SECTION 2 TESTING & SERVICE

TRANSFER TEST

Test the Automatic Transfer Switch portion of the 7000 Series ATB at least once a month. This procedure checks the electrical operation of the Transfer Switch and Controller. Put the engine–generator starting control (at the engine–generator set) in automatic mode.

In the following test the generator will start, the load will be transferred to the Emergency source, then back to the Normal source. An interruption to the load will occur, unless the the Transfer Switch contacts are bypassed be- fore the test. See page 3–1 for bypassing & isolating in- structions if no interruption of load is required.

!

Be sure to close the enclosure door

before proceeding to prevent personal injury

in case of electrical system fault.

Perform the five–stepElectrical Operation --- Transfer Test procedure on page 1–7.

PREVENTIVE MAINTENANCE

Reasonable care in preventive maintenance will insure high reliability and long life for the 7000 Series ATB. An annual preventive maintenance program is recom- mended.

ASCO Services, Inc. (ASI) is ASCO Power Technologies’s national service organization. ASI can be contacted at 1-800-800-2726 (ASCO) for in- formation on preventive maintenance agreements.

Checklist for Yearly Inspection

Hazardous voltage capable of causing shock,

burns, or death is used in this switch.

Deenergize both Normal -- Emergency power

sources before performing inspections!

jClean the ATS enclosure. Brush and vacuum away any excessive dust accumulation. Remove any mois- ture with a clean cloth.

j Check the transfer switch contacts. Remove transfer switch barriers and check the condition of the contacts. Replace contacts when pitted or worn excessively. Reinstall the barriers carefully.

jMaintain transfer switch lubrication. If switch is sub- jected to severe dust or abnormal operating conditions, renew factory lubrication on all movements and link- ages. Relubricate solenoid operator if TS coil is re- placed. Don’t use oil; order lubrication kit 75-100.

jCheck all cable connections & retighten them.

REPLACEMENT PARTS

Replacement parts are available in kit form. When or- dering parts provide the Serial No., Bill of Material No. (BOM), and Catalog No. from the transfer switch name- plate. Contact your local ASCO Power Technolgies sales office or ASI.

In the United States call 1--800--800--ASCO (2726)

In Canada call 1--888--234--ASCO (2726)

DISCONNECTING THE CONTROLLER

The harness disconnect plugs are furnished for repair purposes only and should not have to be unplugged. If the control panel must be isolated, follow these steps:

Bypass-- Isolation Switch is energized! Do not touch isolation contact fingers; shock, burns, or death could result!

Disconnecting the Plugs

1.Bypass and Isolate the Automatic Transfer Switch.

2.Open the upper enclosure door.

3.Separate the two quick disconnect plugs by squeez- ing the latches. Do not pull on the harness wires.

Reconnecting the Plugs

1.The ATS should be still bypassed and isolated.

2.The two harness plugs and sockets are keyed. Care- fully align the plugs with the sockets and press straight in until the latches click.

3.Close the enclosure doors.

4.Follow Return to Service instructions on page 3–3.

2--1

Image 9
Contents Rating Label Table of ContentsNameplate Catalog Number IdentificationRemove the Transfer Switch InstallationTesting Power Conductors Supporting FoundationConnecting Power Conductors InstallationBus Connections HarnessesDo not apply any electrical power to the ATB yet Install the Transfer SwitchMove ATS from Disconnected To Test Position Installation InspectionAutomatic Transfer Bypass-Isolation Switch Functional TestVoltage Checks Manual Operation Test Rotating Weight HandleTurn and hold Transfer Control switch clockwise to Transfer Electrical OperationAutomatic Transfer Preventive Maintenance Testing & ServiceReplacement Parts Disconnecting the ControllerTesting & Service TROUBLE-SHOOTINGManual Load Transfer Bypassing & Isolating BypassingIsolating Transfer Switch Removal Transfer Switch ReinstallationBypassing & Isolating Return to Service To change the position of transfer switchTransfer Test See Controller User’s Guide Index