General Considerations
to
Temperature
The attenuation of
Installation Recommendations
In addition to complying with the cable specifications presented in Sections 2.2 and 2.3, the cabling installation should comply with the following recommendations to obtain optimum performance from the network:
•UTP cabling should be free of splices, stubs, or bridged taps.
•No more than two
•Metal troughs, ducts, etc. carrying Token Ring signals should be properly grounded.
•Cables should be routed away from sources of electrical noise, such as power lines, fluorescent lights, electric motors, radio interference, and heavy machinery.
•Token Ring signals should not be routed through UTP cables that exit a building or which are adjacent to cables either exiting a building or exposed to lightning strikes and power surges.
•UTP cables that contain Token Ring signals should not be simultaneously used for applications which may impress high voltages (greater than 5 volts) with sharp rise or fall times, since the noise coupling from such signals could directly cause errors on the Token Ring network.
•For single telecommunications closet rings, lobe lengths should not exceed 100 meters of 22 to 24 AWG wire from the attaching device and the TCU port.