ADJUSTMENTS (continued)
NOTICE
Do not make any setting changes while the controller is energized.
How to Change a Setting
1.Prevent the transfer switch from operating by discon- necting one source first, then the other, as follows:
a.If the transfer switch is in the Normal position, open the emergency source circuit breaker. Turn the engine starting control to off. Then open the normal source circuit breaker.
b.If the transfer switch is in the Emergency position, open the normal source circuit breaker. Turn engine starting control to test or run. Then open the emergency source circuit breaker.
2.Disconnect both harness plugs from controller by squeezing the latches. Do not pull on the wires.
3.Remove cover from the controller by releasing latch on right side with your thumb. See Figure
4.Locate the appropriate adjustment potentiometer or DIP switch for the setting that you want to change. Refer to Table
5.Use a small screwdriver to turn the potentiometer clockwise to increase the time delay or counter- clockwise to decrease it. See Figure
6.Use a
cover | thumb |
| latch |
hook on left side
Figure 4-1. Controller cover latch.
| 9 volt | |
| alkaline | |
| battery | |
| J5 battery | |
harness | on/off | |
jumper | ||
plugs | ||
| ||
| P1 | |
| retransfer | |
| to normal | |
| time delay | |
S3 DIP | P2 | |
transfer to | ||
switch | emergency | |
S1 DIP | time delay | |
| ||
switch |
| |
| S2 DIP | |
| switch |
Figure 4-2. Location of potentiometers.
7.Install the cover on the controller by hooking it on the left side and latching the right side.
8.Reconnect both harness plugs to the controller by aligning and pressing straight in until latches click.
Close the transfer switch enclosure door.
clockwise to increase
P1 or P2 potentiometer
counterclockwise to decrease
Figure 4-3. Changing time delay potentiometers.
9.Close the enclosure door, then restore both sources:
a.If the transfer switch is in the Normal position first close the normal source circuit breaker, then close the emergency source circuit breaker.
b.If the transfer switch is in the Emergency position, close the normal source circuit breaker. The load will be automatically retransferred to the normal source. Then close the emergency source circuit breaker.
10. Turn the engine starting control to automatic.
DIP
switches
SW1
SW2