Installation Drawings

Figure 9 Bottom cable entry routing and installation order

 

DC (POSITIVE)

 

 

 

DC (NEGATIVE)

 

DC (POSITIVE)

 

GROUND (TOP ENTRY)

 

DC (NEGATIVE)

 

 

 

 

BYPASS NEUTRAL

 

BYPASS NEUTRAL

FAULT BRACE

 

FAULT BRACE

BYPASS INPUT

 

BYPASS INPUT

 

(PHASE C)

BYPASS INPUT

BYPASS INPUT

 

 

 

 

 

FAULT BRACE

RECTIFIER INPUT

FAULT BRACE

RECTIFIER INPUT

(PHASE C)

RECTIFIER INPUT

RECTIFIER

 

 

 

INPUT

FAULT BRACE

OUTPUT (PHASE C)

FAULT BRACE

 

OUTPUT

 

OUTPUT

OUTPUT

 

 

 

GROUND (BOTTOM ENTRY)

OUTPUT NEUTRAL

 

 

 

 

OUTPUT NEUTRAL

 

 

OUTPUT CONDUIT

INPUT CONDUIT

 

BYPASS CONDUIT

FRONT VIEW

DC CONDUIT

SIDE VIEW

 

Recommended order of installation for cables: 1.) Output Neutral

2.) Output Power (Phases A-B-C)

3.) Rectifier Input Power (Phases A-B-C)

4.) Bypass Input Power (Phases A-B-C)

5.) Bypass Neutral

6.) DC Power

7.) Ground

The cables must be routed around the fault braces. This is to prevent the cables from coming in contact with

other busbars.

18

Image 22 Contents
Liebert NXL Product Warranty Registration Contacting Liebert for SupportTable of Contents Figures Important Safety Instructions Page Preliminary Checks SINGLE-MODULE Mechanical InstallationIntroduction Environmental ConsiderationsPositioning System CompositionMaintenance Bypass Cabinet Cable EntryExternal Protective Devices Power CablesUPS Electrical Installation Dual InputPower Cable Connection Procedure Top Cable EntryControl Cable and Communications External Interface Board connections layoutControl Status Inputs Dry Contact Dry ContactsEPO Input Dry Contact Remote EPO inputControl Status Output Dry Contacts Switch Auxiliary Inputs Dry ContactsLoad Bus Synch Connection Communication and Monitoring Single-Module System OptionsOptional Equipment Installation Drawings Main components location, 250kVA Liebert NXL UPSTop View Doors Open Doors and Inner Skins Removed Outline drawing, 300kVA Liebert NXL UPS Front Front View Side View Front View Right Side View Front Doors Removed Front Detail a Battery & DC Parameters SpecificationsLiebert NXL UPS specifications 250 300 400 Input Parameters250 300 400 Physical Parameters and Standards, in mm Environmental ParametersCurrent ratings-rectifier input Current ratings-batteryLiebert NXL system and inverter efficiencies Current ratings-bypass inputRectifier Input BatteryRecommended conduit and cable sizes Bypass InputRecommended lug sizes Series Cable Size One Hole Two HoleTi n Ne tIti That