Configuration
Set Configuration DIP Switches
Using a small tool, set the Configuration DIP Switches (located on the front panel of your unit, see diagram) to optimize Inverter/Charger operation depending on your application.
B4 | B3 | B2 | B1 |
Group B Dip Switches |
|
INPUT C/B
A4 | A3 | A2 | A1 |
| OUTPUT C/B 12A |
|
Group A Dip Switches
Group A DIP Switches
A1 Select Battery
A4 A3 A2 A1
CAUTION: The Battery Type DIP Switch setting must match the type of batteries you connect, or your batteries may be degraded or damaged over an extended period of time. See “Battery Selection,” p. 7 for more information.
Battery Type | Switch Position |
Gel Cell (Sealed) Battery | Up |
Wet Cell (Vented) Battery | Down (factory setting) |
A2 | Select Charger Enable/Inhibit |
|
|
|
|
|
|
|
|
| |
A4 | A3 | A2 | A1 | INHIBIT | |||||||
| (Model EMS1250UL only) |
|
|
| |||||||
|
|
|
|
|
|
|
|
|
Switch is preset to ENABLE, which permits continuous battery charging. If you are connecting the EMS1250UL
to batteries with a separate charger, you may set this ENABLE switch to INHIBIT to disable its
prevent overcharging.
Voltage | Switch Position |
|
| ||||||||||
Inhibit | Up |
|
|
|
|
|
|
|
|
|
| ||
Enable | Down (factory setting) |
|
| ||||||||||
|
|
|
|
|
|
|
|
|
| ||||
A2 | Select High AC Input Voltage Point |
|
|
|
|
|
|
|
|
|
|
| |
A4 |
| A3 |
| A2 |
| A1 |
| 145V | |||||
| for Switching to |
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
| ||||
| (Models EMS1012UL & EMS2012UL) |
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
| 135V | |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Voltage | Switch Position |
|
| 145V | Up |
|
| 135V | Down (factory setting) |
|
|
|
|
|
A4 A3 Select Low AC Input Voltage Point for Switching to
Voltage | Switch Position |
105V | #A4 Up & #A3 Up |
95V | #A4 Up & #A3 Down |
85V | #A4 Down & #A3 Up |
75V | #A4 Down & #A3 Down |
| (factory setting) |
A4 A3 A2 A1
A4 A3 A2 A1
A4 A3 A2 A1
A4 A3 A2 A1
*Most of your connected equipment will perform adequately when your Inverter/Charger’s High AC Input Voltage Point (DIP Switch #2 of Group A) is set to 135V and its Low AC Voltage Input Point (DIP Switches #3 and #4 of Group A) are set to 95V. However, if the unit frequently switches to battery power due to momentary high/low line voltage swings that would have little effect on equip- ment operation, you may wish to adjust these settings. By increasing the High AC Voltage Point and/or decreasing the Low AC Voltage Point, you will reduce the number of times your unit switches to battery due to voltage swings.
Group B DIP Switches
B1 B2 Select Load Sharing—OPTIONAL
Your Inverter/Charger features a
To reduce the chance of tripping this breaker, Inverter/Chargers may be set to automatically limit the charger output. This keeps the sum of the unit’s AC load and charge power within the circuit breaker rating. This