Emerson 10-30kVA installation manual Input Dry Contacts

Page 21

Electrical Connections

Figure 7 Auxiliary terminal block detail (Monitoring Board)

J8

J3J1

LCD

J2

 

 

 

 

 

 

Intellislot 2

J13

J21 J25

J28

J4

J26 J30

J10

Intellislot 1

BFP

INV ACF

EPO

Dry in

MBC

BCB

Intellislot 3

 

 

X1

X2

 

X3

 

 

 

 

 

 

 

J22

J23

J12

J9

J15

J16

J17

X4

J24

X7

X6

PWR

 

MODEM

X5

SNMP CARD

X4

NOTE: The black square ( ) on each slot indicates Pin 1.

2.3Dry Contacts

The UPS provides input dry contacts and output dry contacts.

2.3.1Input Dry Contacts

There are several input dry contacts at the X3 slot.

Figure 8 Input dry contacts

 

 

NOTE: The black square ( ) on each slot indicates Pin 1.

Table 1

Input dry contacts at X3

 

 

 

 

Position

Name

Description

 

 

 

 

 

J4.1

ENV3

Battery Room Alarm (N.C.)

 

J4.2

BtG

Battery Ground Fault Detection (N.C.)

 

 

 

 

 

J4.3

GEN1,2

Generator Join Detection (N.O.)

 

J4.4

+12V

+12V Power

 

 

 

 

 

1 - Must be configured by configuration software before becoming active.

2 - When activated, the charger current can be limited, via software, to a percentage of the full charger current (0-100%). 3 - Activating this feature turns the battery charger off.

15

Image 21
Contents Liebert NX UPS Page Table of Contents Maintenance Bypass Cabinet UPS SpecificationsOptions Figures Tables Important Safety Instructions Battery Cabinet Precautions Glossary of Symbols Internal Inspections External InspectionsUPS Location Preliminary ChecksMechanical Considerations Considerations in Moving the NXSpecial Considerations for 1+N Systems Final PositionClearances Floor InstallationCable Entry 10-30kVA UPSMaintenance Bypass Cabinet LiebertOptional Cabinets Power Cabling Cable RatingLug Size and Torque Requirements Cabling Guidelines UPS Input ConfigurationInput busbars Cable ConnectionsProtective Devices Safety GroundUPS Rectifier and Bypass Input Supply System OutputOutput System Connections-Ensure Correct Phase Rotation Cabling ProcedureCommon Input Connections Dual Input ConnectionsInternal UPS Battery Connections Monitor Board FeaturesControl Cables Input Dry Contacts Dry ContactsMaintenance bypass cabinet interface Maintenance Bypass Cabinet InterfaceBCB Box Interface BCB box interfaceEPO Input-Optional Firmware Before M200 Output Dry ContactsOutput dry contact relays EPO input contact relaysFirmware M200 or Later EPO wiring for firmware M200 or laterSafety IntroductionUPS Batteries Matching Battery Cabinets External Battery Cabinet InstallationConnecting the Batteries Removable retainer Tray handle Insulated post for cablingTop cable entry Battery trays BCB plate and BCB Battery tray support Service shelfTop cable entry Batteries BCB plate Installation Considerations To interior surface of NX Battery tray supports attachFront door note notched Ends of supportsNon-Standard Batteries Connecting the Battery Cabinet to the UPSNormal UPS Mode Bypass SwitchMaintenance Mode Bypass ModeCable Installation Locating the CabinetInput/Output Wiring Power Cable InstallationMaintenance bypass control wire location Line up cabinets so that mounting holes are aligned Bolting Cabinets TogetherLoad Bus Synchronization DBS Cable and SettingsPerformance Requirements LBS CableConfiguring Parallel System Operation Features of Parallel SystemGeneral Installing Parallel System Interconnecting Power CablesParallel Control Cables Parallel System Control Cables Auxiliary Dry Contact CablesInput Distribution Normally Closed EPO Normally Open EPOAvailable battery circuit breaker boxes Battery Circuit Breaker BoxDimensions Circuit BreakerBattery circuit breaker box connections Environmental characteristics UPS Mechanical CharacteristicsMechanical characteristics Conformity and StandardsUPS terminal UPS Electrical CharacteristicsBattery Manufacturers and Models Input RectifierDC Intermediate Circuit Inverter output Inverter OutputBypass Input Bypass input Time LoadInstallation Drawings Dimensions -top and bottom views Cable connections Location of internal batteries Battery 417mm 186mm 687mmW504 to W505 W511 to W510 W507 to W506 W509 to W508 W501 3pcs W500 18pcs W506 to W507 W510 to W511 W502 to W503W505 to W504 W508 to W509 W503 to W502Liebert -supplied interconnect wiring Refer to for key to interconnectionRun From Conductors Maintenance Bypass interconnection Run From Conductors Cabinet Type Liebert-supplied interconnect wiringLineup detail-SlimLine distribution cabinet to NX Lineup detail-1+N Type a connection to NX Interconnect wiring-1+N Type a connection to NXLineup detail-1+N Type A1 connection to NX Interconnect wiring-1+N Type A1 connection to NXLineup detail-1+N Type B connection to NX Interconnect wiring-1+N Type B connection to NXLineup detail-1+N Type B1 connection to NX Interconnect wiring-1+N Type B1 connection to NXLineup detail-1+N Type C connection to NX Interconnect wiring-1+N Type C connection to NXLineup detail-1+N Type C1 connection to NX Interconnect wiring-1+N Type C1 connection to NXLineup detail-1+N Type D connection to NX Interconnect wiring-1+N Type D connection to NXUPS Battery torque rating Torque specificationsInitial Torque Annual Torque Battery In-lb N-m Lug Size and Torque RequirementsMaintenance bypass cabinet electrical data single input Current CB Size aCurrent Rating a OCP CB Size a Current Rating a CB Size a Maintenance bypass cabinet electrical data dual inputMulti-module bypass cabinet electrical data 200A E00, FR0 208 104 125 250 400 MR1 208 280 400 222 300 210 250 167 225 140 175 111 150 Maintenance bypass cabinet lug sizes Battery cabinet physical characteristics Maintenance Bypass Cabinet weightsMaintenance Bypass Cabinet Style, lb. kg Rating Multi-module paralleling cabinet dimensions Maintenance bypass cabinet dimensionsCable Lengths Floor to Connection Point Inside UPS Distance to connection points on the NX UPSSpecifications and Technical Data Specifications and Technical Data Page Iti NetTin That
Related manuals
Manual 80 pages 38.9 Kb

10-30kVA specifications

The Emerson 10-30 kVA, 208V uninterruptible power supply (UPS) solution is a robust system designed to provide reliable power protection for critical applications in commercial and industrial settings. This UPS is ideal for safeguarding IT equipment, communication systems, and other sensitive electronics against power disturbances and interruptions.

One of the standout features of the Emerson 10-30 kVA UPS is its modular design, allowing for flexibility and scalability. This means that as the power needs of a facility grow, the UPS can be easily expanded without requiring a complete system overhaul. This modularity contributes to a more efficient use of resources and minimizes operational costs.

The UPS also incorporates advanced technologies such as double-conversion online architecture, which provides the highest level of power quality. This technology ensures that the output power is consistently clean and stable, effectively eliminating harmful voltage fluctuations and frequency variations. Consequently, connected load receives a pure sine wave output, preventing potential damage or operational issues with sensitive equipment.

Another key feature is the high efficiency rating of the Emerson UPS, which exceeds 95 percent in typical operating conditions. This high efficiency translates to reduced energy costs and a smaller carbon footprint, aligning with modern sustainability goals. The cooling system is designed to be efficient as well, ensuring optimal performance while maintaining a compact footprint.

The user-friendly interface enhances operability, featuring an intuitive LCD display that allows for easy monitoring of critical power parameters. Users can access real-time data related to battery health, load levels, and operational status, which aids in effective management of the power supply.

Battery management is another critical aspect of the Emerson UPS. It employs advanced battery management technologies to ensure optimal battery life and performance. Features such as intelligent battery testing and monitoring help predict potential battery failures before they occur, allowing for proactive maintenance and minimized downtime.

In summary, the Emerson 10-30 kVA, 208V UPS offers a combination of modularity, high efficiency, advanced technologies, and effective power management features that cater to the demanding needs of critical applications. With its reliable performance and user-friendly operation, this UPS solution is an excellent choice for organizations looking to protect their valuable equipment from power disturbances.