Adding or Replacing a DC PEM
Connecting DC Power
Warning Only a DC power source that is isolated from AC mains with reinforced insulation, and that complies with the other safety
Follow these steps to connect DC power to the Cisco 10005 ESR. Refer to
Figure 7.
Step 1 Ensure that power in the DC circuit is off.
Step 2 Ensure that the PEMs are fully inserted into the chassis and secured with their captive screws.
Step 3 Ensure that the circuit breaker on the newly installed PEM is set to 0 (Off).
Step 4 Turn the + and – screws on the new PEM’s terminal block
Step 5 Insert the battery return wire from the external power source into the receptacle labeled + (positive) on the PEM (Figure 7). The stripped part of the wire must be fully inserted so that no bare wire is exposed. Use the screwdriver to tighten the terminal screw to a torque of 1.5 to 1.8 newton meters (13.28 to
15.93
Warning The illustration shows the DC power supply terminal block. Wire the DC power supply as illustrated. The proper wiring sequence is ground to ground, positive to positive, and negative to negative. The ground wire must always be connected first and disconnected last.
| Cisco 10005 ESR DC Power Entry Module Installation |