Emerson 10-30kVA installation manual UPS Electrical Characteristics, UPS terminal

Page 45

UPS Specifications

6.4UPS Electrical Characteristics

Table 10 UPS terminal

Input (for single-input unit)

 

Nominal

Maximum

 

OCP

 

Maximum Recommended Lug

 

 

 

 

 

Unit

Input

Input

OCP

Device

 

Lug T&B

Lug T&B

Rating

Current

Current

Current

Rating

Bolt Size

One Hole 54000

One Hole REDDY

10

28

35

42

45

6M (1/4”)

54105

62204

 

 

 

 

 

 

 

 

15

42

53

63

70

6M (1/4”)

54106

62204

 

 

 

 

 

 

 

 

20

56

70

84

90

6M (1/4”)

54107

62204

 

 

 

 

 

 

 

 

30

83

104

125

125

6M (1/4”)

54152

62205

 

 

 

 

 

 

 

 

Rectifier input (for dual input unit only)

 

Nominal

 

Maximum

 

OCP

 

Maximum Recommended Lug

 

 

 

 

 

 

Unit

Input

 

Input

OCP

Device

 

Lug T&B

Lug T&B

Rating

Current

 

Current

Current

Rating

Bolt Size

One Hole 54000

One Hole REDDY

10

25

 

31

37

40

6M (1/4”)

54130

62204

 

 

 

 

 

 

 

 

 

15

37

 

47

57

60

6M (1/4”)

54106

62204

 

 

 

 

 

 

 

 

 

20

50

 

63

76

80

6M (1/4”)

54107

62204

 

 

 

 

 

 

 

 

 

30

75

 

94

113

125

6M (1/4”)

54152

62205

 

 

 

 

 

 

 

 

Bypass input (for dual input units)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Maximum Recommended Lug

 

 

Nominal

 

 

OCP

 

 

 

 

 

 

 

 

Lug T&B

Lug T&B

 

Unit

Input

 

OCP

Device

 

One Hole

One Hole

 

Rating

Current

 

Current

Rating

Bolt Size

54000

REDDY

 

10

28

 

35

35

6M (1/4”)

54105

62204

 

 

 

 

 

 

 

 

 

 

15

42

 

53

60

6M (1/4”)

54106

62204

 

 

 

 

 

 

 

 

 

 

20

56

 

70

70

6M (1/4”)

54107

62204

 

 

 

 

 

 

 

 

 

 

30

83

 

104

110

6M (1/4”)

54152

62205

 

 

 

 

 

 

 

 

 

 

Output

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Nominal

 

OCP

 

Maximum Recommended Lug

 

 

 

 

 

Unit

Output

OCP

Device

 

Lug T&B

Lug T&B

Rating

Current

Current

Rating

Bolt Size

One Hole 54000

One Hole REDDY

10

 

28

35

35

6M (1/4”)

54130

62204

 

 

 

 

 

 

 

 

15

 

42

53

60

6M (1/4”)

54106

62204

 

 

 

 

 

 

 

 

20

 

56

70

70

6M (1/4”)

54106

62204

 

 

 

 

 

 

 

 

30

 

84

105

110

6M (1/4”)

54108

62205

 

 

 

 

 

 

 

 

 

Battery

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OCP

 

Maximum Recommended Lug

 

 

 

 

 

 

 

 

Unit

Battery

OCP

Device

 

Lug T&B

Lug T&B

Rating

Current

Current

Rating

Bolt Size

One Hole 54000

One Hole REDDY

10/15

 

55

55

70

6M (1/4”)

54106

62204

 

 

 

 

 

 

 

 

20/30

 

110

110

125

8M (5/16”)

54153

62212

 

 

 

 

 

 

 

 

 

39

Image 45
Contents Liebert NX UPS Page Table of Contents Maintenance Bypass Cabinet UPS SpecificationsOptions Figures Tables Important Safety Instructions Battery Cabinet Precautions Glossary of Symbols Internal Inspections External InspectionsUPS Location Preliminary ChecksMechanical Considerations Considerations in Moving the NXSpecial Considerations for 1+N Systems Final PositionClearances Floor InstallationCable Entry 10-30kVA UPSMaintenance Bypass Cabinet LiebertOptional Cabinets Power Cabling Cable RatingLug Size and Torque Requirements Cabling Guidelines UPS Input ConfigurationInput busbars Cable ConnectionsProtective Devices Safety GroundUPS Rectifier and Bypass Input Supply System OutputOutput System Connections-Ensure Correct Phase Rotation Cabling ProcedureCommon Input Connections Dual Input ConnectionsInternal UPS Battery Connections Monitor Board FeaturesControl Cables Input Dry Contacts Dry ContactsMaintenance bypass cabinet interface Maintenance Bypass Cabinet InterfaceBCB Box Interface BCB box interfaceEPO Input-Optional Firmware Before M200 Output Dry ContactsOutput dry contact relays EPO input contact relaysFirmware M200 or Later EPO wiring for firmware M200 or laterSafety IntroductionUPS Batteries Matching Battery Cabinets External Battery Cabinet InstallationConnecting the Batteries Removable retainer Tray handle Insulated post for cablingTop cable entry Battery trays BCB plate and BCB Battery tray support Service shelfTop cable entry Batteries BCB plate Installation Considerations To interior surface of NX Battery tray supports attachFront door note notched Ends of supportsNon-Standard Batteries Connecting the Battery Cabinet to the UPSNormal UPS Mode Bypass SwitchMaintenance Mode Bypass ModeCable Installation Locating the CabinetInput/Output Wiring Power Cable InstallationMaintenance bypass control wire location Line up cabinets so that mounting holes are aligned Bolting Cabinets TogetherLoad Bus Synchronization DBS Cable and SettingsPerformance Requirements LBS CableConfiguring Parallel System Operation Features of Parallel SystemGeneral Installing Parallel System Interconnecting Power CablesParallel Control Cables Parallel System Control Cables Auxiliary Dry Contact CablesInput Distribution Normally Closed EPO Normally Open EPOAvailable battery circuit breaker boxes Battery Circuit Breaker BoxDimensions Circuit BreakerBattery circuit breaker box connections Environmental characteristics UPS Mechanical CharacteristicsMechanical characteristics Conformity and StandardsUPS terminal UPS Electrical CharacteristicsBattery Manufacturers and Models Input RectifierDC Intermediate Circuit Inverter output Inverter OutputBypass Input Bypass input Time LoadInstallation Drawings Dimensions -top and bottom views Cable connections Location of internal batteries Battery 417mm 186mm 687mmW504 to W505 W511 to W510 W507 to W506 W509 to W508 W501 3pcs W500 18pcs W506 to W507 W510 to W511 W502 to W503W505 to W504 W508 to W509 W503 to W502Liebert -supplied interconnect wiring Refer to for key to interconnectionRun From Conductors Maintenance Bypass interconnection Run From Conductors Cabinet Type Liebert-supplied interconnect wiringLineup detail-SlimLine distribution cabinet to NX Lineup detail-1+N Type a connection to NX Interconnect wiring-1+N Type a connection to NXLineup detail-1+N Type A1 connection to NX Interconnect wiring-1+N Type A1 connection to NXLineup detail-1+N Type B connection to NX Interconnect wiring-1+N Type B connection to NXLineup detail-1+N Type B1 connection to NX Interconnect wiring-1+N Type B1 connection to NXLineup detail-1+N Type C connection to NX Interconnect wiring-1+N Type C connection to NXLineup detail-1+N Type C1 connection to NX Interconnect wiring-1+N Type C1 connection to NXLineup detail-1+N Type D connection to NX Interconnect wiring-1+N Type D connection to NXUPS Battery torque rating Torque specificationsInitial Torque Annual Torque Battery In-lb N-m Lug Size and Torque RequirementsMaintenance bypass cabinet electrical data single input Current CB Size aCurrent Rating a OCP CB Size a Current Rating a CB Size a Maintenance bypass cabinet electrical data dual inputMulti-module bypass cabinet electrical data 200A E00, FR0 208 104 125 250 400 MR1 208 280 400 222 300 210 250 167 225 140 175 111 150 Maintenance bypass cabinet lug sizes Battery cabinet physical characteristics Maintenance Bypass Cabinet weightsMaintenance Bypass Cabinet Style, lb. kg Rating Multi-module paralleling cabinet dimensions Maintenance bypass cabinet dimensionsCable Lengths Floor to Connection Point Inside UPS Distance to connection points on the NX UPSSpecifications and Technical Data Specifications and Technical Data Page Iti NetTin That
Related manuals
Manual 80 pages 38.9 Kb

10-30kVA specifications

The Emerson 10-30 kVA, 208V uninterruptible power supply (UPS) solution is a robust system designed to provide reliable power protection for critical applications in commercial and industrial settings. This UPS is ideal for safeguarding IT equipment, communication systems, and other sensitive electronics against power disturbances and interruptions.

One of the standout features of the Emerson 10-30 kVA UPS is its modular design, allowing for flexibility and scalability. This means that as the power needs of a facility grow, the UPS can be easily expanded without requiring a complete system overhaul. This modularity contributes to a more efficient use of resources and minimizes operational costs.

The UPS also incorporates advanced technologies such as double-conversion online architecture, which provides the highest level of power quality. This technology ensures that the output power is consistently clean and stable, effectively eliminating harmful voltage fluctuations and frequency variations. Consequently, connected load receives a pure sine wave output, preventing potential damage or operational issues with sensitive equipment.

Another key feature is the high efficiency rating of the Emerson UPS, which exceeds 95 percent in typical operating conditions. This high efficiency translates to reduced energy costs and a smaller carbon footprint, aligning with modern sustainability goals. The cooling system is designed to be efficient as well, ensuring optimal performance while maintaining a compact footprint.

The user-friendly interface enhances operability, featuring an intuitive LCD display that allows for easy monitoring of critical power parameters. Users can access real-time data related to battery health, load levels, and operational status, which aids in effective management of the power supply.

Battery management is another critical aspect of the Emerson UPS. It employs advanced battery management technologies to ensure optimal battery life and performance. Features such as intelligent battery testing and monitoring help predict potential battery failures before they occur, allowing for proactive maintenance and minimized downtime.

In summary, the Emerson 10-30 kVA, 208V UPS offers a combination of modularity, high efficiency, advanced technologies, and effective power management features that cater to the demanding needs of critical applications. With its reliable performance and user-friendly operation, this UPS solution is an excellent choice for organizations looking to protect their valuable equipment from power disturbances.