Athena Technologies OTC25 N, P OTC25 L Limit Controller Normal Operation, Deviation Band Alarm

Page 8

OTC25 N

Operation

Deviation Band Alarm

A Deviation Band is a pre-set number of degrees, plus and minus, around the Setpoint Value, ex. +10° F. A Deviation Band Alarm provides an indication to the operator that the Actual Temperature has either exceeded or dropped below the chosen

deviation. This parameter can be turned off or adjusted from 1 to 252° F (1 to 140° C). When the process variable is out- side the deviation band, the alarm is indicated by flashing the display (regardless of whether setpoint or actual temperature is displayed) and the optional alarm output is activated.

Display Units

This allows the operator to have the display indicate either degrees Fahrenheit or degrees Celsius.

OTC25 L

Operation

OTC25 L Limit Controller

Normal Operation

The factory default display setting of the OTC25 L is for Actual

Temperature . The default display may be changed to

setpoint temperature by selecting Limit Setpoint at the

Default Display parameter selection.

When the Default Display is changed to Limit Setpoint, the limit

setpoint temperature may be adjusted by using the Raise or

Lower keys. The limit setpoint is adjustable from 32 to 905° F (0 to 485° C).

When the Default Display setting is “Actual” , adjustment of the Limit Setpoint may only be accomplished by pressing the

Parameter Key momentarily to switch the display to Limit

Setpoint, and then using the Raise or Lower Keys to change the Limit Setpoint Value. The display will automatically revert back to “Actual” five seconds after the last keypress.

Parameter Configuration

Your OTC25 L controller’s parameter selections are explained on the next page, with default settings shown in Figure 5b.

To enter the configuration menu, press and hold the Parameter key for 10 seconds until the display changes to the parame- ter mode. Press the Parameter key again to index through the available parameters. Pressing the Parameter Key for 3 seconds or allowing 60 seconds of inactivity will cause the OTC25 L to exit the menu system and return to normal operating mode.

5

Image 8
Contents Series OTC25 N/L/P Features Safety IntroductionNema 4X Front Bezel, Splash-Proof and Resistant to Dust Approvals UR, cUR, CEContents Mounting InstallationPre-Installation Instructions Wiring Athena Series OTC25 Digital Temperature ControllerPower On When power is first applied to the OTC25, all segmentsDefault Display Parameter DescriptionsControl Hysteresis Display OffsetOTC25 N On/Off Temperature Controller Normal Operation Parameter ConfigurationDeviation Band Alarm Parameter Key momentarily to switch the display to LimitOTC25 L Limit Controller Normal Operation Display UnitsAutomatic Startup Reset Limit SetpointOTC25 P PID Temperature Controller Normal Operation Parameter Key momentarily to switch the display toOTC25 P Operation Reset Output 2 ConfigurationProportional Band RateCalibration Calibration ProcedureCalibration Calibration Error Codes Repeat for the upper reference pointBUYER’S Remedy is Limited to Either i Repair or Warranty/Repair InformationTwo-Year Limited Warranty Unit Repairs Technical Specifications Control CharacteristicsOperating Limits Sensor RangeInput Source Temperature Sensor Output Source Power to HeaterPage OTC25-NOTC25-POTC25-L Page OTC25-NOTC25-POTC25-L Page For technical assistance, call toll free