Section 2 — Post Installation Start-up and Adjustments

Air-cooled 8.5 kW Generator

2.1BEFORE INITIAL START-UP

Before starting, complete the following:

1.Set the generator's AUTO/OFF/MANUAL switch to the OFF position.

2.Turn OFF the utility power supply to the transfer switch using the means provided (such as the utility main line circuit breaker).

3.Turn OFF all loads connected to the tranfer switch terminals T1 and T2.

4.Check the engine crankcase oil level and, if nec- essary, fill to the dipstick FULL mark with the recommended oil. Do not fill above the FULL mark.

5.Check the fuel supply. Gaseous fuel lines must have been properly purged and leak tested in accordance with applicable fuel-gas codes. All fuel shutoff valves in the fuel supply lines must be open.

4.Use an accurate AC voltmeter to check UTILITY power source voltage across transfer switch ter- minals N1 and N2. Nominal line-to-line voltage should be 240 volts AC.

5.Check UTILITY power source voltage across ter- minals N1 and the transfer switch neutral lug; then across terminal N2 and neutral. Nominal line-to-neutral voltage should be 120 volts AC.

6.When certain that UTILITY supply voltage is com- patible with transfer switch and load circuit rat- ings, turn OFF the UTILITY power supply to the transfer switch.

7.On the generator panel, set the AUTO/OFF/MAN- UAL switch to MANUAL. The engine should crank and start.

8.Let the engine warm up for about five minutes to allow internal temperatures to stabilize. Then, set the generator’s main circuit breaker to its ON (or closed) position.

Never operate the engine with the oil level

!below the “Add” mark on the dipstick. Doing this could damage the engine.

2.2CHECK TRANSFER SWITCH

OPERATION

Refer to Section 3.5, of the owner’s manual for man- ual operation procedures.

Do not attempt manual transfer switch opera- tion until all power voltage supplies to the transfer switch have been positively turned off. Failure to turn off all power voltage supplies will result in extremely hazardous and possibly fatal electrical shock.

2.3ELECTRICAL CHECKS

Complete electrical checks as follows:

1.Set the generator's main circuit breaker to its OFF (or open) position.

2.Turn OFF all loads connected to the transfer switch terminals T1 and T2.

3.Turn on the UTILITY power supply to the trans- fer switch using the means provided (such as a utility main line circuit breaker).

DANGER

Proceed with caution! Generator power voltage is now supplied to the transfer switch. Contact with live transfer switch parts will result in dangerous and possibly fatal electrical shock.

9.Connect an accurate AC voltmeter and a frequen- cy meter across transfer switch terminal lugs E1 and E2. Voltage should be 242-252 volts; fre- quency should read about 61-63 Hertz.

10.Connect the AC voltmeter test leads across termi- nal lug E1 and neutral; then across E2 and neu- tral. In both cases, voltage reading should be 121- 126 volts AC.

11.Set the generator’s main circuit breaker to its OFF (or open) position. Let the engine run at no- load for a few minutes to stabilize internal engine generator temperatures.

12.Set the generator's AUTO/OFF/MANUAL switch to OFF. The engine should shut down.

NOTE:

It is important not to proceed until certain that generator AC voltage and frequency are correct and within the stated limits. Generally, if both AC frequency and voltage are high or low, the engine governor requires adjustment. If frequency is cor- rect, but voltage is high or low, the generator’s voltage regulator requires adjustment.

DANGER

The transfer switch is now electrically “hot.” Contact with “hot” parts will result in extreme- ly hazardous and possibly fatal electrical shock. Proceed with caution.

10 Generac® Power Systems, Inc.

Image 12
Contents Centurion Introduction Authorized Dealer LocationTroubleshooting General Hazards Electrical Hazards ‹ Standards IndexUNPACKING/INSPECTION Breaker for BedroomsProtection Systems Generator 8.5 kW, V-Twin GT-990/760 EngineSpecifications ‹ 1.5.1 GeneratorReconfiguring Fuel System System SET LEDFuel Requirements Recommendations Fuel ConsumptionBattery Installation Transfer SwitchLocation Battery Battery Cable ConnectionsCheck Transfer Switch Operation Before Initial START-UPElectrical Checks Adjusting the Regulator Natural GAS only Generator Tests Under LoadChecking Automatic Operation Engine Governor Adjustment Set PinVoltage Regulator Adjustment BREAK-IN Procedure‹ 3.2.1 Auto Position Automatic Transfer Operation Sequence of Automatic OperationManual Transfer Operation ‹ 3.2.3 Manual PositionSetting the Exercise Timer ‹ 3.5.2 Transfer Back to Utility Power Source‹ 3.7.1 LOW OIL Pressure Switch ‹ 3.7.2 High Temperature SwitchChecking the Engine OIL Level ‹ 3.7.4 Overspeed‹ 4.3.2 OIL Change Procedure Changing the Engine OILChanging the OIL Filter ‹ 4.3.1 Engine OIL RecommendationsBattery Maintenance Spark PlugsAdjusting Valve Clearance Cooling SystemOUT of Service Procedure ‹ 4.11.2 Return to Service‹ 4.11.1 Removal from Service Corrosion ProtectionService Schedule SYSTEM/COMPONENT Procedure FrequencyTroubleshooting Guide Problem Cause CorrectionMounting Dimensions Electrical Data Customer Battery Utility ATS YLW Electrical Data Electrical Data Air-cooled 8.5 kW Generator Enclosure Drawing No F0100-A Part NO. QTY Description Exploded Views and Parts Lists QTY Description 140 With Sleeve Exploded Views and Parts Lists Part NO. QTY. Description Exploded Views and Parts Lists SWITCH, Spst ON-ON N/O Exploded Views and Parts Lists BOX GTS Load Center Air-cooled 8.5 kW Generator Regulator Drawing No D8720-D CASTING, Twin Regulator Housing Air-cooled 8.5 kW Generator Air-cooled 8.5 kW Generator Your Warranty Rights and Obligations MANUFACTURER’S Emission Control System Warranty CoveragePURCHASER’S/OWNER’S Warranty Responsibilities Emission Control System Warranty Emission Related Parts Include the FollowingWarranty Schedule

004692-2 specifications

The Generac 004692-2 is a reliable and efficient portable generator designed to provide power when and where it’s needed most. Ideal for both residential use and outdoor activities, this generator has become a popular choice for homeowners and outdoor enthusiasts alike.

One of the standout features of the Generac 004692-2 is its power output. It offers a robust wattage capacity, allowing users to run essential appliances during a power outage, or to provide electricity for tools and equipment while camping or during a construction project. Its powerful engine is engineered for durability, ensuring longevity and consistent performance.

Another important aspect of the 004692-2 is its portability. Designed with an ergonomic handle and sturdy wheels, this generator is easy to transport, whether moving it around the yard or taking it on the go for outdoor adventures. Its compact design allows for easy storage, making it a convenient addition to any household.

The Generac 004692-2 incorporates advanced technologies for ease of use and efficiency. It features a user-friendly control panel that includes multiple outlets, allowing users to connect various devices simultaneously. The generator is equipped with a low-oil automatic shutdown system that helps protect the engine from damage, extending the life of the generator.

Moreover, the generator is designed with a quiet operation feature, making it suitable for residential areas. This means users can rely on it for power without disturbing neighbors during critical times such as family gatherings or late-night emergencies.

In terms of fuel efficiency, the Generac 004692-2 performs admirably with its optimized engine design, allowing users to maximize run time while minimizing fuel consumption. This feature is not only cost-effective but also environmentally friendly, reducing the carbon footprint during usage.

Safety is paramount with any generator, and the Generac 004692-2 includes several built-in safety features. The generator is designed to withstand various weather conditions, ensuring reliability during storms or outdoor events. Additionally, the generator's design includes features that reduce the risk of accidental starting, adding an extra layer of protection for the user.

In conclusion, the Generac 004692-2 stands out as an excellent choice for those seeking a dependable portable generator. Its combination of powerful performance, portability, user-friendly design, and built-in safety features makes it an ideal solution for a variety of power needs. Whether for home backup or outdoor use, this generator provides peace of mind with its reliability and efficiency.