PLUMBING FOR WATER CONNECTIONS

HEATER LOCATION-Relative to the pump and filter

The RP 2100 heater requires water flow and positive pressure to fire and operate properly. It must therefore be installed downstream of the discharge side of the filter pump. A typical installation is plumbed as follows:

1.The inlet side of the filter is plumbed directly to the discharge side of the filter pump;

2.The outlet side of the filter is then plumbed to the inlet of the heater; and

3.The outlet of the heater is plumbed to the return line to the pool or spa. The pump, filter and heater are

thus plumbed in series.

Plumbing from the heater back to the pool must not have any valves or restriction that could prevent flow when the pump is operating.

CAUTION: An additional source of heated water, i.e. a solar system, must be connected to the main line ahead of the heater inlet pipe in order for it to act as the primary heat source. If the primary system provides adequate heat to maintain set-point, the RP2100 heater will not fire. Be advised that the RP2100 control panel will then display sensed water temperatures downstream of the primary heating system, rather than the temperature of the water exiting the pool.

Heater must be located so that any water leaks will not damage the structure of adjacent area. PVC pipe may be glued directly into header unions.

FLOW RATES

MODEL

PIPE SIZE

MIN.GPM

*MAX.GPM

185

1-1/4"-1-1/2" - 2

20

125

265

1-1/4"-1-1/2" - 2

25

125

335

1-1/4"-1-1/2" - 2

35

125

405

1-1/4"-1-1/2" - 2

40

125

*When flow rates exceed maximum GPM an external auxiliary bypass valve is required. See external bypass valve section for details.

ASME-Cast Iron

POLYMER HEADERS

CONNECTIONS (POLYMER HEADER)

Before attaching the 2-inch unions to the inlet/outlet header, make sure the o-rings are properly seated in the grooves. Use AquaLube or equivalent non-petroleum based lubricant on the o-ring. Tighten the unions hand tight. Glue PVC piping directly to the unions.

INLET/OUTLET HEADER (Polymer)

Flange Gasket

Header Flange (CPVC)

Header Flange Nut

(CPVC)

Inlet

Fig. #2002.1

High temperature CPVC Header Flanges and header Flange Nuts are provided. If there is any possibility of back- siphoning when the pump stops, it is suggested that a check valve (or valves) also be installed in the system.

19

Image 19
Contents What to do if YOU Smell GAS Installation and Operating InstructionsPage Contents For Your Safety Read Before Operating START-UP ProceduresBefore START-UP Burners Water Lighting Instructions Millivolt SystemTo Turn OFF GAS to Appliance What to do if YOU Smell GAS Electronic Ignitions SystemsOperating Instructions Visual Inspection Maintenance and Care ProceduresWater Pressure Switch After START-UPAutomatic Chlorinators Chemical Feeders Pool & SPA Water ChemistryCold Weather Operation Winterizing the Pool & SPA Heater Receiving Equipment General SpecificationsStandardunit Asme Unit Installation Instructions Outdoorheaters Installations onlyOutdoor KIT Includes Indoor HeaterIndoor KIT Includes Securing the TOP Panel Cover Indoor KIT only Installing the Clips Indoor & Outdoor KitsSecuring the TOP Panel Cover Outdoor KIT only Installing the TOP Cover Outdoor KIT only Combustion AIR Indoor Units Only Specifications and DimensionsGAS Supply Connections Vent PipingGAS Pressure Regulator GAS Pressure Adjustment LocationsPipe Sizing for GAS Connections Flow Rates Plumbing for Water ConnectionsUnitherm Governor Operation Connections Asme ModelsAuxiliary Bypass Valve Adjustment External Auxiliary Bypass Valve Where RequiredHeat Exchanger Pressure Drop Tables For Asme Models call your factory representative Millivolt System Electrical WiringElectronic 240V Wiring Transformer Wiring 120V WiringIndependently Wiring Diagram Millivolt Units Mechanical Thermostat Wiring Diagram IID Units atmospheric Wiring Diagram IID Units Low NOx Control Panel Removal General Location of Controlscontrols and AdjustmentsMillivolt Controls Thermostat Control Operation Digital Thermostat ControlsFahrenheit vs Centigrade Reading a Fault DiagnosticsDisplay Definition Activating the Remote Remote Control Installation and OperationRemote Operation Wire Remote Control On-Off Remote Control WiringPilot Safety Electronic Pressure SwitchFlame ROLL-OUT Safety Switch Pilot Safety MillivoltMain Burner and Orifice Removal Pilot Removal and CleaningBurner Drawer Removal GAS Valve RemovalUnitherm Governor U.G. Replacement TubecleaningprocedureDesootingprocedure Immersion Well ReplacementOperation START-UP ProceduresBurneradjustment Flame ROLL-OUT Safety SwitchCombustion FAN Removal Pilot RemovalMechanicalforqualifiedservicepersonnelonly Trouble Shooting GuideRaypak Pool or SPA Heater Electrical Check with MV GAS Valve Electrical Standing Pilot MillivoltFor qualified Technicians only Electrical Electronic Ignition IID TroubleshootingDigital Control Logic Flow Chart RAYPAK, INC Replacement Parts ListEastman Avenue Oxnard, CA For Canada Page Pilot Assemblies Page Page Page Page Page

P-R185B To P-R405B, C-R185B To P-R405B, P-R185BL To P-R405BL, C-R185BL To C-R405BL, RP2100 specifications

Raypak offers a comprehensive line of boilers and water heaters, notably the P-R185B to P-R405B and C-R185B to P-R405B series, along with the RP2100 model. These products are engineered for efficiency, reliability, and performance in both residential and commercial applications.

The P-R185B to P-R405B series features a range of input capacities from 185,000 to 405,000 BTU/h, making them suitable for various heating requirements. The P-R series is equipped with Raypak's patented Cupro-Nickel heat exchanger, which offers superior corrosion resistance and extended life in challenging water conditions. These units also utilize a sealed combustion system, allowing for efficient operation and reduced energy consumption by drawing air from outside the building.

The C-R185B to P-R405B boilers are specifically designed for commercial applications where reliability is critical. They incorporate similar features to the standard P-R series and are built to handle higher heating demands, making them ideal for larger facilities. The C-R series models are recognized for their durable construction and advanced control systems, offering precise temperature management and enhanced performance.

In addition to these series, the P-R185BL to P-R405BL and C-R185BL to C-R405BL models feature a low-NOx design to comply with stringent environmental regulations. This means they produce lower nitrogen oxides, making them an environmentally friendly option without sacrificing performance.

The RP2100 is another standout model, known for its robust design and cutting-edge technology. It boasts a high efficiency rating and is equipped with an intuitive digital control system, allowing users to monitor and adjust settings with ease. The RP2100 also features a modulating burner system, which adjusts the flame based on the heating demand, optimizing fuel usage and minimizing operational costs.

All Raypak models are designed with safety in mind, incorporating multiple safety features like thermal shutdowns and pressure relief valves. Their compact dimensions make installation straightforward, and the low maintenance requirements ensure longevity and consistent performance.

In summary, Raypak's P-R185B to P-R405B, C-R185B to P-R405B, P-R185BL to P-R405BL, and RP2100 series represent a commitment to quality and innovation in heating solutions, providing efficient and reliable options for both residential and commercial applications.