Emerson 250 installation manual Front View Side View

Page 21

 

 

 

Installation Drawings

Figure 8 Top cable entry routing and installation order

 

 

 

 

OUTPUT CONDUIT

 

 

 

INPUT CONDUIT

 

 

 

BYPASS CONDUIT

 

 

 

DC CONDUIT

 

DC (POSITIVE)

 

DC (POSITIVE)

 

DC (NEGATIVE)

 

 

 

 

 

GROUND (TOP ENTRY)

 

DC (NEGATIVE)

 

 

 

 

 

 

BYPASS NEUTRAL

 

BYPASS NEUTRAL

 

BYPASS INPUT

 

 

 

FAULT BRACE

 

FAULT BRACE

(PHASE C)

 

 

BYPASS INPUT

BYPASS INPUT

BYPASS INPUT

RECTIFIER INPUT

 

 

FAULT BRACE

(PHASE C)

FAULT BRACE

 

 

RECTIFIER INPUT

RECTIFIER INPUT

RECTIFIER INPUT

OUTPUT (PHASE C)

 

 

 

FAULT BRACE

 

FAULT BRACE

 

 

OUTPUT

 

OUTPUT

OUTPUT

 

 

 

 

GROUND

 

 

 

(BOTTOM ENTRY)

 

 

 

OUTPUT NEUTRAL

 

OUTPUT NEUTRAL

FRONT VIEW

SIDE VIEW

Recommended order of installation for cables: 1. DC Power

2. Bypass Neutral

3. Bypass Input Power (Phases A-B-C)

4. Rectifier Input Power (Phases A-B-C)

5. Output Power (Phases A-B-C)

6. Output Neutral

7. Ground

The cables must be routed around the fault braces. This is to prevent the cables from coming in contact with

other busbars.

17

Image 21 Contents
Liebert NXL Contacting Liebert for Support Product Warranty RegistrationTable of Contents Figures Important Safety Instructions Page Introduction SINGLE-MODULE Mechanical InstallationPreliminary Checks Environmental ConsiderationsSystem Composition PositioningCable Entry Maintenance Bypass CabinetUPS Electrical Installation Power CablesExternal Protective Devices Dual InputTop Cable Entry Power Cable Connection ProcedureExternal Interface Board connections layout Control Cable and CommunicationsEPO Input Dry Contact Dry ContactsControl Status Inputs Dry Contact Remote EPO inputSwitch Auxiliary Inputs Dry Contacts Control Status Output Dry ContactsLoad Bus Synch Connection Single-Module System Options Communication and MonitoringOptional Equipment Main components location, 250kVA Liebert NXL UPS Installation Drawings Top View Doors Open Doors and Inner Skins Removed Outline drawing, 300kVA Liebert NXL UPS Front Front View Side View Front View Right Side View Front Doors Removed Front Detail a Liebert NXL UPS specifications SpecificationsBattery & DC Parameters 250 300 400 Input ParametersEnvironmental Parameters 250 300 400 Physical Parameters and Standards, in mmLiebert NXL system and inverter efficiencies Current ratings-batteryCurrent ratings-rectifier input Current ratings-bypass inputRecommended conduit and cable sizes BatteryRectifier Input Bypass InputSeries Cable Size One Hole Two Hole Recommended lug sizesIti Ne tTi n That