Emerson 10-30kVA installation manual Liebert, Optional Cabinets, Maintenance Bypass Cabinet

Page 14

Installation

1.6.4Optional Cabinets

If your NX installation includes a Maintenance Bypass Cabinet, the NX must be positioned to allow the Maintenance Bypass Cabinet to be bolted to left side of the NX (see Figure 1). Cables from the Maintenance Bypass Cabinet must be brought through the bottom side of the NX for connection.

The Maintenance Bypass Cabinet must be cabled and bolted to the NX before the UPS and bypass cabinet are moved into their final position. Connect the input wiring to the Maintenance Bypass Cab- inet ONLY after the units are connected and positioned.

Battery cabinets may be bolted to either side of the NX, unless used in configurations that include a Maintenance Bypass Cabinet. If used with a Maintenance Bypass Cabinet, battery cabinets must be installed on the right side of the UPS; see Figure 1 below.

Figure 1 Cabinet arrangement

ALL UNITS VIEWED FROM ABOVE

Maintenance

Bypass

Cabinet

Liebert

NX

Maintenance

Bypass

Cabinet

Liebert

NX

Battery Cabinet

Battery Cabinet

NX connected only to MBC

NX connected to Maintenance Bypass Cabinet and Battery Cabinets

(MBC must be on left side of the NX)

(MBC must be on left side of the NX)

 

(Battery Cabinets must be on the right side of the NX in this

 

configuration)

Battery Cabinet

Liebert

NX

Battery Cabinet

NX connected to Battery Cabinets

(Battery Cabinets may be on either side of the NX)

8

Image 14
Contents Liebert NX UPS Page Table of Contents Options Maintenance Bypass CabinetUPS Specifications Figures Tables Important Safety Instructions Battery Cabinet Precautions Glossary of Symbols External Inspections Internal InspectionsPreliminary Checks UPS LocationSpecial Considerations for 1+N Systems Considerations in Moving the NXMechanical Considerations Final PositionCable Entry Floor InstallationClearances 10-30kVA UPSOptional Cabinets Maintenance Bypass CabinetLiebert Lug Size and Torque Requirements Power CablingCable Rating UPS Input Configuration Cabling GuidelinesCable Connections Input busbarsUPS Rectifier and Bypass Input Supply Safety GroundProtective Devices System OutputCommon Input Connections Cabling ProcedureOutput System Connections-Ensure Correct Phase Rotation Dual Input ConnectionsControl Cables Internal UPS Battery ConnectionsMonitor Board Features Dry Contacts Input Dry ContactsBCB Box Interface Maintenance Bypass Cabinet InterfaceMaintenance bypass cabinet interface BCB box interfaceOutput dry contact relays Output Dry ContactsEPO Input-Optional Firmware Before M200 EPO input contact relaysEPO wiring for firmware M200 or later Firmware M200 or LaterUPS Batteries SafetyIntroduction Connecting the Batteries External Battery Cabinet InstallationMatching Battery Cabinets Removable retainer Tray handle Insulated post for cablingTop cable entry Batteries BCB plate Top cable entry Battery trays BCB plate and BCBBattery tray support Service shelf Installation Considerations Front door note notched Battery tray supports attachTo interior surface of NX Ends of supportsConnecting the Battery Cabinet to the UPS Non-Standard BatteriesBypass Switch Normal UPS ModeCable Installation Bypass ModeMaintenance Mode Locating the CabinetPower Cable Installation Input/Output WiringMaintenance bypass control wire location Bolting Cabinets Together Line up cabinets so that mounting holes are alignedPerformance Requirements DBS Cable and SettingsLoad Bus Synchronization LBS CableGeneral Configuring Parallel System OperationFeatures of Parallel System Installing Parallel System Parallel Control Cables Parallel System Control Cables Power CablesInterconnecting Auxiliary Dry Contact CablesInput Distribution Normally Open EPO Normally Closed EPODimensions Battery Circuit Breaker BoxAvailable battery circuit breaker boxes Circuit BreakerBattery circuit breaker box connections Mechanical characteristics UPS Mechanical CharacteristicsEnvironmental characteristics Conformity and StandardsUPS Electrical Characteristics UPS terminalDC Intermediate Circuit Battery Manufacturers and ModelsInput Rectifier Bypass Input Bypass input Inverter OutputInverter output Time LoadInstallation Drawings Dimensions -top and bottom views Cable connections Battery 417mm 186mm 687mm Location of internal batteriesW505 to W504 W508 to W509 W501 3pcs W500 18pcs W506 to W507 W510 to W511 W502 to W503W504 to W505 W511 to W510 W507 to W506 W509 to W508 W503 to W502Run From Conductors Liebert -supplied interconnect wiringRefer to for key to interconnection Maintenance Bypass interconnection Liebert-supplied interconnect wiring Run From Conductors Cabinet TypeLineup detail-SlimLine distribution cabinet to NX Interconnect wiring-1+N Type a connection to NX Lineup detail-1+N Type a connection to NXInterconnect wiring-1+N Type A1 connection to NX Lineup detail-1+N Type A1 connection to NXInterconnect wiring-1+N Type B connection to NX Lineup detail-1+N Type B connection to NXInterconnect wiring-1+N Type B1 connection to NX Lineup detail-1+N Type B1 connection to NXInterconnect wiring-1+N Type C connection to NX Lineup detail-1+N Type C connection to NXInterconnect wiring-1+N Type C1 connection to NX Lineup detail-1+N Type C1 connection to NXInterconnect wiring-1+N Type D connection to NX Lineup detail-1+N Type D connection to NXUPS Initial Torque Annual Torque Battery In-lb N-m Torque specificationsBattery torque rating Lug Size and Torque RequirementsCurrent Rating a OCP CB Size a Maintenance bypass cabinet electrical data single inputCurrent CB Size a Maintenance bypass cabinet electrical data dual input Current Rating a CB Size aMulti-module bypass cabinet electrical data 200A E00, FR0 208 104 125 250 400 MR1 208 280 400 222 300 210 250 167 225 140 175 111 150 Maintenance bypass cabinet lug sizes Maintenance Bypass Cabinet Style, lb. kg Rating Battery cabinet physical characteristicsMaintenance Bypass Cabinet weights Cable Lengths Floor to Connection Point Inside UPS Maintenance bypass cabinet dimensionsMulti-module paralleling cabinet dimensions Distance to connection points on the NX UPSSpecifications and Technical Data Specifications and Technical Data Page Tin NetIti That
Related manuals
Manual 80 pages 38.9 Kb

10-30kVA specifications

The Emerson 10-30 kVA, 208V uninterruptible power supply (UPS) solution is a robust system designed to provide reliable power protection for critical applications in commercial and industrial settings. This UPS is ideal for safeguarding IT equipment, communication systems, and other sensitive electronics against power disturbances and interruptions.

One of the standout features of the Emerson 10-30 kVA UPS is its modular design, allowing for flexibility and scalability. This means that as the power needs of a facility grow, the UPS can be easily expanded without requiring a complete system overhaul. This modularity contributes to a more efficient use of resources and minimizes operational costs.

The UPS also incorporates advanced technologies such as double-conversion online architecture, which provides the highest level of power quality. This technology ensures that the output power is consistently clean and stable, effectively eliminating harmful voltage fluctuations and frequency variations. Consequently, connected load receives a pure sine wave output, preventing potential damage or operational issues with sensitive equipment.

Another key feature is the high efficiency rating of the Emerson UPS, which exceeds 95 percent in typical operating conditions. This high efficiency translates to reduced energy costs and a smaller carbon footprint, aligning with modern sustainability goals. The cooling system is designed to be efficient as well, ensuring optimal performance while maintaining a compact footprint.

The user-friendly interface enhances operability, featuring an intuitive LCD display that allows for easy monitoring of critical power parameters. Users can access real-time data related to battery health, load levels, and operational status, which aids in effective management of the power supply.

Battery management is another critical aspect of the Emerson UPS. It employs advanced battery management technologies to ensure optimal battery life and performance. Features such as intelligent battery testing and monitoring help predict potential battery failures before they occur, allowing for proactive maintenance and minimized downtime.

In summary, the Emerson 10-30 kVA, 208V UPS offers a combination of modularity, high efficiency, advanced technologies, and effective power management features that cater to the demanding needs of critical applications. With its reliable performance and user-friendly operation, this UPS solution is an excellent choice for organizations looking to protect their valuable equipment from power disturbances.