Emerson 10-30kVA Inverter Output, Inverter output, Bypass Input Bypass input, Time Load

Page 47

UPS Specifications

6.4.4 Inverter Output

 

 

 

 

 

 

Table 14 Inverter output

 

 

 

 

 

 

 

 

 

 

 

 

 

Rated Power

10kVA

15kVA

 

20kVA

 

30kVA

 

 

 

 

 

 

 

Rated voltage, VAC

 

 

120/208

 

 

 

 

 

 

Supply

 

3-phase, 4-wire plus ground

 

 

 

 

 

 

 

Frequency, Hz

 

 

50 / 60

 

 

 

 

 

 

 

 

 

Rated Power, kW

8

12

 

16

 

24

 

 

 

 

 

 

Three -phase transient overload,

 

10 minutes - 105-125% load

 

min. load

 

1 minute - 126-150% load

 

 

 

 

Voltage Regulation %

±1.0% three-phase RMS average for a balanced three-phase load

 

 

±2.0% three-phase RMS average for a 100% unbalanced load

 

Frequency Regulation %

Nominal frequency regulation is ±0.05% in single module mode,

 

 

and+/- 0.25% in parallel mode.

 

 

 

 

Maximum rate of change of

For single mode, the slew rate is adjustable from 0.1Hz/s to 3Hz/s

 

frequency, Hz/sec

 

 

 

 

 

 

Current rating of neutral cable, A

 

1.5 x input current

 

 

 

 

 

 

 

 

6.4.5 Bypass Input Table 15 Bypass input

Rated Power

10kVA

 

15kVA

20kVA

 

30kVA

 

 

 

 

 

 

 

Rated voltage, VAC

 

120/208

 

 

 

 

 

 

 

Supply

 

 

Three-phase, 4-wire plus ground

 

 

 

 

 

 

 

 

Rated Current, A

 

 

 

 

 

 

208VAC

28

 

42

56

 

83

 

 

 

 

 

 

Bypass voltage tolerance %

Upper limit: +10%, +15% or +20%

Upper limit default: +15%

 

Lower limit: -10%, -20%, -30% or -40%

Lower limit default: -20%

 

 

 

Frequency, Hz

 

50 / 60

 

 

 

 

 

 

 

Input frequency tolerance %

 

 

± 10 or ± 20%; default ±10%

 

 

 

 

 

 

Current rating of neutral cable, A

 

 

1.5 x input current

 

 

 

 

Time

Load

 

Bypass overload capacity

 

Long-term operation:

<135% load

 

(all ratings)

 

 

10 minutes:

135% - 170% load

 

 

 

 

100milliseconds:

1000% full UPS rated output current

41

Image 47
Contents Liebert NX UPS Page Table of Contents Options Maintenance Bypass CabinetUPS Specifications Figures Tables Important Safety Instructions Battery Cabinet Precautions Glossary of Symbols Internal Inspections External InspectionsUPS Location Preliminary ChecksFinal Position Considerations in Moving the NXMechanical Considerations Special Considerations for 1+N Systems10-30kVA UPS Floor InstallationClearances Cable EntryOptional Cabinets Maintenance Bypass CabinetLiebert Lug Size and Torque Requirements Power CablingCable Rating Cabling Guidelines UPS Input ConfigurationInput busbars Cable ConnectionsSystem Output Safety GroundProtective Devices UPS Rectifier and Bypass Input SupplyDual Input Connections Cabling ProcedureOutput System Connections-Ensure Correct Phase Rotation Common Input ConnectionsControl Cables Internal UPS Battery ConnectionsMonitor Board Features Input Dry Contacts Dry ContactsBCB box interface Maintenance Bypass Cabinet InterfaceMaintenance bypass cabinet interface BCB Box InterfaceEPO input contact relays Output Dry ContactsEPO Input-Optional Firmware Before M200 Output dry contact relaysFirmware M200 or Later EPO wiring for firmware M200 or laterUPS Batteries SafetyIntroduction Removable retainer Tray handle Insulated post for cabling External Battery Cabinet InstallationMatching Battery Cabinets Connecting the BatteriesTop cable entry Batteries BCB plate Top cable entry Battery trays BCB plate and BCBBattery tray support Service shelf Installation Considerations Ends of supports Battery tray supports attachTo interior surface of NX Front door note notchedNon-Standard Batteries Connecting the Battery Cabinet to the UPSNormal UPS Mode Bypass SwitchLocating the Cabinet Bypass ModeMaintenance Mode Cable InstallationInput/Output Wiring Power Cable InstallationMaintenance bypass control wire location Line up cabinets so that mounting holes are aligned Bolting Cabinets TogetherLBS Cable DBS Cable and SettingsLoad Bus Synchronization Performance RequirementsGeneral Configuring Parallel System OperationFeatures of Parallel System Installing Parallel System Auxiliary Dry Contact Cables Power CablesInterconnecting Parallel Control Cables Parallel System Control CablesInput Distribution Normally Closed EPO Normally Open EPOCircuit Breaker Battery Circuit Breaker BoxAvailable battery circuit breaker boxes DimensionsBattery circuit breaker box connections Conformity and Standards UPS Mechanical CharacteristicsEnvironmental characteristics Mechanical characteristicsUPS terminal UPS Electrical CharacteristicsDC Intermediate Circuit Battery Manufacturers and ModelsInput Rectifier Time Load Inverter OutputInverter output Bypass Input Bypass inputInstallation Drawings Dimensions -top and bottom views Cable connections Location of internal batteries Battery 417mm 186mm 687mmW503 to W502 W501 3pcs W500 18pcs W506 to W507 W510 to W511 W502 to W503W504 to W505 W511 to W510 W507 to W506 W509 to W508 W505 to W504 W508 to W509Run From Conductors Liebert -supplied interconnect wiringRefer to for key to interconnection Maintenance Bypass interconnection Run From Conductors Cabinet Type Liebert-supplied interconnect wiringLineup detail-SlimLine distribution cabinet to NX Lineup detail-1+N Type a connection to NX Interconnect wiring-1+N Type a connection to NXLineup detail-1+N Type A1 connection to NX Interconnect wiring-1+N Type A1 connection to NXLineup detail-1+N Type B connection to NX Interconnect wiring-1+N Type B connection to NXLineup detail-1+N Type B1 connection to NX Interconnect wiring-1+N Type B1 connection to NXLineup detail-1+N Type C connection to NX Interconnect wiring-1+N Type C connection to NXLineup detail-1+N Type C1 connection to NX Interconnect wiring-1+N Type C1 connection to NXLineup detail-1+N Type D connection to NX Interconnect wiring-1+N Type D connection to NXUPS Lug Size and Torque Requirements Torque specificationsBattery torque rating Initial Torque Annual Torque Battery In-lb N-mCurrent Rating a OCP CB Size a Maintenance bypass cabinet electrical data single inputCurrent CB Size a Current Rating a CB Size a Maintenance bypass cabinet electrical data dual inputMulti-module bypass cabinet electrical data 200A E00, FR0 208 104 125 250 400 MR1 208 280 400 222 300 210 250 167 225 140 175 111 150 Maintenance bypass cabinet lug sizes Maintenance Bypass Cabinet Style, lb. kg Rating Battery cabinet physical characteristicsMaintenance Bypass Cabinet weights Distance to connection points on the NX UPS Maintenance bypass cabinet dimensionsMulti-module paralleling cabinet dimensions Cable Lengths Floor to Connection Point Inside UPSSpecifications and Technical Data Specifications and Technical Data Page That NetIti Tin
Related manuals
Manual 80 pages 38.9 Kb

10-30kVA specifications

The Emerson 10-30 kVA, 208V uninterruptible power supply (UPS) solution is a robust system designed to provide reliable power protection for critical applications in commercial and industrial settings. This UPS is ideal for safeguarding IT equipment, communication systems, and other sensitive electronics against power disturbances and interruptions.

One of the standout features of the Emerson 10-30 kVA UPS is its modular design, allowing for flexibility and scalability. This means that as the power needs of a facility grow, the UPS can be easily expanded without requiring a complete system overhaul. This modularity contributes to a more efficient use of resources and minimizes operational costs.

The UPS also incorporates advanced technologies such as double-conversion online architecture, which provides the highest level of power quality. This technology ensures that the output power is consistently clean and stable, effectively eliminating harmful voltage fluctuations and frequency variations. Consequently, connected load receives a pure sine wave output, preventing potential damage or operational issues with sensitive equipment.

Another key feature is the high efficiency rating of the Emerson UPS, which exceeds 95 percent in typical operating conditions. This high efficiency translates to reduced energy costs and a smaller carbon footprint, aligning with modern sustainability goals. The cooling system is designed to be efficient as well, ensuring optimal performance while maintaining a compact footprint.

The user-friendly interface enhances operability, featuring an intuitive LCD display that allows for easy monitoring of critical power parameters. Users can access real-time data related to battery health, load levels, and operational status, which aids in effective management of the power supply.

Battery management is another critical aspect of the Emerson UPS. It employs advanced battery management technologies to ensure optimal battery life and performance. Features such as intelligent battery testing and monitoring help predict potential battery failures before they occur, allowing for proactive maintenance and minimized downtime.

In summary, the Emerson 10-30 kVA, 208V UPS offers a combination of modularity, high efficiency, advanced technologies, and effective power management features that cater to the demanding needs of critical applications. With its reliable performance and user-friendly operation, this UPS solution is an excellent choice for organizations looking to protect their valuable equipment from power disturbances.