Emerson 250 installation manual Important Safety Instructions

Page 5

IMPORTANT SAFETY INSTRUCTIONS

SAVE THESE INSTRUCTIONS

This manual contains important instructions that should be followed during installation of your Liebert NXLUPS.Read this manual thoroughly, paying special attention to the sections that apply to your installation, before working with the UPS. Retain this manual for use by installing per- sonnel.

! WARNING

Risk of electrical shock. Can cause personal injury or death.

This UPS has several circuits that are energized with high DC as well as AC voltages. Check for voltage with both AC and DC voltmeters before working within the UPS. Check for voltage with both AC and DC voltmeters before making contact.

Only properly trained and qualified personnel wearing appropriate safety headgear, gloves, shoes and glasses should be involved in installing the UPS or preparing the UPS for installation. When performing maintenance with any part of the equipment under power, service personnel and test equipment should be standing on rubber mats.

In case of fire involving electrical equipment, use only carbon dioxide fire extinguishers or those approved for use in fighting electrical fires.

Extreme caution is required when performing installation and maintenance.

Special safety precautions are required for procedures involving handling, installation and maintenance of the UPS system. Observe all safety precautions in this manual before handling or installing the UPS system. Observe all precautions in the Operation and Maintenance Manual, SL-25425, before as well as during performance of all maintenance procedures. Observe all DC safety precautions before working on or near the DC system.

! WARNING

Risk of heavy unit falling over. Improper handling can cause equipment damage, injury or death.

Exercise extreme care when handling UPS cabinets to avoid equipment damage or injury to personnel. The UPS module weight ranges from 3965 to 5250lb (1768 to 2381kg).

Locate center of gravity symbols and determine unit weight before handling each cabinet. Test lift and balance the cabinets before transporting. Maintain minimum tilt from vertical at all times.

Slots at the base of the modules cabinets are intended for forklift use. Base slots will support the unit only if the forks are completely beneath the unit.

Read all of the following instructions before attempting to move, lift, remove packaging from or preparing unit for installation.

! WARNING

Risk of electrical shock and fire. Can cause equipment damage, personal injury or death.

Under typical operation and with all UPS doors closed, only normal safety precautions are necessary. The area around the UPS system should be kept free of puddles of water, excess moisture and debris.

Only test equipment designed for troubleshooting should be used. This is particularly true for oscilloscopes. Always check with an AC and DC voltmeter to ensure safety before making contact or using tools. Even when the power is turned Off, dangerously high potential electric charges may exist at the capacitor banks and at the DC connections.

All wiring must be installed by a properly trained and qualified electrician. All power and control wiring must comply with all applicable national, state and local codes.

One person should never work alone, even if all power is disconnected from the equipment. A second person should be standing by to assist and to summon help in case of an accident.

1

Image 5 Contents
Liebert NXL Contacting Liebert for Support Product Warranty RegistrationTable of Contents Figures Important Safety Instructions Page Introduction SINGLE-MODULE Mechanical InstallationPreliminary Checks Environmental ConsiderationsSystem Composition PositioningCable Entry Maintenance Bypass CabinetUPS Electrical Installation Power CablesExternal Protective Devices Dual InputTop Cable Entry Power Cable Connection ProcedureExternal Interface Board connections layout Control Cable and CommunicationsEPO Input Dry Contact Dry ContactsControl Status Inputs Dry Contact Remote EPO inputLoad Bus Synch Connection Switch Auxiliary Inputs Dry ContactsControl Status Output Dry Contacts Optional Equipment Single-Module System OptionsCommunication and Monitoring Main components location, 250kVA Liebert NXL UPS Installation DrawingsTop View Doors Open Doors and Inner Skins Removed Outline drawing, 300kVA Liebert NXL UPS Front Front View Side View Front View Right Side View Front Doors Removed Front Detail a Liebert NXL UPS specifications SpecificationsBattery & DC Parameters 250 300 400 Input ParametersEnvironmental Parameters 250 300 400 Physical Parameters and Standards, in mmLiebert NXL system and inverter efficiencies Current ratings-batteryCurrent ratings-rectifier input Current ratings-bypass inputRecommended conduit and cable sizes BatteryRectifier Input Bypass InputSeries Cable Size One Hole Two Hole Recommended lug sizesIti Ne tTi n That