Function | Factory Default | Options | Description | |
|
|
|
| |
Name String | Outlet Group 1 | Edit these names using an external interface, such as the Network | ||
Outlet Group |
| |||
| Management Card Web interface. | |||
|
| |||
UPS Name String | UPS Outlets | |||
|
| |||
|
|
|
| |
Turn On Delay | 0 sec | Set the value in | The amount of time the UPS or Switched Outlet | |
|
| seconds | Group will wait between receiving the command | |
|
|
| to turn on and the actual startup. | |
|
|
|
| |
Turn Off Delay | 0 sec | Set the value in | The amount of time that the UPS or Switched | |
|
| seconds | Outlet Group will wait between receiving the | |
|
|
| command to turn off and the actual shut down. | |
|
|
|
| |
Reboot Duration | 4 sec | Set the value in | The amount of time that the UPS or Switched | |
|
| seconds | Outlet Group must remain off before it will | |
|
|
| restart. | |
|
|
|
| |
Minimum Return | 0 sec | Set the value in | The amount of battery runtime that must be | |
Time |
| seconds | available before the UPS or Switched Outlet | |
|
|
| Group will turn on. |
Load Shed On | Disabled | • Shutdown with |
Battery |
| Delay |
|
| • Shutdown |
|
| immediately |
|
| • Turn off |
|
| immediately |
|
| • Turn off with delay |
|
| • Disabled |
When the unit switches to battery power, the UPS can disconnect power to the Switched Outlet Group to save runtime.
Configure this delay time, use the LOAD SHED TIME WHEN ON BATTERY setting.
Load Shed Time Disabled | Set the value in | The amount of time the outlets will function on |
when On Battery | seconds | battery power before they will turn off. |
Load Shed On | Disabled | • Shutdown with |
Runtime |
| delay |
|
| • Shutdown |
|
| immediately |
|
| • Turn off |
|
| immediately |
|
| • Turn off with delay |
|
| • Disabled |
When the battery runtime falls below the specified value, the Switched Outlet Group will turn off.
Configure this time using the LOAD SHED
RUNTIME REMAINING setting.
Load Shed On | Disabled | Set the value in | When the remaining runtime reaches this level, |
Runtime |
| seconds | the Switched Outlet Group will turn off. |
Remaining |
|
|
|
|
|
|
|
Load Shed on | Disabled | • Disabled | In the event of an overload (greater than 100% |
Overload |
| • Enabled | output), the Switched Outlet Group will |
|
|
| immediately turn off to conserve power for |
|
|
| critical loads. The Switched Outlet Group will |
|
|
| only turn on again with a manual command. |
Network Management Card Settings
These settings are available only on units that have a Network Management Card (NMC) and are set in the factory. These settings can only be modified using an external interface, like the NMC web interface.
•NMC IP Address Mode
•NMC IP Address
•NMC Subnet Mask
•NMC Default Gateway
10 |