Briggs & Stratton 30230 manual Troubleshooting, Problem Cause Correction

Page 14

PowerBOSS™

5600W Portable Generator

TROUBLESHOOTING

 

 

 

TROUBLESHOOTING

Problem

Cause

Correction

 

 

 

 

 

 

1.

One of the circuit breakers is

1.

Reset circuit breaker.

 

 

open.

 

 

No AC output is available, but

2.

Fault in generator.

2.

Contact Authorized service facility.

3.

Poor connection or defective cord

3.

Check and repair.

generator is running.

 

set.

 

 

 

 

 

 

 

4.

Connected device is bad.

4.

Connect another device that is in

 

 

 

 

good condition.

 

 

 

 

 

Generator runs good at no-load

1.

Short circuit in a connected load.

1.

Disconnect shorted electrical load.

 

 

 

 

but "bogs" down" when loads are

2.

Generator is overloaded.

2.

See "Don't Overload Generator".

connected.

3.

Shorted generator circuit.

3.

Contact Authorized service facility.

 

 

 

 

Generator will not start; or starts

Low oil level.

Fill crankcase to proper level or place

and runs rough.

 

 

generator on level surface.

 

 

 

 

 

Generator shuts down during

1.

Out of fuel.

1.

Fill fuel tank.

2.

Low oil level.

2.

Fill crankcase to proper level or

operation.

 

 

 

place generator on level surface.

 

 

 

 

 

 

 

Generator lacks power.

Load is too high.

See "Don't Overload Generator".

 

 

 

 

 

14

Image 14
Contents Model / Modelo 030230 5600W Equipment Description Table of ContentsSafety Rules When Operating Equipment When Adding or Draining FuelWhen Starting Equipment When Transporting or Repairing EquipmentWhen Adjusting or Making Repairs to Your Generator When Testing for Engine SparkKnow Your Generator Install Wheel Kit AssemblyCarton Contents Unpack the GeneratorAdd Engine Oil When Adding FuelBefore Starting the Engine Add FuelSystem Ground Using the GeneratorConnecting to a Building’s Electrical System Generator LocationStarting the Engine Connecting Electrical LoadsOperating Generator Do not Overload the GENERATOR. See Don’t Overload Generator120/240 Volt AC, 30 Amp, Locking Receptacle ReceptaclesStopping the Engine Volt AC, 20 Amp, Duplex ReceptaclesCapacity Power ManagementDont Overload Generator ExampleEngine Maintenance SpecificationsGeneral Maintenance Recommendations Generator MaintenanceEngine Storage StorageGenerator Storage Other Storage TipsTroubleshooting Problem Cause CorrectionLimited Warranty Descripción DEL Equipo Conserve Estas InstruccionesTabla DE Contenidos Reglas DE SeguridadCuando Opere EL Equipo Cuando Añada Combustible O Vacíe EL DepósitoCuando Ponga EN Funcionamiento EL Equipo Cuando Transporte O Repare EL EquipoCuando Pruebe LA Bujía DEL Motor PrecauciónCuando Ajuste O Haga Reparaciones a SU Generador Conozca SU Generador Tapa del Depósito del Aceite Llene el motor con aceiteContenido de la Caja MontajeDesembalaje del Generador Instale el Juego de RuedasAgregue Combustible Antes DE Darle Arranque AL MotorAgregar Aceite al Motor Cuando Añada CombustibleUbicación del Generador USO DEL GeneradorTierra del Sistema Conexión al Sistema Eléctrico de un EdificioConexion De Cargas Electricas Operando EL GeneradorEncienda el Motor No Sobrecargue EL GENERADOR.Vea No Sobrecargue Generador120/240 Voltios AC, 30 Amp, Receptáculo de Seguridad Receptáculos PrecauciónParado Del Motor Volt AC, 20 Amp, Receptáculos DoblesControl de la Energía No Sobrecargue GeneradorCapacidad EjemploMantenimiento del Motor EspecificacionesRecomendaciones Generales DE Mantenimiento Para Limpiar el GeneradorAlmacenando el Generador Diagnositicos DE AveríasAlmacenamiento Almacenando el MotorUso del consumidor Uso comercial