Baldor PG 6000 manual Section Operation, Operator Control Panel

Page 17

Section 4

Operation

Operator Control Panel

The Operator Panel is shown in Figure 4-1.

Figure 4-1 Operator Panels

AC Circuit Breakers

120VAC

120VAC

240VAC

20A

20A

22A

WARNING: Never connect this generator to any buildings electrical system unless a licensed electrician has installed an approved transfer switch. The National Electrical Code (NEC) requires that connection of a generator to any electrical circuit normally powered by means of an electric utility must be connected by means of approved transfer switch equipment so as to isolate the electrical circuit from the utility distribution system when the generator is operating. Failure to isolate the electrical circuits by such means may result in injury or death to utility power workers due to backfeed of electrical energy onto the utility lines.

AC Circuit Breakers Provide overcurrent protection for the generator output. When tripped, the plunger (in center of breaker) will extend out about 3/8 inch. Remove the loads, push the plunger into the breaker to reset the breaker. Correct any overloads then restore the loads.

Receptacles − Receptacles are provided to allow easy connection of electrical loads. Never connect this generator to any buildings electrical system unless a licensed electrician has installed an approved transfer switch. Multiple receptacles may be used at the same time provided the total electrical load does not exceed the generators rated output.

120Volts − PG6000 has 2 outlets each rated 125VAC at 20 Amperes. (NEMA 520R Duplex receptacle125VAC at 20 Amperes).

240 Volts − Twist lock NEMA L1430R receptacle rated 250Volts at 30 Amperes.

Note: The nominal voltage produced by the generator at each receptacle is 120VAC or 240VAC.

Pre−Start Checks Before the engine is started, several things must first be checked.

1.Place the generator set in an open, dry, well ventilated and reasonably level location.

2.If grounding is required for your application, check to make sure your unit is grounded properly (see Section3).

3.Check the engine’s oil level and add oil if necessary to bring it to the level recommended by the engine manufacturer.

4.Check the fuel level and add fuel to within 1/2 inch of the fill tube if necessary.

5.Open the fuel valve on the fuel tank (and on the engine if installed).

6.Check the fuel system for fuel leaks and repair them prior to starting the engine. Wipe up any fuel spills before starting the engine.

7.Disconnect or “turn off” all external loads.

8.Make sure all circuit breakers are set (pushed in).

9.Tighten any bolts or nuts that may have loosened due to vibration.

10.Be sure all extension cords are in good condition before starting the generator. Use only U.L. listed extension cords and connectors.

MN2418

Operation 4-1

Image 17
Contents PG 6000 Generator California Proposition 65 Warning Table of Contents Ii Table of Contents MN2418 Read This Manual Thoroughly Section Product Safety InformationOperation Precaution Statements Used In This ManualProperty Operation Warning Statements Burn Installation Maintenance Product Safety Information MN2418 Labor Parts Limited WarrantySection General Information General Information MN2418 PG6000 Generator Storage Section Receiving & InstallationPhysical Location Receptacle Connections Single Phase Power Receptacle DescriptionUse of Electric Motor Loads Frame Ground ConnectionEngine Oil Operator Control Panel Section OperationStopping Procedure Start−Up Procedure Recoil StartEngine Section Troubleshooting and MaintenanceGeneral Service Problems and SolutionsTroubleshooting Guide Appendix a PG6000 Connections Figure A-2 PG6000 Wiring Diagram Appendix B Special Information for California Special Information for California MN2418 Baldor District Offices Baldor Electric Company