Emerson 250 installation manual Power Cable Connection Procedure, Top Cable Entry

Page 11

UPS Electrical Installation

The following are guidelines only and superseded by local regulations and codes of practice where applicable:

Take special care when determining the size of the neutral cable (grounded conductor), because current circulating on the neutral cable may be greater than nominal current in the case of non- linear loads. Refer to the values in Table 6.

The grounding conductor should be sized according to the fault rating, cable lengths, type of pro- tection, etc. The grounding cable connecting the UPS to the main ground system must follow the most direct route possible.

Consideration should be given to the use of paralleled smaller cables for heavy currents, as this can ease installation considerably.

2.2.1Power Cable Connection Procedure

The rectifier input, bypass, output and battery power cables (all require lug type terminations) are connected to busbars situated in the I/O section as shown in Figures 7 through 9.

Equipment Ground

The equipment ground busbar is located in the I/O section as shown in Figure 7. The grounding con- ductor must be connected to the ground busbar and bonded to each cabinet in the system.

All cabinets and cabling should be grounded in accordance with local regulations.

NOTE

Proper grounding reduces problems in systems caused by electromagnetic interference.

! WARNING

Failure to follow adequate grounding procedures can result in electric shock hazard to personnel, or the risk of fire, should a ground fault occur.

All operations described in this section must be performed by properly trained and qualified electricians or technical personnel. If any difficulties are encountered, contact Liebert Services. See the back page of this manual for contact information.

The grounding and neutral bonding arrangement must be in accordance with local and national codes of practice.

Once the equipment has been positioned and secured, connect the power cables as described below (refer to the appropriate cable connection drawing in 4.0 - Installation Drawings):

1.Verify that the UPS equipment is isolated from its external power source and all the UPS power isolators are open. Check that these supplies are electrically isolated and post any necessary warning signs to prevent their inadvertent operation.

2.Open exterior and interior panels on the front of the I/O.

3.Connect the ground and any necessary main bonding jumper to the equipment ground busbar located in the I/O section.

4.Make power connections and tighten the connections to the proper torque according to one of the two procedures below, depending on the type of installation:

Ensure correct phase rotation.

Top Cable Entry (see Figure 8)

Bottom Cable Entry (see Figure 9)

Top Cable Entry

When making the power connections for top cable entry, the recommended order of pulling and installing cables is to start from the top connections to the bottom connections. The cables must be routed around the fault braces (see Detail in Figure 8). This is to prevent the cables from contacting other busbars. The recommended conduit layout is shown in Figure 7.

7

Image 11 Contents
Liebert NXL Contacting Liebert for Support Product Warranty RegistrationTable of Contents Figures Important Safety Instructions Page Environmental Considerations SINGLE-MODULE Mechanical Installation Introduction Preliminary ChecksSystem Composition PositioningCable Entry Maintenance Bypass CabinetDual Input Power CablesUPS Electrical Installation External Protective DevicesTop Cable Entry Power Cable Connection ProcedureExternal Interface Board connections layout Control Cable and CommunicationsRemote EPO input Dry ContactsEPO Input Dry Contact Control Status Inputs Dry ContactLoad Bus Synch Connection Switch Auxiliary Inputs Dry ContactsControl Status Output Dry Contacts Optional Equipment Single-Module System OptionsCommunication and Monitoring Main components location, 250kVA Liebert NXL UPS Installation DrawingsTop View Doors Open Doors and Inner Skins Removed Outline drawing, 300kVA Liebert NXL UPS Front Front View Side View Front View Right Side View Front Doors Removed Front Detail a 250 300 400 Input Parameters SpecificationsLiebert NXL UPS specifications Battery & DC ParametersEnvironmental Parameters 250 300 400 Physical Parameters and Standards, in mmCurrent ratings-bypass input Current ratings-batteryLiebert NXL system and inverter efficiencies Current ratings-rectifier inputBypass Input BatteryRecommended conduit and cable sizes Rectifier InputSeries Cable Size One Hole Two Hole Recommended lug sizesThat Ne tIti Ti n
Related manuals
Manual 35 pages 5.73 Kb