Baldor PG 6000 manual Single Phase Power Receptacle Description, Receptacle Connections

Page 15

Electrical Connections All load connections are made at the panel using electrical cords with the proper mating plug for the receptacle being used. More than one receptacle can be used as long as the total load does not exceed the continuous rating of the generator.

WARNING: Never connect this generator to any buildings electrical system unless a licensed electrician has installed an approved transfer switch. The National Electrical Code (NEC) requires that connection of a generator to any electrical circuit normally powered by means of an electric utility must be connected by means of approved transfer switch equipment so as to isolate the electrical circuit from the utility distribution system when the generator is operating. Failure to isolate the electrical circuits by such means may result in injury or death to utility power workers due to backfeed of electrical energy onto the utility lines.

Use correct size insulated wire to connect the generator to the load. The gauge of the wire will depend on the distance to the load, the permissible voltage drop at the load, and the current required by the load. If you are not sure of the gauge wire needed for your application, consult a competent electrician. Using wire that is too small can result in fire hazard. Also, be sure the wire has the appropriate ratings for insulation and environment conditions.

The correct mating connector must be used to fit the connectors provided on the operator panel of your generator. Table 3-1describes the connector types provided (receptacles) and the load characteristics to help you choose the correct size wire. Figure 3-2shows the receptacles.

Table 3-1 Single Phase Power Receptacle Description

Model

 

Electrical Connection Information (Receptacle Provided at Panel)

 

 

 

 

 

 

 

 

Straight 120VAC

 

Twist Lock 120/240VAC

 

Rated Watts/

 

(20Amp)

 

(30Amp)

 

(Full load Amps 120/240)

 

 

 

 

 

 

PG6000

2− 520R 120VAC

 

1− L1430R 120/240VAC

 

5700 / (44.2/22.1)

Class 1 wiring methods must be used for field wiring connections to terminals of a Class 2 circuit.

Figure 3-2 Receptacle Connections

Ground

 

(GOLD)

120VAC

G

X

 

 

NEMA

L14−30R

125/250V

30A

NEMA 520R

120VAC

Y

W

Neutral

(GOLD)

(SILVER)

125V 20A

 

 

 

 

 

 

MN2418

Receiving & Installation 3-3

Image 15
Contents PG 6000 Generator California Proposition 65 Warning Table of Contents Ii Table of Contents MN2418 Read This Manual Thoroughly Section Product Safety InformationPrecaution Statements Used In This Manual PropertyOperation Operation Warning Statements Burn Installation Maintenance Product Safety Information MN2418 Limited Warranty Section General InformationLabor Parts General Information MN2418 PG6000 Generator Storage Section Receiving & InstallationPhysical Location Receptacle Connections Single Phase Power Receptacle DescriptionFrame Ground Connection Engine OilUse of Electric Motor Loads Operator Control Panel Section OperationStopping Procedure Start−Up Procedure Recoil StartSection Troubleshooting and Maintenance GeneralEngine Problems and Solutions Troubleshooting GuideService Appendix a PG6000 Connections Figure A-2 PG6000 Wiring Diagram Appendix B Special Information for California Special Information for California MN2418 Baldor District Offices Baldor Electric Company