Tripp Lite APS 612 owner manual Configuration, DIP Switches

Page 5

Configuration

DIP Switches

Using a small tool, set the four “Battery Type / Voltage Point” Configuration DIP Switches (located on the front panel of your APS); see Diagram 4, p. 28.

• Select Battery Type (DIP Switch #1)

CAUTION:The Battery Type DIP Switch setting must match the type of batteries you connect or your batteries may be degraded or damaged over an extended period of time. See “Battery Selection,”page 6 for more information.

Battery Type

Switch Position

Gel Cell (Sealed) Battery

Up

Wet Cell (Vented) Battery

Down*

• Select High AC Voltage Switch To

Battery Point (DIP Switch #2)

Voltage

Switch Position

145V

Up

135V

Down*

4

3

2

1

Gel Cell

 

Wet Cell*

4 3 2 1 145V

135V*

• Select Low AC Voltage Switch To

Battery Point (DIP Switches #4 & #3)

Voltage

Switch Postion

105V

#4 Up & #3 Up

95V

#4 Up & #3 Down

85V

#4 Down & #3 Up

75V

#4 Down & #3 Down*

Most loads will perform adequately when your APS’s High AC Voltage Point DIP Switch #2 is set to 135V and its Low AC Voltage Point DIP Switches #3 and #4 are set to 95V. However, if your APS frequently switches to battery power due to momentary high/low line voltage swings that would have little effect on equipment operation, you may wish to adjust these settings. Your APS will switch to battery due to voltage swings the least if the High AC Voltage Switch to Battery Point is on its highest setting and the Low AC Voltage Switch to Battery Point is on its lowest setting.

4 3 2 1

105V

4 3 2 1

95V

4 3 2 1

85V

4 3 2 1

75V*

* Factory default settings.

5

Image 5
Contents APS 612 PowerVerter High Efficiency Output IntroductionStage Battery Charger APS Location Warnings DIP Switches ConfigurationSelecting Battery Amp Hour Capacity Battery SelectionSelecting Battery Type DC Ground Connection Battery ConnectionAC Connection Set Operating Mode SwitchAC Input Electrical Connection AC Output Electrical ConnectionIndicator Lights Switches, Indicator Lights & Other FeaturesSwitches Other Features Limited Warranty Maintenance & ServiceMaintenance ServiceSymptom Problems Corrections Two symbols are used on the APS labels AC Voltage DC Voltage Manual de Operación Salida de Alta Eficiencia IntroducciónProtección Automática contra Sobrecargas Luces Indicadoras de Funciones MúltiplesCargador Avanzado De 3 Etapas para Baterías Introducción continuaInversor con Salida de Frecuencia Controlada Tarjetas de Circuitos ProtegidasPrecauciones Sobre la Conexión de Baterías Precauciones Sobre la Ubicación del APSPrecauciones Sobre la Conexión de Equipos Precauciones de OperaciónInterruptores DIP ConfiguraciónSeleccione el Tipo de Baterías Interruptor DIP No Seleccione el Punto Bajo de Voltaje de CASeleccione el Tipo de Baterías Selección de BateríasSeleccione la Capacidad en Amperios/Hora de las Baterías Conexión de CD a Tierra Conexión de BateríasConexión de CA Regule el Interruptor Operating Mode Modo de OperaciónConexión de la Entrada Eléctrica de CA Conexión de la Salida Eléctrica de CALuces Indicadoras Interruptores, Luces Indicadoras y Otras CaracterísticasInterruptores Línea Encendida INV Encendido Otras CaracterísticasServicio Garantía LimitadaMantenimiento Simtoma Problemas Solucion Resolucion de ProblemasInversor Nota sobre el etiquetadoDiagrams/Esquemas Battery HI/MED/LO