Tripp Lite 277/480V AC, 240/415V AC, 230/400V, 220/380V owner manual Shutdown Procedure

Page 14

Multiple UPS Operation (Parallel) (continued)

Shutdown Procedure

This procedure removes power from and shuts down the UPS power modules.

WARNING!

When shutting down individual UPS power modules in a parallel configuration, the user must ensure that the UPS power modules within the configuration that remain ON can collectively power the equipment load. If they cannot, the UPS power modules within the parallel configuration will be overloaded and will shut down and cease powering the equipment load.

NOTE!

Apply each step to each UPS power module within the parallel configuration before moving on to the next step.

Step 1. For each UPS power module in the parallel configuration which will be shut down, simultaneously press the “OFF” and “” Buttons and hold for 3 seconds. The power module's inverter will turn off; its LCD Screen will display “Output Close” and support of the equipment load will be transferred and shared equally among the other UPS power modules in the parallel configuration that have not yet been shut down. As each consecutive power module's inverter is turned off, however, a point will be reached where the power modules which have not yet been shut down will not be able to share the combined load. At this point, the remaining power modules will automatically shut down their inverters, transfer the load to reserve power and display “Bypass Mode” on their LCD Screens.

Step 2. Locate the external fuse block(s) on the battery module(s) and turn off (open) the fuses.

Step 3. Turn off (open) the “RECTIFIER INPUT” Breaker and “UPS OUTPUT” Breaker of each UPS power module.

Step 4. Wait approximately 5 minutes for the DC capacity to discharge. Press the “ON” and “OFF” Buttons of each UPS power module to test the inverter for adequate discharge of DC capacity. Then, for each UPS power module in turn, simultaneously press the “OFF” and “” Buttons to turn off their inverter. Confirm that BUS voltage is safe.

Step 5. Turn off (open) the “RESERVE INPUT” Breaker of each UPS power module.

Manual Maintenance Bypass Procedure

This procedure allows for routine maintenance by qualified service personnel. Tripp Lite recommends a routine maintenance inspection every six months. Note: since the power modules' inverters are bypassed during this procedure, the UPSs will not be able to switch to Back-Up Mode and support connected equipment in the event of a power failure.

Manual Maintenance Procedure (ON Bypass)

Step 1. For each UPS power module in the parallel configuration which will be placed on bypass, simultaneously press the “OFF” and “” Buttons and hold for 3 seconds. The power module's inverter will turn off; its LCD Screen will display “Output Close” and support of the equipment load will be transferred and shared equally among the other UPS power modules in the parallel configuration that have not yet been placed on bypass. As each consecutive power module's inverter is turned off, however, a point will be reached where the power modules which have not yet been placed on bypass will not be able to share the combined load. At this point, the remaining power modules will automatically shut down their inverters, transfer the load to reserve power and display “Bypass Mode” on their LCD Screens.

Step 2. Locate the external fuse block(s) on the battery module(s) and turn off (open) the fuses.

Step 3. Turn off (open) the “RECTIFIER INPUT” Breaker of each UPS power module.

Step 4. Wait approximately 5 minutes for the DC capacity to discharge. Press the “ON” and “OFF” Buttons of each UPS power module to test the inverter for adequate discharge of DC capacity. Then, for each UPS power module in turn, simultaneously press the “OFF” and “” Buttons to turn off their inverter. Confirm that BUS voltage is safe.

Step 5. Turn on (close) the “MANUAL BYPASS” Breaker of each UPS power module. Support of the equipment load will transfer to manual bypass. The LCD Screen of each UPS power module will display “Manual Bypass”.

Step 6. Turn off (open) the “UPS OUTPUT” Breaker, the “RESERVE INPUT” Breaker and the auxiliary power (+) and fan power (N) fuse isolators of each UPS power module. The LCD Screens will go dark.

Note: When the UPSs are in Maintenance Bypass Mode, no high voltages will be present within the UPS power modules except at the terminals and the “MANUAL BYPASS” Breakers.

Manual Maintenance Procedure (OFF Bypass):

Step 1. Turn on (close) the “UPS OUTPUT” Breaker, the “RESERVE INPUT” Breaker and the auxiliary power (+) and fan power (N) fuse isolators of each UPS power module. Support of the equipment load will transfer to manual bypass. The LCD Screens will display “Manual Bypass”.

Step 2. Turn off (open) the “MANUAL BYPASS” Breaker of each UPS power module. Support of the equipment load will transfer to reserve power. The LCD Screens will display “Bypass Mode”.

Step 3. Turn on (close) the “RECTIFIER INPUT” breaker of each UPS power module and wait approximately 30 seconds. Step 4. Locate the external fuse block(s) on the battery module(s) and turn on (close) the fuses.

Step 5. For each UPS power module to be taken off bypass, simultaneously press the “ON” and “” Buttons and hold for 3 seconds. The inverter will turn on and voltage will build for about 30 seconds. The load will be transferred to the inverter. The LCD Screens will display “Normal Mode”.

Step 6. Measure the voltage on the UPS “OUTPUT” Breaker of each power module to determine if it is normal or abnormal. If the output voltage is normal, turn on (close) the “OUTPUT” Breakers of each power module to supply power to the load. After approximately 30 seconds, the UPS will automatically execute a battery test.

14

Image 14
Contents Español Important Safety Warnings Safety WarningsControl Panel 160kVA-200kVA Power Module Breakers, Switches and Fuses50kVA-120kVA Power Module Installation Checklist Communication InterfaceConnection Checklist Parallel Wiring DiagramsOperational Modes Start-Up Procedure Shutdown Procedure Manual Maintenance Bypass ProcedureMultiple UPS Operation Parallel Multiple UPS Operation Parallel Multiple UPS Operation Parallel Start-Up Procedure Shutdown Procedure Main Menu Parameter Setting Sub-Menu System Control Sub-Menu Event Log Sub-MenuOther Information Sub-Menu Dry-Contacts Remote Emergency Power Off EPO Generator Contact Ethernet PowerRS-232 Port/Ethernet Port/SNMP Card Slot RS-485 Ports UPS Parallel Communication PortsLimited Warranty Manual del propietario Advertencias sobre la conexión del no-break Advertencias de seguridad importantesAdvertencias sobre la ubicación del no-break Advertencias sobre la conexión de equiposAdvertencias de seguridad importantes continúa Panel de ControlModulo DE Energia DE 160kVA-200kVA Características del módulo de potencia continuaciónModulo DE Energia DE 50kVA-120kVA Interfaz de comunicación Lista de verificación de la instalaciónLista de verificación de la conexión Carga Operación de un no-break continuación Operación de un no-break continuación Modos de operación Interruptor automático de Derivación manualOperación de varios no-break En paralelo continuación Flujo de energía Interruptor automático deSalida no-break ¡NOTA ¡ADVERTENCIA Modo Normal Menú principalSubmenú Configuración de parámetros Navegación en pantalla LCD continuaciónSubmenú Control del sistema Submenú Registro de eventosSubmenú Otra información AÑO 5 DÍA 13 Hora 5 MINContactos secos Desconexión remota de emergencia EPOAlimentación Ethernet Comunicaciones continuaciónRanura de tarjeta de Puerto RS-232/Puerto Ethernet/SNMP Contacto del generadorPuertos RS-485 Puertos paralelos de comunicación del no-breakGarantía Limitada Phase UPS Specifications Addendum-50kVA & Above Terminal Wiring Diagrams Battery+Rectifier Reserve Breaker Breaker Input Output Ground Battery Cabinet Ground Page Input Battery Output Ground Cabinet English Diagramas de cableado de terminales Tierra De la Batería Batería aInterruptor Interruptor Del de reserva rectificador Entrada Salida Tierra Batería Gabinete De la batería a Conexión eléctrica continúa Entrada Bateria Reserva Salida Tierra

220/380V, 277/480V AC, 230/400V, 240/415V AC specifications

Tripp Lite is a renowned manufacturer in the field of power solutions, offering a wide range of products designed to meet various electrical and connectivity requirements. Among its extensive portfolio, Tripp Lite provides effective AC power distribution units (PDUs) that support multiple voltage configurations, including 240/415V AC, 230/400V AC, 277/480V AC, and 220/380V. These PDUs are essential for managing power within industrial, commercial, and data center environments.

One of the main features of Tripp Lite's AC PDUs is their versatility in handling different voltage inputs, which allows them to cater to a wide range of global electrical standards. This feature is crucial for businesses operating in multiple regions or those with diverse electrical equipment that require specific voltage levels. The PDUs are equipped with multiple outlet configurations, ensuring compatibility with various types of plugs used in different countries.

Safety is another critical aspect of Tripp Lite’s design, with built-in protections such as surge protection and circuit breakers. These enhancements help safeguard connected devices from power surges, spikes, and overloads, ultimately reducing the risk of damage and downtime. Additionally, the units are constructed with high-quality materials to ensure durability and reliable performance, even under demanding conditions.

Tripp Lite also integrates advanced technologies into its PDUs to enhance functionality and user experience. Features such as remote monitoring capabilities allow users to track power usage, load balance, and environmental conditions in real time. This data is invaluable for optimizing energy management and ensuring that power distribution is both efficient and effective.

The compact design of Tripp Lite PDUs makes them easy to install in various spaces, including server racks and telecommunications closets. With options for vertical or horizontal mounting, users can customize their setup to best fit their needs. In terms of cooling efficiency, many of these PDUs are designed to facilitate optimal airflow, further enhancing the lifespan of connected equipment.

Tripp Lite’s commitment to delivering high-quality power solutions is evident in their warranty and customer support services. With years of industry experience, Tripp Lite stands out as a reliable partner for businesses looking to enhance their power management systems. The combination of advanced features, robust safety mechanisms, and versatile voltage compatibility makes Tripp Lite PDUs an excellent choice for any organization seeking dependable AC power solutions.