Generac 04675-3, 04673-2, 04674-2 owner manual Location, ‹ 1.9.1 Generator, ‹ 1.9.2 Transfer Switch

Page 10

Section 1 — General Information

Air-cooled 7 kW, 12 kW and 15 kW Generators

1.Turn off the gas supply. (if connected)

2.Open the roof and remove the door.

3.Remove the battery. (if installed)

4.Remove the engine air in baffle located on the left- hand side of the battery compartment. Two M6 screws are located on top of the baffle and two M6 screws are located on the inside of the baffle towards the back.

5.Remove the small hose clamp and hose from the fuel regulator. It may be necessary to pry the hose off of the brass fitting using a screwdriver to gen- tly lift up the hose edge.

6.Remove the small brass hose fitting from the regulator casting.

7.Place the small fuel jet, thread side first, into the threaded hole originally occupied by the brass hose fitting (Figure 1.4).

Figure 1.4 - Demand Regulator

14.It may be necessary to make minor adjustments to the preset adjustment screw settings to achieve maximum power, particularly at higher altitudes. If experiencing problems with the unit producing maximum power, follow the procedure in Section 2.6 (Adjusting the Fuel Regulator).

1.9LOCATION

‹ 1.9.1 GENERATOR

Install the generator set, in its protective enclosure, outdoors, where adequate cooling and ventilating air is always available. Consider these factors:

• Install the unit where air inlet and outlet open-

ings will not become obstructed by leaves, grass,

snow, etc. If prevailing winds will cause blowing or

drifting, consider using a windbreak to protect the

unit.

• Install the generator on high ground where water

levels will not rise and endanger it.

• Allow sufficient room on all sides of the generator

IDLE CIRCUIT PORT

 

 

 

OUTLET PORTS

 

 

 

FUEL HOSE

 

 

 

BRASS HOSE

 

 

 

FITTING

U

 

BRASS HOSE

 

T

 

FITTING

1

 

TAP

 

 

1/8 NPT

 

 

 

ADJUSTER

 

 

 

 

 

 

 

 

 

SCREWS

SMALL

FUEL JET

REGULATOR

HOUSING PORT

for maintenance and servicing. A good rule is to

allow three feet of space on all sides.

• Where strong prevailing winds blow from one

direction, face the generator air inlet openings to

the prevailing winds.

• Install the generator as close as possible to the fuel

supply, to reduce the length of piping.

• Install the generator as close as possible to

the transfer switch. HOWEVER, REMEMBER

THAT LAWS OR CODES MAY REGULATE THE

DISTANCE.

8.Using a short No. 2 Phillips screw driver, thread the small fuel jet into the regulator casting. Do not over tighten.

9.Apply thread sealant to the threads of the hose fitting and replace it into the regulator body.

10.Re-attach the small hose and hose clamp and tighten as necessary.

11.Replace the engine air in baffle using the four M6 screws.

12.Identify both brass adjustment screws on the regulator.

NOTE:

One adjustment screw can be accessed from the front of the unit and the second can be accessed from the back of the unit enclosure by removing the plastic hole plug. The screw can be turned with a long flat blade screwdriver.

13.To adjust the system to run on LP fuel, turn BOTH adjuster screws 1/2 TURN CLOCKWISE. The system should now be set for maximum power and best perfomance. DO NOT, UNDER ANY CIRCUMSTANCES, REMOVE THE SET PINS FROM THE REGULATOR HOUSING. THIS WILL VOID THE WARRANTY.

‹1.9.2 TRANSFER SWITCH

1.9.2.1 7 kW, 12 kW and 15 kW Units

Transfer switches for use with these generators are sold separately and can be purchased from Authorized Dealers.

Install the transfer switch on a firm, sturdy sup- porting structure.

To prevent switch distortion, level the switch if necessary. This can be done by placing washers between the switch enclosure and mounting sur- face.

Never install the switch where water or any corro- sive substance might drip onto the enclosure.

Protect the switch at all times against excessive moisture, dust, dirt, lint, construction grit and cor- rosive vapors.

Failure to utilize the manufacturer’s transfer switch with this generator may void the warranty.

8

Image 10
Contents Installation Introduction Authorized Dealer LocationTroubleshooting Post Installation Start-up AdjustmentsMaintenance Introduction Inside Front CoverGeneral Hazards Fire Hazards ‹ Standards IndexProtection Systems UNPACKING/INSPECTIONSystem SET LED Generator Gfci‹ 1.5.1 Generator Specifications‹ 1.5.2 Engine Fuel Consumption Reconfiguring the Fuel SystemFuel Requirements Recommendations ‹ 1.8.1 7 KW, 410CC‹ 1.9.1 Generator ‹ 1.9.2 Transfer SwitchLocation 2.1 7 kW, 12 kW and 15 kW UnitsBattery Installation BatteryBefore Initial START-UP Check Transfer Switch OperationElectrical Checks Generator Tests Under Load Checking Automatic OperationEngine Governor Adjustment Adjusting the Regulator Natural GAS only‹ 2.7.1 7 KW Units Voltage Regulator Adjustment ‹ 2.7.2 12 KW and 15 KW UnitsSequence of Automatic Operation BREAK-IN ProcedureAutomatic Transfer Operation ‹ 3.2.1 Auto Position‹ 3.5.2 Transfer Back to Utility Power Source Manual Transfer Operation‹ 3.7.2 High Temperature Switch Setting the Exercise Timer‹ 3.7.1 LOW OIL Pressure Switch ‹ 3.7.3 OvercrankApproximate Crank Cycle Times Checking the Engine OIL Level‹ 3.7.4 Overspeed Changing the OIL Filter ‹ 4.3.2 OIL Change ProcedureChanging the Engine OIL ‹ 4.3.1 Engine OIL RecommendationsBattery Maintenance Spark PlugsAdjusting Valve Clearance Cooling System‹ 4.12.2 Return to Service OUT of Service Procedure‹ 4.12.1 Removal from Service Corrosion ProtectionService Schedule SYSTEM/COMPONENT Procedure FrequencyTroubleshooting Guide Problem Cause CorrectionElectrical Data Customer Battery Utility Battery Charger Utility Connection BCR RED Exploded Views and Parts Lists Part NO. QTY Description Exploded Views and Parts Lists Part NO. QTY. Description 16B Sleeve 122 124 125 138 139 136135 KNOB, AIR Cleaner 45 30 1016 1519 QTY Exploded Views and Parts Lists QTY Description Exploded Views and Parts Lists PIN, Piston D20 Exploded Views and Parts Lists SCREW, Taptite M6-1.0X8 Yellow Chrome 7KW CASTING, Twin Regulator Housing Mounting Dimensions Air-cooled 7 kW, 12 kW and 15 kW Generators MANUFACTURER’S Emission Control System Warranty Coverage Your Warranty Rights and ObligationsPURCHASER’S/OWNER’S Warranty Responsibilities Emission Control System Warranty Emission Related Parts Include the FollowingWarranty Schedule Errata Sheet PRE Packaged Units only ASSEMBLY, Enclosure Base
Related manuals
Manual 56 pages 28.41 Kb

04674-2, 04675-3, 04673-2 specifications

Generac, a prominent name in the power equipment sector, offers a range of reliable and efficient energy solutions, including the models Generac 04673-2, 04675-3, and 04674-2. These models are designed to meet diverse consumer needs, from residential applications to larger commercial setups, providing dependable backup power during outages.

The Generac 04673-2 is a standout home standby generator specifically engineered for residential use. It boasts an automatic operation feature, ensuring that power is restored within seconds of an outage. This model operates on a robust Generac engine, delivering a reliable power output that can support essential household appliances and systems, including HVAC units, refrigerators, and sump pumps. One of the main characteristics of this generator is its Quiet Test mode, which runs at a lower RPM to minimize noise while conducting weekly self-tests, ensuring that the system is always ready when needed.

Moving on to the Generac 04675-3, this model offers enhanced features tailored for users needing higher power output. With a larger capacity, it can handle more demanding power needs, making it suitable for larger homes or small businesses. The 04675-3 is equipped with advanced technologies, including the Mobile Link™ remote monitoring system, which enables users to check the status and performance of their generator from anywhere using a smartphone or computer. This connectivity empowers users with real-time information and alerts regarding their generator's operational performance.

The Generac 04674-2 model rounds out the trio, engineered for those who need a powerful standby generator with a slightly different configuration. It features the same robust engine as the other models, ensuring reliability and user-friendly operation. Its standout feature is the integrated transfer switch capability, which allows for seamless transfer of power from the grid to the generator without manual intervention. This model also supports various fuel types, providing flexibility depending on user preference and availability.

All three Generac models focus on safety and efficiency, incorporating features such as excellent ventilation systems, all-weather enclosures, and user-friendly control panels. They are designed for low maintenance, ensuring long-lasting performance without extensive upkeep. With Generac's commitment to innovation and quality, these generators offer peace of mind, enabling users to maintain their lifestyles and operations without interruption during power outages. Whether for home or business use, the Generac 04673-2, 04675-3, and 04674-2 models represent a reliable choice in emergency power solutions.