Emerson 381333122 E manual Installation, Voltage Checks

Page 6

INSTALLATION (continued)

observe these lights

Figure 1–5. Standard controls and indicators.

2 – Voltage Checks

First check nameplate on transfer switch; rated voltage must be the same as normal and emergency line voltages.

Verify that the feeders have been connected to the proper lugs.

Use extreme caution when using a meter to measure voltages in the following steps. Do not touch power terminals; shock, burns, or death could result !

Perform steps 1 through 6 at the right. Observe the status lights. See Figure 1–5.

O Black circle means light is on.

P White circle means light is off.

* If necessary, adjust voltage regulator on the generator

according to the manufacturer’s recommendations. The

Close the normal source circuit

Source Accepted

breaker. The Normal Transfer

1 Switch Position and the Normal

Normal

Source Accepted lights should

Emergency

come on.

 

Use an accurate voltmeter to check phase to phase and

2 phase to neutral voltages pres- ent at the transfer switch normal source terminals.

Close the emergency source

Source Accepted

circuit breaker. (Start generator,

3 if necessary.) The Emergency

Normal

Source Accepted light should

Emergency

come on.

 

Use an accurate voltmeter to check phase to phase and

4 phase to neutral voltages pres- ent at the transfer switch emer- gency source terminals.*

Automatic Transfer Switch will respond only to the rated

Use a phase rotation meter to

A B C

voltage specified on the Transfer Switch nameplate.

Also see page 4–1 for the HI–LOW voltage adjust setting in the controller. The LOW setting shifts all voltage settings down 4.2%; for example, 240 V to 230 V.

5 check phase rotation of emer- gency source; it must be the same as the normal source.

Shut down the engine–genera-

 

tor, if applicable. The Emergen-

Source Accepted

cy Source Accepted light should

6 go off. Then put the starting

Normal

control selector switch (on the

Emergency

generator set) in the automatic

 

position. Close enclosure door.

 

Now continue to 3 – Electrical Operation on next page.

1--4

Image 6
Contents Operator’s Manual 381333-122 ENameplate Catalog Number Identification 1000 1200 1600 2000 2600 3000Installation Engine Starting Contacts Source fails Transfer switchController Ground Auxiliary CircuitsInstallation Functional Test ATS Position IndicatorsManual Operation Test Installation Voltage ChecksElectrical Operation Close the enclosure door firstSequence of Operation Transfer To EmergencyTesting & Service Preventive MaintenanceDisconnecting the Controller Proceed with care Automatic transfer switch is energized Testing & ServiceTROUBLE-SHOOTING Manual Load TransferSensor Adjustments AdjustmentsTime Delay Adjustment Time Delay SettingsAdjustments How to Change a SettingClose the enclosure door How to Set Built-In Timer Control Features Engine ExercisersDIP Switch Settings BUILT-IN Engine ExerciserControl Features Programmable Engine Exerciser ModuleFill in your settings for future reference Daylight Savings Time Adjust DisplayFast / Slow Adjust Display Navigating the MenuRemote Control Features Inphase Monitor For Motor Load TransferLoad Disconnect Feature Available Kits from Asco Control Features Optional Strip Heater AccessoryStrip Heater Accessory ControlsIndex