ENCLOSURE AND SITE

Proper cooling of the generator is vital to maintain performance and prevent equipment failure. Blocked cabinet openings or other airflow obstructions are potential fire hazards and can cause failures. Periodically inspect generator cabinet openings and the engine oil cooler for blockages. Do not allow leaves, grass, dirt, snow or other objects to build up around the cabinet. Keep plants and other landscaping groomed to allow a minimum of three (3) feet of open space around all sides of the generator. Do not place a cover over the generator.

DANGER

Generator exhaust air contains carbon monoxide, a deadly odorless, colorless and tasteless gas. Breathing carbon monoxide causes severe nausea, fainting or death. Do not allow exhaust air to enter a building through windows, doors, air intakes or other means. Avoid breathing exhaust air while operating or servicing the generator set. The engine exhaust from this product contains chemicals known to the State of California to cause cancer, birth defects, or other reproductive harm.

CAUTION

Covering or restricting the air passages on the generator will cause the unit to overheat and may create a fire hazard. Do not allow snow or leaves to cover enclosure openings.

Leave a three foot open area around all sides of the unit. Do not plant trees or plants which may grow within three feet of the unit.

Unit should be located to prevent combustible material from accumulating against the generator.

The generator MUST be installed outdoors.

GOVERNOR SPEED ADJUSTMENT

The engine governor is set at the factory to maintain generator output frequency within specifications and is readjusted if required during installation. However, engine wear may cause frequency to vary as the generator accumulates hours. Periodic checking and adjustment of generator frequency by a qualified generator technician is recommended as outlined in the table on page 25. If speed adjustment is necessary, follow the listed procedure to set the correct engine speed.

CAUTION

This adjustment should only be performed by trained personnel. If incorrect adjustments are made, the unit may fail to operate or operate inefficiently.

1.Start the engine by moving the control panel Mode switch to the RUN position and let the generator run for a minimum of five minutes with no electrical loads connected.

2.Once the generator is warmed up, check the generator output frequency with a suitable meter. Normal unloaded frequency is approximately 62.5 Hz.

3.Adjust engine speed to 62.5 as required by turning the engine governor screw, shown in Fig K. Turn the screw clockwise to increase frequency and counterclockwise to decrease frequency.

4.Turn the engine off by moving the control panel Mode switch back to the OFF position.

Fig. K

32

200-2341

Image 32
Contents Models PM401211 PM400911 Table of Contents General Safety Guidelines General Safety Guidelines Unpacking Instruction S Installation Plannin GIntroductio N Generator Location Utomatic Transfer Switch Generator Installation Placement and AnchoringInstallation Drawings Electrical Hookup AIN Line Output Powe RGenerator Start Signal Gfci Circuit Supply12KW Wiring Diagram CP200 Controller Fuel Specifications Consumption Require MentsFuel Hookup Natural Gas NGPropane Vapor LPG Connection Battery Requirement SBattery Placement Nnection con t LubricationFirst Time Startup Generator Specifications PM401211 PM400911Alternator Specifications FuelGenerator Feature Identificatio NGenerator Operation Control Panel FeaturesControl Panel Switches Starting the Generator Cyclic CrankRUN State ShutdownStatus Indicators FaultsMaintenance Engine OIL Level Chec K Crankcase pressure can blow hot engine oil outND Clean ING Engine OIL and OIL FilterHange Engine OIL Cooler InspectionBattery Maintenanc E Engine AIR Filter ChangeTT ERY Maintenanc E con t Spark Plug Check Fig. GSpark Arrestor Cleaning Fig. GGGovernor Speed Adjustment Enclosure and SiteFuel System Inspection Adjustmen TValve Clearance Check Troubleshooting Symptom Possible Cause Corrective ActionSymptom Parts Drawing Exhaust System Parts Drawing Enclosure Parts Drawing LID Assembly Parts Drawing Generator Parts Drawing -H2X Breakdown Parts Drawing Engine Panel END Assembly Parts Drawing Control Panel Breakdown Parts Drawing Battery Hold Down 200-2341 200-2341 Coverage Contact the Coleman Powermate Product Service Department AT 200-2341