Emerson 10-30kVA installation manual Battery Cabinet Precautions

Page 8

! CAUTION

This equipment is fitted with RFI suppression filters.

Ground leakage current exceeds 3.5 mA and is less than 1000 mA.

Transient and steady-state ground leakage currents, which may occur when starting the equipment, should be taken into account when selecting instantaneous residual current circuit breakers (RCCBs) or residual current devices (RCDs).

RCCBs must be selected sensitive to DC unidirectional pulses (Class A) and insensitive to transient current pulses.

Note also that the ground leakage currents of the load will be carried by this RCCB or RCD.

! WARNING

Under typical operation and with all UPS doors closed, only normal safety precautions are necessary. The area around the UPS system should be kept free of puddles of water, excess moisture and debris.

Special safety precautions are required for procedures involving handling, installation and maintenance of the UPS system and the battery. Observe all safety precautions in this manual before handling or installing the UPS system. Observe all precautions in the Operation and Maintenance Manual, before as well as during performance of all maintenance procedures. Observe all battery safety precautions before working on or near the battery.

This equipment contains several circuits that are energized with high voltage. Only test equipment designed for troubleshooting should be used. This is particularly true for oscilloscopes. Always check with an AC and DC voltmeter to ensure safety before making contact or using tools. Even when the power is turned Off, dangerously high electric charges may exist within the UPS.

All power and control wiring should be installed by a qualified electrician. All power and control wiring must comply with the NEC and applicable local codes.

ONLY qualified service personnel should perform maintenance on the UPS system. When performing maintenance with any part of the equipment under power, service personnel and test equipment should be standing on rubber mats. The service personnel should wear insulating shoes for isolation from direct contact with the floor (earth ground).

Never work alone, even if all power is removed from the equipment. A second person should be standing by to assist and summon help in case an accident should occur.

! CAUTION

This unit complies with the limits for a Class A digital device, pursuant to Part 15 Subpart J of the FCC rules. These limits provide reasonable protection against harmful interference in a commercial environment. This unit generates, uses and radiates radio frequency energy and, if not installed and used in accordance with this instruction manual, may cause harmful interference to radio communications. This unit is not designed for use in a residential area. Operation of this unit in a residential area may cause harmful interference that the user must correct at his own expense.

Battery Cabinet Precautions

The following warning applies to all battery cabinets supplied with UPS systems. Additional warn- ings and cautions applicable to battery cabinets may be found in 3.0 - Battery Installation.

! WARNING

Internal battery strapping must be verified by manufacturer prior to moving a battery cabinet (after initial installation).

Battery cabinets contain non-spillable batteries.

Keep units upright.

Do not stack.

Do not tilt.

Failure to heed this warning could result in smoke, fire or electric hazard. Call 1-800-LIEBERT before moving battery cabinets (after initial installation).

2

Image 8
Contents Liebert NX UPS Page Table of Contents Options Maintenance Bypass CabinetUPS Specifications Figures Tables Important Safety Instructions Battery Cabinet Precautions Glossary of Symbols External Inspections Internal InspectionsPreliminary Checks UPS LocationConsiderations in Moving the NX Mechanical ConsiderationsSpecial Considerations for 1+N Systems Final PositionFloor Installation ClearancesCable Entry 10-30kVA UPSOptional Cabinets Maintenance Bypass CabinetLiebert Lug Size and Torque Requirements Power CablingCable Rating UPS Input Configuration Cabling GuidelinesCable Connections Input busbarsSafety Ground Protective DevicesUPS Rectifier and Bypass Input Supply System OutputCabling Procedure Output System Connections-Ensure Correct Phase RotationCommon Input Connections Dual Input ConnectionsControl Cables Internal UPS Battery ConnectionsMonitor Board Features Dry Contacts Input Dry ContactsMaintenance Bypass Cabinet Interface Maintenance bypass cabinet interfaceBCB Box Interface BCB box interfaceOutput Dry Contacts EPO Input-Optional Firmware Before M200Output dry contact relays EPO input contact relaysEPO wiring for firmware M200 or later Firmware M200 or LaterUPS Batteries SafetyIntroduction External Battery Cabinet Installation Matching Battery CabinetsConnecting the Batteries Removable retainer Tray handle Insulated post for cablingTop cable entry Batteries BCB plate Top cable entry Battery trays BCB plate and BCBBattery tray support Service shelf Installation Considerations Battery tray supports attach To interior surface of NXFront door note notched Ends of supportsConnecting the Battery Cabinet to the UPS Non-Standard BatteriesBypass Switch Normal UPS ModeBypass Mode Maintenance ModeCable Installation Locating the CabinetPower Cable Installation Input/Output WiringMaintenance bypass control wire location Bolting Cabinets Together Line up cabinets so that mounting holes are alignedDBS Cable and Settings Load Bus SynchronizationPerformance Requirements LBS CableGeneral Configuring Parallel System OperationFeatures of Parallel System Installing Parallel System Power Cables InterconnectingParallel Control Cables Parallel System Control Cables Auxiliary Dry Contact CablesInput Distribution Normally Open EPO Normally Closed EPOBattery Circuit Breaker Box Available battery circuit breaker boxesDimensions Circuit BreakerBattery circuit breaker box connections UPS Mechanical Characteristics Environmental characteristicsMechanical characteristics Conformity and StandardsUPS Electrical Characteristics UPS terminalDC Intermediate Circuit Battery Manufacturers and ModelsInput Rectifier Inverter Output Inverter outputBypass Input Bypass input Time LoadInstallation Drawings Dimensions -top and bottom views Cable connections Battery 417mm 186mm 687mm Location of internal batteriesW501 3pcs W500 18pcs W506 to W507 W510 to W511 W502 to W503 W504 to W505 W511 to W510 W507 to W506 W509 to W508W505 to W504 W508 to W509 W503 to W502Run From Conductors Liebert -supplied interconnect wiringRefer to for key to interconnection Maintenance Bypass interconnection Liebert-supplied interconnect wiring Run From Conductors Cabinet TypeLineup detail-SlimLine distribution cabinet to NX Interconnect wiring-1+N Type a connection to NX Lineup detail-1+N Type a connection to NXInterconnect wiring-1+N Type A1 connection to NX Lineup detail-1+N Type A1 connection to NXInterconnect wiring-1+N Type B connection to NX Lineup detail-1+N Type B connection to NXInterconnect wiring-1+N Type B1 connection to NX Lineup detail-1+N Type B1 connection to NXInterconnect wiring-1+N Type C connection to NX Lineup detail-1+N Type C connection to NXInterconnect wiring-1+N Type C1 connection to NX Lineup detail-1+N Type C1 connection to NXInterconnect wiring-1+N Type D connection to NX Lineup detail-1+N Type D connection to NXUPS Torque specifications Battery torque ratingInitial Torque Annual Torque Battery In-lb N-m Lug Size and Torque RequirementsCurrent Rating a OCP CB Size a Maintenance bypass cabinet electrical data single inputCurrent CB Size a Maintenance bypass cabinet electrical data dual input Current Rating a CB Size aMulti-module bypass cabinet electrical data 200A E00, FR0 208 104 125 250 400 MR1 208 280 400 222 300 210 250 167 225 140 175 111 150 Maintenance bypass cabinet lug sizes Maintenance Bypass Cabinet Style, lb. kg Rating Battery cabinet physical characteristicsMaintenance Bypass Cabinet weights Maintenance bypass cabinet dimensions Multi-module paralleling cabinet dimensionsCable Lengths Floor to Connection Point Inside UPS Distance to connection points on the NX UPSSpecifications and Technical Data Specifications and Technical Data Page Net ItiTin That
Related manuals
Manual 80 pages 38.9 Kb

10-30kVA specifications

The Emerson 10-30 kVA, 208V uninterruptible power supply (UPS) solution is a robust system designed to provide reliable power protection for critical applications in commercial and industrial settings. This UPS is ideal for safeguarding IT equipment, communication systems, and other sensitive electronics against power disturbances and interruptions.

One of the standout features of the Emerson 10-30 kVA UPS is its modular design, allowing for flexibility and scalability. This means that as the power needs of a facility grow, the UPS can be easily expanded without requiring a complete system overhaul. This modularity contributes to a more efficient use of resources and minimizes operational costs.

The UPS also incorporates advanced technologies such as double-conversion online architecture, which provides the highest level of power quality. This technology ensures that the output power is consistently clean and stable, effectively eliminating harmful voltage fluctuations and frequency variations. Consequently, connected load receives a pure sine wave output, preventing potential damage or operational issues with sensitive equipment.

Another key feature is the high efficiency rating of the Emerson UPS, which exceeds 95 percent in typical operating conditions. This high efficiency translates to reduced energy costs and a smaller carbon footprint, aligning with modern sustainability goals. The cooling system is designed to be efficient as well, ensuring optimal performance while maintaining a compact footprint.

The user-friendly interface enhances operability, featuring an intuitive LCD display that allows for easy monitoring of critical power parameters. Users can access real-time data related to battery health, load levels, and operational status, which aids in effective management of the power supply.

Battery management is another critical aspect of the Emerson UPS. It employs advanced battery management technologies to ensure optimal battery life and performance. Features such as intelligent battery testing and monitoring help predict potential battery failures before they occur, allowing for proactive maintenance and minimized downtime.

In summary, the Emerson 10-30 kVA, 208V UPS offers a combination of modularity, high efficiency, advanced technologies, and effective power management features that cater to the demanding needs of critical applications. With its reliable performance and user-friendly operation, this UPS solution is an excellent choice for organizations looking to protect their valuable equipment from power disturbances.