Page 86

Chapter 5 - MODBUS-RTU Communication

Negative Acknowledge Response

NAK

Drive No.

CMD

Error Code

SUM

EOT

15h

“01” ~ “1F”

“X”

“**”

“XX”

04h

1 byte

2 bytes

1 byte

2 bytes

2 bytes

1 byte

Total byte = 9 bytes

Action Request for Monitor Registration: Request for read of address registered by monitor registration.

ENQ

 

 

 

Drive No.

 

 

CMD

 

SUM

 

EOT

 

05h

 

 

“01” ~ “1F”

 

 

“Y”

 

“XX”

 

04h

 

1 byte

 

 

 

2 bytes

 

 

1 byte

 

2 bytes

 

1 byte

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Total byte = 7 bytes

 

 

 

 

 

 

 

 

 

 

 

 

Acknowledge Response

 

 

 

 

 

 

 

 

 

ACK

 

 

Drive

 

CMD

 

 

Data

 

SUM

EOT

 

06h

 

 

“01” ~

 

 

“Y”

 

 

“XXXX

 

“XX”

04h

 

1 byte

 

2 bytes

 

1 byte

 

n * 4

 

2 bytes

1 byte

 

Total byte= 7 + n * 4 = max. 39 bytes

 

 

 

 

 

Negative Acknowledge Response

 

 

 

 

 

NAK

 

 

Drive

 

CMD

 

 

Error

 

SUM

EOT

 

15h

 

 

“01” ~

 

 

“Y”

 

 

“**”

 

“XX”

04h

 

1 byte

 

2 bytes

 

1 byte

 

2 bytes

 

2 bytes

1 byte

 

Total byte = 9 bytes

 

 

 

 

 

 

 

 

 

 

 

 

Error Code

 

 

 

 

 

 

 

 

 

 

 

 

Error Code

 

 

 

 

 

 

 

Description

 

 

SE

 

 

 

Sum Error

 

 

 

 

 

 

 

 

 

FE

 

 

 

Frame Error

 

 

 

 

 

 

 

 

 

FC

 

 

 

Frame Error (Command): Not in use

 

 

FS

 

 

 

Frame Error (Size)

 

 

 

 

 

EE

 

 

 

Parameter EEP Access Error

 

 

80

Image 86
Contents Installation, Operation Maintenance Instruction 4 HPSafety Instructions Otherwise, electric shock could occurOtherwise, it could result in a secondary accident and fire Otherwise, you may get an electric shockOtherwise, fire could occur Otherwise, fire or accident could occurOperating Precautions Page Page Contents 105 100104 106460V Class 0.5~ 5.4HP User Selection Guide Actionmaster Specifications230V Class 0.5~5.4HP Motor Rating1 Output Capacity2 kVAControl Method Control008 InstallationInspection Environmental ConditionsOther Precautions Installation100 128 117.5 130.9 DimensionsInverter 130 118 128 117.5 152.9SV037ACtionMaster 150 138 128 117.5 155.0 Basic Wiring MccbPower Terminals Wiring Power Terminals Precautions on WiringGrounding Warning Motor should be connected to the U, V, and W Terminals Wires and Terminal LugsScrew Ring Terminals Wire6 Inverter Torque5 Mm2 Kgf·cm/lb-in Control Terminals30A 30C 30B Control Circuit Terminal Wiring Control Terminals Precautions on WiringInside Inverter Pin No Keypad Wiring the KeypadKeypad Connector Pin Configuration Inverter Side DescriptionSegment Keypad and Parameter Group SettingOperation RUN KeySetting the DRV Group Data Parameter Setting and ChangeProcedures OperationFrequency Adjusting Function and I/O Group DataExample Changing the F5 data to Trip CurrentParameter Group Group Name DescriptionMoving Through DRV Group Codes Moving Through Function Group Codes Moving Through I/O Group CodesOperation From Control Terminal OperationOperation From Keypad and Control Terminal Operation From Keypad Parameter List Drive Group DRVFunction Group 1 FU1 Parameter ListFU1-53 50 / 60 Hz FU1-37FU1-52 Function Group 2 FU2 FU2-3415 FU2-3214FU2-33 FU2-36FU2-88 FU2-83FU2-85 FU2-89Input/Output Group I/O 50 /60 HzYes Deceleration Time To 999.9 sec Yes For Step Frequency Deceleration Time To 999.9 secYes For Step Frequency Acceleration Time To 999.9 sec Yes Acceleration Time To 999.9 secStall Acceleration Time To 999.9 secYes FM Frequency Meter Output Current Selection Voltage Yes Reference Free RunYes Modbus-RTU BitDRV-00 Output Frequency Related Functions DRV-04 Freq Mode FU1-20 Max FreqParameter Description DRV-01 Acceleration Time DRV-02 Deceleration TimeSelect the source of Run/Stop command Parameter Description DRV DRV-03 Drive Mode Run/stop MethodDRV-04 Frequency Mode Frequency Setting Method Select the source of frequency settingDRV-08 Output Current Parameter Description DRVDRV-05 ~ DRV-07 Step Frequency 1 ~ DRV-09 Motor SpeedDRV-10 DC Link Voltage DRV-12 Fault DisplayFault Contents DRV-11 User Display SelectionPage FU1-00 Jump to Desired Code # Function 1 Group FU1Parameter Description FU1 FU1-03 Run PreventionFU1-07 Stop Mode Selects the stopping method for the inverterStop Mode ‘Free-run’ Output Frequency FU1-22 Time Output Voltage Freq. limit ‘Yes’ Parameter Description FU1 FU1-29 Volts/Hz Pattern FU1-30 ~ FU1-37 User V/F Frequency and VoltageFU1-38 Output Voltage Adjustment FU1-39 Energy Save LevelMotor i2t Characteristic Curve FU1-54 Overload Warning Level FU1-55 Overload Warning Time FU1-59 Stall Prevention Mode Selection St bitParameter Description FU1 FU1-99 Return Code This code is used to exit a group. Press Func key to exitFU2-00 Jump to Desired Code # Function 2 Group FU2Parameter Description FU2 FU2-07 Dwell Frequency FU2-08 Dwell TimeFU2-19 Input/Output Phase Loss Protection Bit Set FU2-10 ~ FU2-16 Frequency JumpFU2-19 Phase Loss Protection Select FU2-20 Power on Start SelectionFU2-21 Restart After Fault Reset Setting RangeFU2-22 Speed Search Select Motor Speed Time Output Frequency Output Voltage FU2-39 Carrier Frequency Output frequency = Reference freq. + Delta freq Parameter Description FU2 FU2-40 Control Method SelectionThis is to select the control method of inverter FU2-70 Reference Frequency for Accel/Decel Delta freqFU2-73 User Display Selection FU2-72 Power On DisplayParameter Description FU2 FU2-71 Accel/Decel Time Scale FU2-74 Gain for Motor Speed DisplayFU2-81 ~ FU2-90 2nd Motor Related Functions FU2-76 Duty of DB Dynamic Braking ResistorFU2-79 Software Version Displays the software versionFU2-94 Parameter Write Protection FU2-91 Parameter Read FU2-92 Parameter WriteFU2-93 Parameter Initialize FU2-99 Return CodeParameter Description FU2 Parameter Description I/O 01 ~ I/O-05 Analog Voltage Input V1 Signal Adjustment06 ~ I/O-10 Analog Current Input I Signal Adjustment 00 Jump to Desired Code #11 Criteria for Analog Input Signal Loss Following table shows the selection in I/O-48Speed-L, Speed-M, Speed-H Step Parameter Speed-H Speed-M Speed-LAccel/Decel Parameter DC-Brake2nd Function TimeUp, Down WireV1-Ext Ext Trip-A21 ~ I/O-24 Step Frequency 4, 5, 6 15 Terminal Input Status 16 Terminal Output Status20 Jog Frequency Analog HoldMulti-Accel/Decel Time Operation 40 FM Frequency Meter Output 41 FM Adjustment25 ~ I/O-38 1st ~ 7th Accel/Decel Time 42 FDT Frequency Detection Level 43 FDT Bandwidth 44 Multi-function Output define MO-MGFDT-3 FDT-1FDT-2 FDT-4IOL Stall45 Fault Output Relay 30A, 30B, 30C 46 Inverter Number 47 Baud Rate50 Communication Protocol Selection 99 Return Code 7-Segment KeypadIntroduction SpecificationsMODBUS-RTU Communication Connecting the communication line InstallationItems Specifications System configurationFunction Code Name OperatingCommunication Protocol Modbus-RTU Exception Code NameCommunication Protocol CMC-BUS Ascii Basic Format Command Message RequestError Response Negative Acknowledge Response Normal Response Acknowledge ResponseNegative Acknowledge Response Detail Communication ProtocolAcknowledge Response Request for Write Request for Registration of ‘n’ numbers of AddressError Code Parameter Code List Common Parameter Description Unit Read/Write Data value HEXValue Parameter DescriptionRead/Write Data value HEX Description Default Max. value Min. value Unit 180 Retry delay630A SS I-GainDescription Default Max. value Min value Unit Group ParameterParameter Description Default Max. value Min value Unit Troubleshooting Refer to this chapter when a trouble is occurredMODBUS-RTU Communication Space Ascii Code ListCharacter Hex Display Protective Description Troubleshooting & MaintenanceFault Display Troubleshooting & Maintenance Fault Inverter Fault Reset Fault Remedy Protective Cause RemedyCondition Check Point Short How to Check Power ComponentsElements Test Polarity Measured Value ModuleRoutine Inspection MaintenancePrecautions Periodical InspectionInspection Method Criterion Measuring Instrument Daily and Periodic Inspection ItemsPeriod Inspection Fan Troubleshooting & Maintenance 400V Class Model Number 004-4 008-4 015-4 022-4 037-4 OptionsBraking Resistor Options Phase230V, or Phase 230/460V 50/60Hz DB Resistor2DIN Rail Base Unit mm103 Appendix a Functions Based on the USE Use Related Parameter CodeAppendix B- Peripheral Devices InverterDeclaration of Conformity CD 73/23/EEC and CD 89/336/EECEN 50178 Safety of information technology equipmentCharacteristics of information technology equipment EN 55022EMC Installation Guide Essential Requirements for CE Compliance109 RFI Filters Footprint Standard for ACtionMaster Series Footprint FiltersRevision History Revision Date Remarks112 Cleveland Motion Controls

inverter specifications

The Cleveland Range inverter is a state-of-the-art piece of kitchen equipment designed to elevate cooking efficiency and precision in commercial kitchens. This versatile appliance is particularly well-suited for establishments such as restaurants, cafeterias, and catering operations, where high-performance and reliability are critical to success.

One of the standout features of the Cleveland Range inverter is its innovative inverter technology. Unlike traditional cooking equipment that utilizes standard heating elements, the inverter system allows for continuous, variable power control. This means that cooks can seamlessly adjust the cooking temperature, offering unparalleled control over the cooking process. The result is more consistent cooking outcomes and a significant reduction in food preparation time, ensuring that dishes are cooked just right every time.

Another characteristic that sets the Cleveland Range inverter apart is its energy efficiency. The inverter technology not only enhances cooking precision but also utilizes energy more effectively, leading to reduced power consumption. This is particularly beneficial for commercial kitchens where energy costs can quickly add up. By minimizing energy waste, the Cleveland Range inverter contributes to a more sustainable kitchen operation.

Safety is also a prime focus of the Cleveland Range inverter. With built-in safety features such as automatic shut-off functions, the appliance ensures that accidental overheating or overcooking is avoided, safeguarding both the kitchen staff and the food being prepared. Additionally, the design of the inverter is user-friendly, making it accessible for cooks at all experience levels.

Durability and ease of maintenance are further characteristics of the Cleveland Range inverter. Built with high-quality materials and a robust construction, it is designed to withstand the rigors of a busy kitchen environment. The straightforward design allows for easy cleaning and maintenance, ensuring that the inverter remains in top working condition over its lifespan.

In conclusion, the Cleveland Range inverter stands out in the commercial kitchen landscape due to its innovative inverter technology, energy efficiency, safety features, and durability. It is an excellent investment for any culinary operation looking to enhance its cooking capabilities while maintaining high standards of food quality and safety. This appliance not only meets the demands of modern kitchens but also sets a benchmark for others in the industry.