Emerson 7000 SERIES ATB Installation Inspection, Move ATS from Disconnected To Test Position

Page 5

INSTALLATION (continued)

Inspection 1

!

Do not force the Isolation Handle. Be sure that the sensing lead isolation contacts do not hit the male stabs head on, but rather slide on them.

 

 

sensing lead contact

IS

stab

 

TS

 

 

isolation contacts

 

 

 

Figure 1–5. Isolation contacts in TEST position.

 

Move ATS from DISCONNECTED To TEST Position

 

(without electrical power)

 

 

Action

Turn the Isolation Handle (Figure 1–3) clockwise approximately 7 or 8 turns.

Observe

The Transfer Switch should be pulled inward; the sensing lead isolation

contacts should make with the male stabs as shown in Figure 1–5.

 

 

Inspection 2

!

Do not force the Isolation Handle. Be sure that the isolation contact fingers make with the male stabs on both sides in the CONNECTED position.

IS TS

Figure 1–6. Isolation contacts CONNECTED

(CLOSED).

Move ATS From TEST To CONNECTED Position

(without electrical power)

With solenoid latch interference tag in place (Figure 1–2), continue slowly

Action turning the Isolation Handle clockwise until it stops (approximately 6 or 7 turns). Now remove the interference tag from the solenoid latch.

The Transfer Switch should be pulled inward; the isolation contact fingers

Observe should make with the male stabs as shown in Figure 1–6. Also check that the Bypass Switch switched neutral contacts have opened (Figure 1–4).

Inspection 3

!

Be sure that the isolation contacts disconnect in the TEST position; the sensing lead contacts should still touch the male stabs.

IS TS

Figure 1–7. Isolation contacts back in TEST position.

 

Move ATS From CONNECTED Back To TEST Position

 

(without electrical power)

 

 

Action

Turn the Isolation Handle (Figure 1–3) back counterclockwise until the

isolation contacts separate (approximately 6 or 7 turns).

 

 

The Transfer Switch should be pushed outward; the isolation contacts

Observe

should disconnect, but the sensing lead contacts should remain touching

 

as shown in Figure 1–7.

If all inspections are satisfactory connect harness plugs J2 and J5. Proceed to the Function Test.

1--4

Image 5
Contents Rating Label Table of ContentsNameplate Catalog Number IdentificationRemove the Transfer Switch InstallationTesting Power Conductors Supporting FoundationConnecting Power Conductors InstallationBus Connections HarnessesDo not apply any electrical power to the ATB yet Install the Transfer SwitchMove ATS from Disconnected To Test Position Installation InspectionVoltage Checks Automatic Transfer Bypass-Isolation SwitchFunctional Test Manual Operation Test Rotating Weight HandleAutomatic Transfer Turn and hold Transfer Control switch clockwise to TransferElectrical Operation Preventive Maintenance Testing & ServiceReplacement Parts Disconnecting the ControllerManual Load Transfer Testing & ServiceTROUBLE-SHOOTING Isolating Bypassing & IsolatingBypassing Bypassing & Isolating Transfer Switch RemovalTransfer Switch Reinstallation Transfer Test Return to ServiceTo change the position of transfer switch See Controller User’s Guide Index