Problems and Solutions
Some of the more common problems are listed in Table
Table 5-1 Troubleshooting Guide
Problem | Possible Cause | Remedy |
|
|
|
Engine will not start | No fuel. | Check that fuel valves are ON. Check fuel level in fuel tank. |
| Restricted air flow. | Check/replace air filter. |
| No spark. | Check/replace spark plug(s). Check that engine switch is in Start |
|
| position. |
|
|
|
Engine starts but will not run smoothly | Fuel or ignition problem | Refer to engine manual. |
|
|
|
Engine overheats | Excessive load | Remove one or more electrical loads. |
| Debris or dirt buildup on engine | Remove debris. Clean engine surfaces to allow cooling. |
|
|
|
No output voltage | Ciruit Breaker tripped or defective. | Reset circuit breaker or replace if required. |
| Loss of residual magnetism in exciter | Flash field. |
| field poles. |
|
| Open in stator windings | Check for continuity in windings. Return to factory for repair if open. |
| Defective exciter circuit. | Check/replace diode and capacitor and flash the field. |
|
|
|
Output voltage varies | Irregular speed (fixed speed mode) | Check engine for malfunction or load for fluctuation |
| Fluctuating speed (fixed speed mode) | Stabilize load. The addition of a lamp load (resistance load) may |
|
| compensate partially for load changes caused by intermittent motor |
|
| operation. Do not overload. |
| Loose terminal or load connections | Verify all connections are proper and check tighness torque of |
|
| terminals. |
| Defective bearing (uneven air gap) | Replace worn bearing |
Low output voltage | Low engine speed |
| Excessive load |
| High resistance connections − |
| connections will be warm or hot |
| Shorted field |
Check that the Auto Idle switch is in OFF position (if installed). Check engine for malfunction or system for overload. Reduce load. Verify all connections are proper and check tighness torque of terminals.
Test field coils for possible short by checking resistance with an ohmmeter or resistancebridge. Return rotor assembly to service center for repair if alternator field coils are shorted.
|
| Low power factor | Reduce inductive (motor) load. Some AC motors use about the |
|
|
| same current regardless of load. Do not use motors of greater |
|
|
| horsepower rating than is necessary to move the mechanical load. |
|
|
|
|
High output voltage |
| Excessive speed (fixed speed mode) | Check engine for malfunction |
|
|
| |
Electrical shock when frame is touched | Static charge. | Ground generator frame at local reference ground (see Section 3). | |
|
| Grounded armature or field coil. | Return to service center for repair |
|
|
|
|
Mechanical noise |
| Defective bearing | Replace bearing |
|
| Rotor rubbing on stator | Bad bearing − replace. |
|
|
| Bent shaft − return to service center. |
|
|
| Loose end bell − tighten; |
|
|
| Loose drive Discs − tighten |
|
| Loose or misaligned coupling | Tighten; align coupling and alternator shaft to engine shaft. |
|
| ||
Service | Service for your generator can be obtained from a generator service center. Please have the | ||
| following information available: |
| |
| The model number and serial number of the generator set. | ||
| A complete and accurate description of the problem. | ||
Parts | Parts for your generator can be obtained from a generator service center. Please have the |
following information available:
The model number and serial number of the generator set.
A complete and accurate description of the part (part number if known).
Note: Engine parts can usually be obtained by using the information in the engine manufacturer’s owner’s manual.