Snapper 030215-1 manual Stopping the Engine, Volt AC, 20 Amp, Duplex Receptacles

Page 10

Snapper 5600W Portable Generator

Stopping the Engine

1.Turn OFF and unplug all electrical loads from generator panel receptacles. NEVER start or stop engine with electrical devices plugged in and turned ON.

2.Let engine run at no-load for several minutes to stabilize internal temperatures of engine and generator.

3.Turn engine off according to instructions given in the engine operator’s manual.

4.Move fuel valve to “Off” position.

This receptacle powers 120/240 Volt AC, 60 Hz, single phase loads requiring up to 5,600 watts of power (5.6 kW) at 23.3 Amps for 120 Volts or 240 Volts.The outlet is protected by push–to–reset circuit breakers.

120 Volt AC, 20 Amp, Duplex Receptacles

Each duplex receptacle (Figure 6) is protected against overload by a push–to–reset circuit breaker.

Figure 6 — 120 Volt, 20 Amp Duplex Receptacle

RECEPTACLES

CAUTION

Receptacles may be marked with rating value greater than generator output capacity.

NEVER attempt to power a device requiring more amperage than generator or receptacle can supply.

DO NOT overload the generator. See “Don’t Overload Generator”.

120/240 Volt AC, 30 Amp, Locking Receptacle

Use a NEMA L14–30 plug with this receptacle. Connect a 4–wire cord set rated for 250 Volt AC loads at 30 Amps (or greater) (Figure 5).You can use the same 4–wire cord if you plan to run a 120 Volt load.

Figure 5 — 120/240 Volt AC, 30 Amp Receptacle

4-Wire Cord Set

240V

120V 120V

W (Neutral)

Use each receptacle to operate 120 Volt AC, single–phase, 60 Hz electrical loads requiring up to 2,400 watts (2.4 kW) at 20 Amps of current. Use cord sets that are rated for 125 Volt AC loads at 20 Amps (or greater).

Y (Hot)

X (Hot)

NEMA L14-30

Ground (Green)

10

Image 10
Contents Watt Generator Safety Rules Table of ContentsEquipment Description When Operating Equipment When Adding or Draining FuelWhen Starting Equipment When Transporting or Repairing EquipmentWhen Adjusting or Making Repairs to Your Generator When Testing for Engine SparkKnow Your Generator Install Wheel Kit AssemblyCarton Contents Unpacking the GeneratorAdd Engine Oil When Adding FuelBefore Starting the Engine Add FuelSystem Ground Using the GeneratorConnecting to a Building’s Electrical System Generator LocationStarting the Engine Connecting Electrical LoadsOperating Generator Do not Overload the GENERATOR. See Don’t Overload GeneratorVolt AC, 20 Amp, Duplex Receptacles ReceptaclesStopping the Engine 120/240 Volt AC, 30 Amp, Locking ReceptacleCapacity Power ManagementDont Overload Generator ExampleEngine Maintenance SpecificationsGeneral Maintenance Recommendations Generator MaintenanceEngine Storage StorageGenerator Storage Other Storage TipsTroubleshooting Problem Cause CorrectionAbout your equipment warranty Snapper Owner Warranty Policy Effective August 1Equipment Consumer Use Commercial Use Reglas DE Seguridad Tabla DE ContenidosDescripción DEL Equipo AdvertenciaCuando Opere EL Equipo Cuando Añada Combustible O Vacíe EL DepósitoCuando Ponga EN Funcionamiento EL Equipo Cuando Transporte O Repare EL EquipoCuando Ajuste O Haga Reparaciones a SU Generador PrecauciónCuando Pruebe LA Bujía DEL Motor Tapa del Depósito del Aceite Llene el motor con aceite Conozca SU GeneradorTomacorriente Dobles de 120 Voltios AC, 20 Amp Contenido de la Caja MontajeDesembalaje del Generador Instale el Juego de RuedasAgregue Combustible Antes DE Darle Arranque AL MotorAgregar Aceite al Motor Cuando Añada CombustibleConexión al Sistema Eléctrico de un Edificio USO DEL GeneradorTierra del Sistema Ubicación del GeneradorConexion De Cargas Electricas Operando EL GeneradorEncienda el Motor No Sobrecargue EL GENERADOR.Vea No Sobrecargue GeneradorVolt AC, 20 Amp, Receptáculos Dobles Receptáculos PrecauciónParado Del Motor 120/240 Voltios AC, 30 Amp, Receptáculo de SeguridadControl de la Energía No Sobrecargue GeneradorCapacidad EjemploMantenimiento del Motor EspecificacionesRecomendaciones Generales DE Mantenimiento Mantenimiento del GeneradorAlmacenando el Generador Diagnositicos DE AveríasAlmacenamiento Almacenando el MotorGarantía Limitada Efectiva desde el 1 ro de AgostoEquipo Para Uso Del Consumidor Para Uso Comercial Acerca de la seguridad de su equipo