Technical Specification -- continued
EMC Type Tests -- Continued
Standard | Description | Compliance Level | Remarks |
|
|
|
|
IEEE1613, Power Substation Testing |
|
| |
|
|
|
|
IEEE1613, Clause 7.3.2 |
| Class 2 transverse mode | Surge fast transient |
|
| Class 1 common mode | waveform – power AC |
|
|
|
|
|
| Class 2 transverse mode | Surge fast transient |
|
| Class 1 common mode | waveform – power DC |
|
|
|
|
|
| Class 1 common mode | Surge fast transient |
|
|
| waveform – relay port |
|
|
|
|
|
| Class 1 common mode | Surge fast transient |
|
|
| waveform – Ethernet 10 |
|
|
| Mbps |
|
|
|
|
|
| Class 1 common mode | Surge fast transient |
|
|
| waveform – Ethernet 100 |
|
|
| Mbps |
|
|
|
|
IEEE1613, Clause 8 |
| Class 2 | Radio frequency |
|
|
| susceptibility |
|
|
|
|
IEEE1613, Clause 9 |
| Class 1 | ESD contact discharge 8kV |
|
|
|
|
Troubleshooting
If the industrial switch fails, isolate and correct the failure by determining the answers to the following questions and then taking the indicated action:
1. | Is the “PRI” (primary power) LED illuminated? | ||
| NO | Ensure the power source is the proper voltage | |
| • | ||
|
| VAC, 50/60Hz). |
|
| • | Ensure that the positive, negative, and ground wires from the power | |
|
| source are properly connected to the primary inputs. | |
| • | Contact Technical Support: | US/Canada: |
|
|
| International: |
| YES |
|
|
•Proceed to step 2.
2.
NO
•If the device does not have an auxiliary power source, proceed to step 3.
•Ensure the power source is the proper voltage
•Ensure that the positive, negative, and ground wires from the power source are properly connected to the auxiliary inputs.
•Contact Technical Support: US/Canada:
YES
•Proceed to step 3.
Troubleshooting -- continued
3.Is the “FAULT” LED illuminated?
NO
•Proceed to step 4.
YES
•Contact Technical Support: US/Canada:
4.For each port with a cable installed is either the “10MB” or the “100MB” LED illuminated?
YES
•Proceed to step 5.
NO
•For each port with a cable installed and its LED is OFF, check the cable for proper connection.
•For the fiber ports, verify that the TX and RX cables on the SIBTF10xx- 10x are connected to the RX and TX ports, respectively, on the device at the other end of the fiber cables.
•Contact Technical Support: US/Canada:
5.For each
•10MB is ON = The industrial switch has selected 10Mb/s operation.
•100MB is ON = The industrial switch has selected 100Mb/s operation.
•If the speed is not correct, disconnect and reconnect the cable to restart the initialization process.
•Proceed to step 6.
6.For each fiber port with a cable installed, is the “FD”
NO
•The industrial switch has selected
•If the mode is not correct, disconnect and reconnect cable to restart the initialization process.
•Check the cable for proper connection.
•Contact Tech Support:
YES
•The industrial switch has selected
•If the mode is not correct, disconnect and reconnect cable to restart the initialization process.
•Check the cable for proper connection.
•Contact Tech Support: