Powermate PM401211 owner manual Symptom

Page 35

TROUBLESHOOTING

SYMPTOM

Low generator output voltage

Overspeed light stays lit

Underspeed light stays lit

Overcrank light stays lit Not In Auto light stays lit

Low oil pressure light stays lit

Low battery light stays lit

High engine temperature light stays lit

 

POSSIBLE CAUSE

 

CORRECTIVE ACTION

 

Low engine speed

 

• Verify correct engine speed. Remove excess

 

 

 

loads or adjust speed as required.

 

Excitation capacitor failure

 

• Contact a qualified generator dealer for service

 

 

 

assistance.

 

Generator diode or varistor failure

 

• Contact a qualified generator dealer for service

 

 

 

assistance.

 

Shutdown due to high engine

 

• Verify correct engine speed setting. Adjust

 

speed

 

engine speed as required.

 

Shutdown due to low engine

 

• Reduce loads connected to generator

 

speed

 

 

 

 

 

• Check engine speed setting at no load.

 

 

 

Adjust as required.

 

Failure to start

 

• See "Engine cranks without starting"

 

Generator not set for unattended

 

• Place mode switch into AUTO position if

 

 

 

operation

 

automatic function is required

 

Shutdown due to low engine oil

 

• Check engine oil level.

 

pressure

 

 

 

 

 

• Verify correct type of engine oil for ambient

 

 

 

temperature conditions

 

Low battery

 

• Test battery. Replace as necessary.

 

 

 

• Ensure charger is plugged into GFCI

 

 

 

receptacle

 

 

 

• Check for tripped GFCI receptacle. Reset if

 

 

 

required.

 

 

 

• Check for tripped breaker in branch circuit

 

 

 

supplying GFCI. Reset if required.

 

 

 

• Check all charger cable connections for

 

 

 

cleanness and tightness.

 

 

 

• Check battery charger inline fuse

 

 

 

• Check charger lights to verify correct

 

 

 

operation. See Table A, Page 29.

 

Blown charger circuit fuse

 

• Check engine alternator fuse

 

Shutdown due to high engine

 

• Allow engine to cool, then restart

 

temperature

 

 

 

 

 

• Decrease loads on generator

 

 

 

• Check enclosure openings for blockage

 

 

 

• Check oil cooler for blockage

200-2341

35

Image 35
Contents Models PM401211 PM400911 Table of Contents General Safety Guidelines General Safety Guidelines Unpacking Instruction S Installation Plannin GIntroductio N Generator Location Utomatic Transfer Switch Placement and Anchoring Generator InstallationInstallation Drawings AIN Line Output Powe R Electrical HookupGfci Circuit Supply Generator Start Signal12KW Wiring Diagram CP200 Controller Consumption Require Ments Fuel SpecificationsNatural Gas NG Fuel HookupPropane Vapor LPG Connection Battery Requirement SBattery Placement Lubrication Nnection con tFirst Time Startup PM401211 PM400911 Generator SpecificationsFuel Alternator SpecificationsIdentificatio N Generator FeatureGenerator Operation Control Panel FeaturesControl Panel Switches Shutdown Starting the GeneratorCyclic Crank RUN StateFaults Status IndicatorsMaintenance Crankcase pressure can blow hot engine oil out Engine OIL Level Chec KEngine OIL Cooler Inspection ND Clean INGEngine OIL and OIL Filter HangeEngine AIR Filter Change Battery Maintenanc ETT ERY Maintenanc E con t Fig. G Spark Plug CheckFig. GG Spark Arrestor CleaningEnclosure and Site Governor Speed AdjustmentFuel System Inspection Adjustmen TValve Clearance Check Symptom Possible Cause Corrective Action TroubleshootingSymptom Parts Drawing Exhaust System Parts Drawing Enclosure Parts Drawing LID Assembly Parts Drawing Generator Parts Drawing -H2X Breakdown Parts Drawing Engine Panel END Assembly Parts Drawing Control Panel Breakdown Parts Drawing Battery Hold Down 200-2341 200-2341 Coverage Contact the Coleman Powermate Product Service Department AT 200-2341