APC SUM1500RMXL2U, SMT1500 operation manual Network Management Card Settings

Page 13

Function

Factory Default

Options

Description

 

 

 

 

Name String

Outlet Group 1

Edit these names using an external interface, such as the Network

Outlet Group

 

 

Management Card Web interface.

 

 

UPS Name String

UPS Outlets

 

 

 

 

 

 

Turn On Delay

0 sec

Set the value in

The amount of time the UPS or Switched Outlet

 

 

seconds

Group will wait between receiving the command

 

 

 

to turn on and the actual startup.

 

 

 

 

Turn Off Delay

0 sec

Set the value in

The amount of time that the UPS or Switched

 

 

seconds

Outlet Group will wait between receiving the

 

 

 

command to turn off and the actual shut down.

 

 

 

 

Reboot Duration

4 sec

Set the value in

The amount of time that the UPS or Switched

 

 

seconds

Outlet Group must remain off before it will

 

 

 

restart.

 

 

 

 

Minimum Return

0 sec

Set the value in

The amount of battery runtime that must be

Time

 

seconds

available before the UPS or Switched Outlet

 

 

 

Group will turn on.

Load Shed On

Disabled

• Shutdown with

Battery

 

Delay

 

 

• Shutdown

 

 

immediately

 

 

• Turn off

 

 

immediately

 

 

• Turn off with delay

 

 

• Disabled

When the unit switches to battery power, the UPS can disconnect power to the Switched Outlet Group to save runtime.

Configure this delay time, use the LOAD SHED TIME WHEN ON BATTERY setting.

Load Shed Time Disabled

Set the value in

The amount of time the outlets will function on

when On Battery

seconds

battery power before they will turn off.

Load Shed On

Disabled

• Shutdown with

Runtime

 

delay

 

 

• Shutdown

 

 

immediately

 

 

• Turn off

 

 

immediately

 

 

• Turn off with delay

 

 

• Disabled

When the battery runtime falls below the specified value, the Switched Outlet Group will turn off.

Configure this time using the LOAD SHED

RUNTIME REMAINING setting.

Load Shed On

Disabled

Set the value in

When the remaining runtime reaches this level,

Runtime

 

seconds

the Switched Outlet Group will turn off.

Remaining

 

 

 

 

 

 

 

Load Shed on

Disabled

• Disabled

In the event of an overload (greater than 100%

Overload

 

• Enabled

output), the Switched Outlet Group will

 

 

 

immediately turn off to conserve power for

 

 

 

critical loads. The Switched Outlet Group will

 

 

 

only turn on again with a manual command.

Network Management Card Settings

These settings are available only on units that have a Network Management Card (NMC) and are set in the factory. These settings can only be modified using an external interface, like the NMC web interface.

NMC IP Address Mode

NMC IP Address

NMC Subnet Mask

NMC Default Gateway

10

Smart-UPS 750/1000/1500/2200/3000 VA 120/230 Vac Tower

Image 13
Contents Smart-UPSUPS Contents Smart-UPS Factory Warranty Overview SafetyProduct Description Product Overview1000/1500 VA 120 Vac 750 VA 120 Vac Rear panels1000/1500 VA 230 Vac Installation SpecificationsEnvironmental Specifications Operating ConditionsOperation Rear Panel FeaturesConnect Equipment to the UPS Display Interface Using the display interfaceOverview Standard menusAdvanced menus UPS Settings ConfigurationStart-up Settings General SettingsBattery Replacement Audible Alarm Low BatteryBattery Self SettingUsing the Main Outlet Group and the Switched Outlet Group Main Outlet Group and the Switched Outlet GroupNetwork Management Card Settings EPO Overview Emergency Power OffNormally open contacts Normally closed contactsUPS does not provide expected backup time TroubleshootingDisplay interface indicators flash sequentially UPS is emitting an audible beeping soundReplace battery indicator is illuminated Problem and Possible CauseDisplay interface has a Site Wiring Fault message Service Service and SupportAPC Worldwide Customer Support Transport the unitLimited Warranty Smart-UPS Factory WarrantyApplicable Council Harmonized StandardsDirectives Type of Equipment Model Numbers990-3534-001 06/2009