Raypak 155C Troubleshooting Honeywell S8600, Electrical Electronic Ignition IID, High Voltage

Page 28

ELECTRICAL (ELECTRONIC IGNITION IID)

Intermittent Pilot System

TROUBLESHOOTING HONEYWELL S8600

WARNING

HIGH VOLTAGE

For qualified Technicians ONLY

NOTE: Some heaters may be equipped with an ignition module that shuts off pilot gas if pilot fails to light. To reset, interrupt power to heater.

START

TURN GAS SUPPLY OFF.

TURN THERMOSTAT

(CONTROLLER) TO CALL

FOR HEAT

POWER TO MODULE

(24 V NOMINAL)

YES

NOTE:Before troubleshooting, familiarize yourself with the start-up and checkout procedure.

NO

Check line voltage power, low voltage transformer, limit controller, thermostat

(controller) and wiring.

SPARK ACROSS

IGNITER/SENSOR GAP

YES

NO

Pull ignition lead and check spark at module.

Spark Okay?

YES

Check ignition cable, ground wiring, ceramic insulator and gap, and correct.

Check boot of the ignition cable for signs of melting or buckling. Take protective action to shield cable and boot from excessive temperatures.

TURN GAS SUPPLY ON

PILOT BURNER LIGHTS?

YES

SPARK STOPS WHEN

PILOT IS LIT?

YES

MAIN BURNER LIGHTS?

YES

SYSTEM RUNS UNTIL CALL FOR HEAT ENDS?

YES

 

 

• Check that all manual gas valves are open, supply tubing and pressures are good,

NO

 

 

 

 

and pilot burner orifice is not blocked.

 

 

Check electrical connections between module and pilot operator on gas control.

Check for 24 Vac across PV-MV/PV terminals on module. If voltage is okay, replace gas control; if not, replace module.

 

 

NOTE:If S8600H goes into lockout, reset system. Lockout is used on L.P.G. models.

 

 

 

 

 

 

 

 

NO

 

Check continuity of ignition cable and ground wire.

 

 

 

Clean flame rod.

 

 

Check electrical connections between flame rod and module.

 

 

Check for cracked ceramic flame rod insulator.

 

 

Check that pilot flame covers flame rod and is steady and blue.

 

 

Adjust pilot flame.

 

 

If problem persists, replace module.

 

 

 

 

 

 

Check for 24 Vac across MV-MV/PV terminals. If no voltage, replace module.

NO

 

 

Check electrical connections between module and gas control. If okay, replace

 

 

 

 

gas valve or gas control operator, i.e. pilot gas valve, flow switch etc.

NOTE: IF S8600H goes into lockout, reset system.

NO

• Check continuity of ignition cable and ground wire.

 

NOTE: If ground is poor or erratic, shutdowns may occur occasionally even though operation is normal at the time of checkout.

Check that pilot flame covers flame rod and is steady and blue.

If checks are okay, replace module.

CALL FOR HEAT ENDS

SYSTEM SHUTS OFF?

YES

TROUBLESHOOTING

ENDS

NO

 

Check for proper thermostat (controller) operation.

 

 

 

Remove MV lead at module; if valve closes, recheck temperature controller and

 

 

 

 

 

wiring; if not, replace gas valve.

Repeat procedure until troublefree operation is obtained.

28

Image 28
Contents Versa What to do if YOU Smell GASContents Part TWO INSTALLATION/SERVICE InstructionsSTART-UP Procedures Before START-UPBurners WaterMillivolt System Operating Instructions Electronic Ignition SystemsIID After START-UP Water Pressure SwitchVisual Inspection Maintenance and Care Procedures Basic Tips if Heater will not FirePool & SPA Water Chemistry Automatic Chlorinators and Chemical FeedersCold Weather Operation Pressure Switch Compression Fitting Return HeaderWinterizing the Pool & SPA Heater Installation Instructions General SpecificationsReceiving Equipment Clearances High Wind Conditions Outdoor Units only Combustion AIR Indoor Units only Indoor HeatersVenting Connections Z223.1 Vent PipingGAS Supply Connections Pipe Sizing for GAS ConnectionsPlumbing for Water Connections Location Companion Flange ConnectionsAuxiliary Bypass Valve Adjustment Pressure Relief Valve InstallationUnitherm Governor Operation Internal Automatic BY-PASS ValveElectrical Wiring Millivolt SystemElectronic Intermittent Ignition Device System IID Honeywell Intermittent Ignition DeviceWiring Diagram KEY ANSI/NFPAWiring Diagram Millivolt Units Fig. #2182eWiring Diagram 152148 Model 155 IID Controls / Adjustments / Replacements Temperature ControlsGeneral Location of Controls View of Heater from Front View of Heater from BackFlame ROLL-OUT Safety Switch Pressure SwitchHigh Limits Pilot Removal and Cleaning Burner Drawer RemovalGAS Valve Removal Main Burner and Orifice RemovalUnitherm Governor U.G. Replacement Control Immersion Well ReplacementHeat Exchanger Removal Tube Replacement Procedure Desooting ProcedureCombustion Chamber Removal Refractory Panels TOP ViewTrouble Shooting Guide Electrical Millivolt Electrical Electronic Ignition IID Troubleshooting Honeywell S8600High Voltage Electrical Solid State Thermostat IID Voltage Between 21.5-28.5 Voltage Outside Range 21.5-28.5Replacement Parts List RAYPAK, INCPage Page Page Warranty Exclusion

155C specifications

The Raypak 155C is a versatile and efficient heater designed for both residential and commercial applications. Renowned for its robust construction and reliable performance, this unit is an excellent choice for pool and spa heating as well as for providing comfortable ambient temperatures in enclosed or outdoor spaces.

One of the standout features of the Raypak 155C is its innovative copper heat exchanger, which is designed for maximum heat transfer efficiency. This technology allows for rapid heating capabilities, ensuring that water reaches the desired temperature quickly and effectively. The heat exchanger is also resistant to corrosion, thanks to its durable design, prolonging the unit's life and maintaining performance over time.

Designed with user convenience in mind, the Raypak 155C features an intuitive digital control system. This user-friendly interface allows for easy temperature adjustments and monitoring, giving users precise control over their heating requirements. An integrated diagnostic system is also included, providing real-time feedback on the heater's performance and alerting users to any potential issues, which helps in proactive maintenance.

Incorporating advanced safety features, the Raypak 155C includes a high limit switch and a water flow switch, ensuring safe operation at all times. These safety mechanisms prevent overheating and dry firing, protecting both the heater and the connected plumbing system.

The Raypak 155C is engineered for energy efficiency, meeting and exceeding industry standards. With a compact design, it ensures easy installation and integration into existing setups, making it a favorable choice for various applications. Its quiet operation adds to user comfort, allowing it to be installed in residential settings without causing disturbances.

With a heating capacity of 155,000 BTU, the Raypak 155C is capable of effectively heating larger pools and spas, making it ideal for homes with extensive water features. The heater is designed to run on natural gas or propane, providing flexibility based on user preferences and availability.

Overall, the Raypak 155C combines state-of-the-art technology with practical features, making it one of the top choices for those looking to enhance their pool experience or improve comfort levels in their outdoor areas. Its reliability, efficiency, and user-friendly features make it a valuable investment for any property.