Baldor PG 6000 manual Section Troubleshooting and Maintenance, General, Engine

Page 19

Section 5

Troubleshooting and Maintenance

Maintenance This manual contains only very minimal engine maintenance instructions. Refer to the engine manufacturer’s owner’s manual for specific engine maintenance instructions for your generator set. Any maintenance instructions or recommendations in the engine owner’s manual take precedence over any of the following general recommendations.

General:

1.Inspect the fuel system for leaks. Replace all defective components immediately.

2.Inspect and replace any fuel line that shows signs of deterioration.

3.Inspect all fuel clamps to ensure they are tight.

4.Make sure the fuel cap fits snugly on the fuel tank and that the fuel tank does not leak.

5.Inspect the external wire cables and connectors used with the generator set for cuts, frayed insulation, or loose connections. Repair or replace damaged parts before use.

6.The engine should be checked for proper speed setting(s).

Prior to adjusting the engine speed, turn the auto idler switch to “OFF” (if present). Make sure that the auto idler magnet does not touch the throttle lever of the engine when running.

a.Disconnect all electrical loads and start the engine.

b.Adjust the engine speed to 3720 RPM (62 Hz) with no load speed.

Engine:

1.Clean and/or replace any fuel, oil, and/or air filters per the engine manufacturers’ guidelines.

2.Check oil level regularly; at least every 5 to 8 operating hours. Maintain the proper oil level.

3.Change the oil as is recommended in the engine manufacturer’s owner’s manual.

4.Replace the spark plug(s) as is recommended by the engine manufacturer.

5.Clean the cooling fins on the engine to keep the engine’s heat dissipation potential at it’s maximum.

6.Inspect and clean all governor and carburetor linkages so they operate properly.

7.Inspect the recoil starting rope for any damage and replace it if necessary (if applicable).

8.Clean the trash screen around the recoil starter or other cooling air intake. Alternator: ( also called Generator End)

This generator set must be run at its proper speed to obtain the correct electrical power at its output. All engines have a tendency to slow down when a load is applied to it. The engine governor is designed to hold the operating speed as nearly constant as possible. When the electrical load is increased, the engine is more heavily loaded and engine speed drops slightly. This slight decrease in engine speed results in a slight decrease in generator voltage and frequency output. This voltage and frequency variation has no appreciable effect in the operation of motors, lights, and most appliances and tools. However, timing devices and clocks will not keep perfect time when used on this generator.

1.Clean the generator set and remove any and all dust, dirt, or other foreign material.

2.Inspect and clean the cooling air intake and exhaust louvers of the generator end. Make sure they are clean. Remove dirt or any buildup that may restrict the cooling air flow.

3.Clean the generator set and its components with a damp cloth or sponge. Never use a water hose or pressure washer as this may damage electrical components.

4.Inspect and replace any control panel components that are broken or not working properly (receptacles, circuit breakers, switches, etc.)

MN2418

Troubleshooting and Maintenance 5-1

Image 19
Contents PG 6000 Generator California Proposition 65 Warning Table of Contents Ii Table of Contents MN2418 Read This Manual Thoroughly Section Product Safety InformationProperty Precaution Statements Used In This ManualOperation Operation Warning Statements Burn Installation Maintenance Product Safety Information MN2418 Section General Information Limited WarrantyLabor Parts General Information MN2418 PG6000 Generator Storage Section Receiving & InstallationPhysical Location Receptacle Connections Single Phase Power Receptacle DescriptionEngine Oil Frame Ground ConnectionUse of Electric Motor Loads Operator Control Panel Section OperationStopping Procedure Start−Up Procedure Recoil StartGeneral Section Troubleshooting and MaintenanceEngine Troubleshooting Guide Problems and SolutionsService Appendix a PG6000 Connections Figure A-2 PG6000 Wiring Diagram Appendix B Special Information for California Special Information for California MN2418 Baldor District Offices Baldor Electric Company