Page 7
Figure 9.
REMOVE FLOW VALVE BEFORE DRILLING THE NPT PORT

7

Maintenance

MAINTENANCE INSTRUCTIONS

It is recommended that you check the following items at least every six months and at the beginning of every swimming season.

CAUTION

REMOVE THE FLOW VALVE ASSEMBLY WHEN DRILLING THE HOLE TO INSTALL A PRV. OTHERWISE, YOU WILL DRILL INTO THE VALVE ASSEMBLY.

1.Examine the venting system. Make sure there are no ob- structions in the flow of combustion and ventilation air.

2.Visually inspect the main burner and the pilot burner flame. The normal color of the flame is blue. When flame appears yellow, burners should be inspected and cleaned; see Figure 8.

3.Keep the heater area clear and free from combustibles and flammable liquids.

Blue Flame

Figure 7.

Figure 8.

Pressure Relief Valve

In some installations, a pressure relief valve (PRV) is required on the MiniMax CH heater. To install a PRV, carefully drill a 3/8 in. hole in center of 3/4 in. NPT port (on main header) being careful to drill only thru wall at bottom of 3/4 in. NPT port and no deeper—now thread

in the 3/4 NPT PRV. (Sold separately.)

FOR PRV INSTALLATION DRILL THRU THE NPT PORT

ENERGY SAVING TIPS

1.If possible, keep pool or spa covered when not in use. This will not only cut heating costs, but also keep dirt and debris from settling in the pool and conserve chemicals.

2.Reduce the pool thermostat setting to 78° F. or lower. This is accepted as being the most healthy temperature for swimming by the American Red Cross.

3.Use an accurate thermometer.

4.When the proper maximum thermostat settings have been determined, tighten the thermostat knob stopper.

5.Set time clock to start circulation system no earlier than daybreak. The swimming pool loses less heat at this time.

6.For pools that are only used on the weekends, it is not necessary to leave the thermostat set at 78° F. Lower the temperature to a range that can be achieved easily in one day. Generally, this would be 10° F. to 15° F., if pool heater is sized properly.

7.During the winter or while on vacation, turn the heater off.

8.Set up a regular program of preventative maintenance for the heater each new swimming season. Check heat exchanger, controls, burners, operation, etc.

SPRING AND FALL OPERATION

If the pool is being used occasionally, do not turn the heater completely off. Set the thermostat down to 65° F. This will keep the pool and the surrounding ground warm enough to bring the pool up to a comfortable swimming temperature in a shorter period of time.

WINTER OPERATION

CAUTION

OPERATING THIS HEATER CONTINUOUSLY AT WATER TEMPERATURE BELOW 68° F. WILL CAUSE HARMFUL CONDENSATION AND WILL DAMAGE THE HEATER AND WILL VOID THE WARRANTY.

If the pool won't be used for a month or more, turn the heater off at the main gas valve. For areas where there is no danger of water freezing, water should circulate through the heater all year long, even though you are not heating your swimming pool. The MiniMax CH should not be operated out doors at temperatures below 0° F. for propane and -20° F. for natural gas. Where freezing is possible, it is necessary to drain the water from the heater. This may be done by opening the drain valve located at the inlet/outlet header (see Figure 9.) allowing all water to drain out of the heater. It would be a good practice to use compressed air to blow the water out of the heat exchanger. (See additional notes under Important Notices in Introduction on page 3.)

Rev. C 1-22-04

P/N 472128

Image 7
Contents What to do if YOU Smell GAS For Your Safety Read Before OperatingFor additional free copies of this manual call 800 Table of Contents Important Notices Code RequirementsOperation contd Warranty InformationSafety Rules Product IdentificationLighting Instructions For Your Safety Read Before LightingTo Turn OFF GAS to Heater Operating Controls Dual Temperature Control SystemWinter Operation Maintenance InstructionsEnergy Saving Tips Spring and Fall OperationAlkalinity High Low Maintenance contdChemical Balance If pH becomes too high over alkaline, it has these effectsSpecifications Installation InstructionsPlumbing Connections Installation contdPlumbing Insulating the High Limits Water ConnectionsGAS Connections GAS Line InstallationsRegulated Manifold Pressure Test Ventilation Outdoor Installation onlyFront Stack Type Indoor Draft Hood KIT Electrical MiniMax CH Millivolt Wiring DiagramHeater Short Cycling Rapid On and Off Operation Troubleshooting GeneralMinimax CH Heater ALL Models MiniMax CH Parts List MiniMax CH Parts List, contd Rev. C MiniMax CH 150 IID Model To Turn OFF GAS to Appliance Operating InstructionsOperation Safety Lockout Thermostat Knob Stopper Indicator Light DescriptionHeat Heat Troubleshooting ControlsTroubleshooting Controls Transformer Wiring Instruction InstallationRegulated Manifold Pressure Test Diagram Electronic Ignition WiringWire Remote Remote Switch Dual Therm IID onlyMinimax CH Heater 150 IID Model MiniMax CH Parts List 150 IID Model MiniMax CH Parts List 150 IID Model, contd Rev. C Pentair Pool Products, Inc
Related manuals
Manual 36 pages 27.89 Kb

CH specifications

Pentair CH is a leading provider of advanced water treatment solutions, known for its innovative approaches in delivering high-quality water through cutting-edge technologies. Designed for both residential and commercial use, Pentair CH focuses on enhancing water quality and efficiency while promoting sustainability.

One of the standout features of Pentair CH products is their robust filtration systems. The company's advanced multi-stage filtration technology ensures that water is treated effectively, removing impurities and contaminants that can affect taste, odor, and safety. The filtration process often includes a combination of activated carbon, reverse osmosis, and UV sterilization, allowing for comprehensive protection against a wide range of pollutants.

Moreover, the Pentair CH technology is designed with user convenience in mind. Many models come equipped with smart features that allow users to monitor water quality and consumption through mobile apps. This connectivity not only helps in tracking usage patterns but also alerts users about maintenance needs, ensuring optimal performance and longevity of the system.

Energy efficiency is another hallmark of Pentair CH appliances. The company emphasizes the development of energy-saving designs that minimize electricity consumption while maximizing output. This commitment to environmental stewardship is reflected in its eco-friendly materials and manufacturing processes, making Pentair CH an excellent choice for those looking to reduce their ecological footprint.

Durability and reliability are key characteristics of Pentair CH products. The systems are engineered to withstand various water conditions and climatic changes, providing consistent performance over an extended lifespan. The use of high-grade materials and rigorous testing standards further underscores the brand’s commitment to quality.

Pentair CH also offers a range of customized solutions tailored to meet the specific needs of different customers. Whether addressing the requirements of a large commercial facility or a family home, the flexibility in product design ensures that users can find the perfect fit for their water treatment needs.

In conclusion, Pentair CH stands out in the water treatment industry with a comprehensive product lineup characterized by state-of-the-art filtration technologies, user-centric design, energy efficiency, durability, and flexibility. These features combine to provide users with safe, clean, and great-tasting water, reinforcing Pentair CH’s position as a trusted leader in water treatment solutions.