fuel Gas Code specifies a 4' (1.2 m) horizontal vent terminal clearance from gas and electric meters, regulators and relief equipment.

6.2.2 Canadian Requirements

The vent shall not terminate within 6' (1.8 m) of a mechanical air supply inlet to any building.

The vent shall not terminate within 3' (.9 m) of a window or door that can be opened in any building, any non-mechanical air supply inlet to any building, or of the combustion air inlet of any other appliance.

6.3 Vent Installation

Maintain clearences to combustibles at all times for safety. Clearences are the required distances that combustible objects must be away from the heater to prevent serious fire hazard. See Page 7, Figure 4. For vented units, the vent must terminate outside of the building.

Vents must be fully sealed and correctly sized for the model. If the vent passes through a wall or ceiling of combustible material, it must be enclosed by a listed thimble and be separated from the thimble by at least a 2" (5 cm) air gap.

For separated combustion models, vents and air intakes must be a fully sealed system and correctly sized for the model. Vent should be assembled as detailed on Page 17, Figure 9 through Page 20, Figure 14. The joints between the vent terminal and the roof or wall must be properly sealed. If the vent passes through a wall or ceiling of combustible material, it must be enclosed by a listed thimble and be separated from the thimble by at least a 2" (5 cm) air gap.

14

Image 20
Contents Blackheat Page Roberts-Gordon LLC Page Table of Figures Page Safety Labels and Their Placement Heater SafetyManpower Requirements UHA 30 45 Label Placement UHA 60 75 Label Placement UHA 100 125 Label Placement Installer Responsibility Wall TagCorrosive Chemicals National Standards and Applicable CodesMinimum Required Installation Clearances Critical Considerations 3.1 Basic InformationManufactured Units Clearances to CombustiblesVent Gas SupplyElectrical Supply National Standards and Applicable Codes High Altitude Wall Mounting Major Components 5.1 GeneralShelf Mounting and Suspension Suspension Methods Wall Shelf Mounting and Hanging Suspension Vertical Louvers Optional Vent Installation VentingChanging Vent and Air Intake Orientation United States RequirementsStandard Vented Heaters Models Uhax 30 Separated Combustion Heaters Models Uhaxs 30Unvented Operation Horizontal VentingVertical Venting Length RequirementsMaximum Vent Lengths Vent MaterialVent and Roof Detail Standard Vented Heater Common Vertical Vent Termination Concentric Vent Box Vertical Separated Combustion Installation Unvented InstallationAIR Supply Building VentilationGAS Piping ConnectionsWiring Positioning ThermostatsFan Control Low Voltage Thermostat with One HeaterLow Voltage Thermostat with Multiple Heaters 30 Low Voltage Thermostat with Multiple Heaters 60 Internal Wiring Diagram TransformerLadder Wiring Diagram FlameElectrical Connection to the Heater Operation and Maintenance Pressure Regulator Gas Outlet Outlet Pressure Turning Off the Heater Pressure SwitchCheck Gas Rate Complete Start-Up Instruction to the UserUser Instructions User InstructionsHeater Operation Lighting Instructions 11.4.1 To Turn On HeaterTo Turn the Heater Off Simple TroubleshootingSimple Troubleshooting Burner Faults Servicing Maintenance Checklist Venting and Air Intake PipeVicinity of the Heater Vehicles and OtherWhen installed Wall Tag Combustion Air IntakePipe Heat ExchangerTroubleshooting 13.1 General Troubleshooting For Automatic Ignition Burner Systems Conduct start-up procedure as shown on Page 29, SectionTroubleshooting for Flame Supervision System Troubleshooting for Gas Valves Troubleshooting for Flue BlowerReplacement Parts Burner ComponentsBurner Compartment Burner InjectorsIgnition Electrode and Flame Probe Louver and Louver Springs Re-usedFlue Blower Vertical Installation Axial Fan/Guard/Motor Assembly Ignition ControlLimit Switches Removal and Replacement Fan Removal and ReplacementTo Replace the Fan Assembly Specifications 15.1 Dimension Data Model UhaxsGeneral Technical Data Table All Models Technical Data Table All ModelsWarranty is Void if Roberts Gordon will not PAY forRoberts-Gordon Limitations on Authority RepresentativesPage Owner Warranty Registration Card Page Page Some objects can catch fire or explode when placed
Related manuals
Manual 60 pages 21.77 Kb

60, 30, 45, 125, 100 specifications

Roberts Gordon is a recognized leader in the manufacturing of innovative heating solutions, with a diverse product line including the 100, 125, 75, 45, and 60 series of radiant tube heaters. Each model is designed to meet specific heating needs while emphasizing efficiency, durability, and performance.

The Robert Gordon 100 series is known for its high efficiency and ability to provide consistent warmth in large industrial spaces. It features advanced infrared technology, which heats objects and surfaces directly, resulting in quicker temperature increases and enhanced comfort. This model is equipped with modulating burners that allow for optimal gas usage and can be easily integrated into existing systems.

The 125 series builds upon the efficiency of the 100 model while offering increased heating capacity. Its robust design ensures it can handle the demands of larger applications, such as warehouses and manufacturing facilities. With enhanced control options, users can tailor the heating output to match specific operational requirements, reducing energy consumption.

The 75 series offers a compact solution for smaller commercial spaces, providing a reliable heating source without taking up excessive floor space. Its lightweight design facilitates easy installation, while the modular approach allows for scalability to meet changing heating demands. This series emphasizes sustainability, utilizing advanced combustion technologies that minimize emissions.

For smaller applications, the 45 series stands out with its efficient heating capabilities in confined spaces. This series features simple, yet effective controls, enabling straightforward operation. The robust construction ensures durability, making it well-suited for different commercial environments, including retail settings or small workshops.

Finally, the 60 series combines the best features of the range with energy conservation as a primary focus. Its innovative design incorporates smart technology to monitor energy usage and optimize performance. The heaters are equipped with the latest in safety features, providing peace of mind for users.

Overall, Roberts Gordon’s radiant tube heaters showcase a commitment to high-quality heating solutions that cater to a variety of industrial and commercial applications. With energy efficiency, superior durability, and advanced heating technologies as core characteristics, Roberts Gordon remains a trusted choice for businesses looking to enhance their heating performance.