Emerson 250 Dry Contacts, EPO Input Dry Contact, Control Status Inputs Dry Contact

Page 13

UPS Electrical Installation

2.3.1Dry Contacts

Volt-free and isolated contacts are used for interfacing to customer connections external to the NXL unit. These circuits use at least 8mA of current at +24V.

NOTE

All auxiliary cables must be segregated from power circuits (for shielding), must be double- insulated and should be 12-24AWG (2.5-0.2mm2) stranded for maximum runs between 82-164 ft. (25 and 50m) respectively.

NOTE

If connection to more than one module is required, use a separate contact for each module.

EPO Input Dry Contact

Table 1

Remote EPO input

 

 

 

 

 

 

 

 

 

 

 

 

Terminal

 

 

Connects to

Description

Item

 

Block

 

Pin

(description of external item)

of interface

 

 

 

 

1

REPO Switch, normally open contact

Input, protected

 

 

 

 

 

 

 

Remote EPO Input

 

 

2

REPO Switch, common contact

+24V, 10mA,

TB0824

 

current limited

Form C

 

 

 

 

 

 

 

 

3

REPO Switch, normally closed contact, set

Input, protected

 

 

 

 

jumper J5: 1-2 to enable, 2-3 to disable

 

 

 

 

 

 

Control Status Inputs Dry Contact

The following inputs can sense either a normally open or normally closed contact.

Table 2

Control or status inputs

 

 

 

 

 

 

 

 

 

 

Terminal

 

Connects to

Description

 

Item

Block

Pin

(description of external item)

of interface

 

 

 

1

On generator switch, closed = on generator

Input, protected

On Generator Input

 

 

 

 

TB0816

2

On generator switch, common

+24V, 10mA,

Form C

 

current limited

 

 

 

 

 

 

 

3

On generator switch, closed = not on generator

Input, protected

 

 

 

 

 

 

 

 

 

1

Key status switch, closed = key removed

Input, protected

 

 

 

 

 

Key Status Input

TB0820

2

Key status switch, common

+24V, 10mA,

Form C

 

current limited

 

 

 

 

 

 

 

3

Key status switch, closed = key inserted

Input, protected

 

 

 

 

 

 

9

Image 13 Contents
Liebert NXL Contacting Liebert for Support Product Warranty RegistrationTable of Contents Figures Important Safety Instructions Page Introduction SINGLE-MODULE Mechanical InstallationPreliminary Checks Environmental ConsiderationsSystem Composition Positioning Cable Entry Maintenance Bypass CabinetUPS Electrical Installation Power CablesExternal Protective Devices Dual InputTop Cable Entry Power Cable Connection ProcedureExternal Interface Board connections layout Control Cable and CommunicationsEPO Input Dry Contact Dry ContactsControl Status Inputs Dry Contact Remote EPO inputControl Status Output Dry Contacts Switch Auxiliary Inputs Dry ContactsLoad Bus Synch Connection Communication and Monitoring Single-Module System OptionsOptional Equipment Main components location, 250kVA Liebert NXL UPS Installation DrawingsTop View Doors Open Doors and Inner Skins Removed Outline drawing, 300kVA Liebert NXL UPS Front Front View Side View Front View Right Side View Front Doors Removed Front Detail a Liebert NXL UPS specifications SpecificationsBattery & DC Parameters 250 300 400 Input ParametersEnvironmental Parameters 250 300 400 Physical Parameters and Standards, in mmLiebert NXL system and inverter efficiencies Current ratings-batteryCurrent ratings-rectifier input Current ratings-bypass inputRecommended conduit and cable sizes BatteryRectifier Input Bypass InputSeries Cable Size One Hole Two Hole Recommended lug sizesIti Ne tTi n That