Raypak 155C Maintenance and Care Procedures, Basic Tips if Heater will not Fire

Page 7

SECTION 3 / MAINTENANCE AND CARE PROCEDURES

To be followed one month after start-up and then semi-annually.

1.Inspect top of heater and draft hood for soot, (a sticky black substance around finned tubes and "V" baffles), and open flue gas passageways.

CAUTION: Soot may be combustible. Wet sooted surfaces completely prior to cleaning. Do not use steel wire brush.

2.Clean main burners and pilot burner of dust and lint.

3.Inspect and operate all controls, gas valve and pressure relief valve.

4.Make a visual check of the burner and pilot flame. Flame pattern on the main burner and pilot is indicated in the previous illustration. Yellow flame means restriction of the air openings. Lifting or blowing flame indicates high gas pressure. Low flame means low gas pressure. Should this occur, shut the heater off and contact your gas supplier or qualified service agency.

5.On indoor heaters, clean room intake open- ings to assure adequate flow of combustion and ventilation air.

CAUTION: Combustion air must not be contaminated by corrosive chemical fumes which can damage the heater and void the warranty.

6.Keep area around heater clear and free from combustible materials, gasoline and other flammable and corrosive vapors and liquids.

BASIC TIPS IF HEATER WILL NOT FIRE:

1.If you have no electrical power; it may be your "circuit breakers" have tripped. Try re-setting them.

2.If you have electrical power but the heater will not fire

check the following:

3.The time clock must be moved to the "ON" position.

4.Your pump strainer basket may be full. If so remove debris.

5.Your filter may be dirty. If so, backwash or clean filter. (To tell if your filter is dirty, the gauge pressure will be higher than usual).

6.The pump may have lost it's prime. It may be running dry, check the pressure gauge on the filter. If there is no pressure; then you are not moving water (or your gauge is broken). Try to get the pump to run at it's normal flow rate.

POOL & SPA WATER CHEMISTRY

Chemical imbalance can cause severe damage to your heater and associated equipment. Maintain your water pH between 7.4 and 7.8 and total alkalinity between 100 and 150 p.p.m. If the mineral content and dissolved solids in the water become too high, scale forms inside the heat exchanger tubes, reducing heater efficiency and also damaging the heater. If the pH drops below 7.2, the heater will be severely dam- aged. This will result in corrosion of the heat ex- changer. Heat exchanger damage resulting from chemical imbalance is not covered by the warranty.

AUTOMATIC CHLORINATORS AND CHEMICAL FEEDERS

All chemicals must be introduced and completely diluted into the pool or spa water before being circu- lated through the heater. Do not place chlorine tablets or bromine sticks in the skimmer. High chemical concentrations will result when the pump is not running (i.e. overnight).

Chlorinators must feed downstream of the heater and have an anti-siphoning device to prevent chemical back-up into the heater when the pump is shut off.

NOTE: High chemical concentrates from feeders and chlorinators that are out of adjustment will cause very rapid corrosion to the heat exchanger in the heaters. Such damage is not covered under the warranty.

7

Image 7
Contents What to do if YOU Smell GAS VersaPart TWO INSTALLATION/SERVICE Instructions ContentsWater START-UP ProceduresBefore START-UP BurnersMillivolt System Operating Instructions Electronic Ignition SystemsIID After START-UP Water Pressure SwitchVisual Inspection Automatic Chlorinators and Chemical Feeders Maintenance and Care ProceduresBasic Tips if Heater will not Fire Pool & SPA Water ChemistryCold Weather Operation Pressure Switch Compression Fitting Return HeaderWinterizing the Pool & SPA Heater Installation Instructions General SpecificationsReceiving Equipment Clearances High Wind Conditions Outdoor Units only Combustion AIR Indoor Units only Indoor HeatersVenting Connections Vent Piping Z223.1Pipe Sizing for GAS Connections GAS Supply ConnectionsCompanion Flange Connections Plumbing for Water Connections LocationInternal Automatic BY-PASS Valve Auxiliary Bypass Valve AdjustmentPressure Relief Valve Installation Unitherm Governor OperationHoneywell Intermittent Ignition Device Electrical WiringMillivolt System Electronic Intermittent Ignition Device System IIDANSI/NFPA Wiring Diagram KEYFig. #2182e Wiring Diagram Millivolt UnitsWiring Diagram 152148 Model 155 IID View of Heater from Front View of Heater from Back Controls / Adjustments / ReplacementsTemperature Controls General Location of ControlsFlame ROLL-OUT Safety Switch Pressure SwitchHigh Limits Main Burner and Orifice Removal Pilot Removal and CleaningBurner Drawer Removal GAS Valve RemovalUnitherm Governor U.G. Replacement Control Immersion Well ReplacementHeat Exchanger Removal Refractory Panels TOP View Tube Replacement ProcedureDesooting Procedure Combustion Chamber RemovalTrouble Shooting Guide Electrical Millivolt Electrical Electronic Ignition IID Troubleshooting Honeywell S8600High Voltage Voltage Between 21.5-28.5 Voltage Outside Range 21.5-28.5 Electrical Solid State Thermostat IIDRAYPAK, INC Replacement Parts ListPage Page Page Warranty Exclusion

155C specifications

The Raypak 155C is a versatile and efficient heater designed for both residential and commercial applications. Renowned for its robust construction and reliable performance, this unit is an excellent choice for pool and spa heating as well as for providing comfortable ambient temperatures in enclosed or outdoor spaces.

One of the standout features of the Raypak 155C is its innovative copper heat exchanger, which is designed for maximum heat transfer efficiency. This technology allows for rapid heating capabilities, ensuring that water reaches the desired temperature quickly and effectively. The heat exchanger is also resistant to corrosion, thanks to its durable design, prolonging the unit's life and maintaining performance over time.

Designed with user convenience in mind, the Raypak 155C features an intuitive digital control system. This user-friendly interface allows for easy temperature adjustments and monitoring, giving users precise control over their heating requirements. An integrated diagnostic system is also included, providing real-time feedback on the heater's performance and alerting users to any potential issues, which helps in proactive maintenance.

Incorporating advanced safety features, the Raypak 155C includes a high limit switch and a water flow switch, ensuring safe operation at all times. These safety mechanisms prevent overheating and dry firing, protecting both the heater and the connected plumbing system.

The Raypak 155C is engineered for energy efficiency, meeting and exceeding industry standards. With a compact design, it ensures easy installation and integration into existing setups, making it a favorable choice for various applications. Its quiet operation adds to user comfort, allowing it to be installed in residential settings without causing disturbances.

With a heating capacity of 155,000 BTU, the Raypak 155C is capable of effectively heating larger pools and spas, making it ideal for homes with extensive water features. The heater is designed to run on natural gas or propane, providing flexibility based on user preferences and availability.

Overall, the Raypak 155C combines state-of-the-art technology with practical features, making it one of the top choices for those looking to enhance their pool experience or improve comfort levels in their outdoor areas. Its reliability, efficiency, and user-friendly features make it a valuable investment for any property.