Page 3

Important Safety Warnings (continued)

Connect only Tripp Lite battery modules to the UPS's external battery hardware terminals.

Do not operate the UPS without batteries.

Fuses should be replaced only by factory authorized personnel. Blown fuses should be replaced only with fuses of the same number and type.

Potentially lethal voltages exist within the UPS as long as the battery supply is connected. Service and repair should be done only by trained personnel. During any service work, the UPS should be turned off or put into manual bypass and fuses removed from all connected battery modules.

Do not connect or disconnect the battery modules while the UPS is operating from the battery supply or when the unit is not in bypass mode.

Power Module Features

There are two separate UPS system modules: a power module and a battery module. Familiarize yourself with the location and function of the features on each module before installing and operating the UPS system. The power module is described below. The battery module is described in a separate manual.

Control Panel

1LCD Display: This backlit display indicates a wide range of UPS operating conditions and diagnostic data. It will illuminate after the UPS has been properly installed and started up.

2MAINTENANCE BYPASS LED: This red LED will illuminate when the UPS is providing filtered mains power without engaging its converter or inverter. Connected equipment will not receive battery power in the event of a blackout when this light is illuminated.

3RESERVE POWER LED: This green LED will illuminate to indicate the presence of a reserve power breaker and reserve power source connected to the UPS.

4RECTIFIER LED: This green LED will illuminate to indicate the UPS rectifier is operating.

5BATTERY LED: This orange LED will illuminate when the UPS is discharging the battery to provide connected equipment with AC power.

6INVERTER LED: This green LED will illuminate constantly to indicate the UPS inverter is activated.

7RESERVE POWER STATIC SWITCH LED: This green LED will illuminate when the UPS is powering connected equipment through a reserve power source connected to the UPS.

8INVERTER MC LED: This green LED will illuminate to indicate connected equipment is supplied with power through the UPS inverter.

9AC OUTPUT LED: This green LED will illuminate constantly to indicate your UPS is supplying AC power to connected equipment.

10

 

EMERGENCY POWER OFF Button: In case of emergency, press this button to turn off the UPS rectifier, inverter and output. After

 

 

 

pressing the button, it will remain down until reset. To reset the UPS system and restore output, press the EMERGENCY POWER OFF

 

 

 

button until it pops back up.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ON Button: This button, when used

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

11

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

with the ￿ button, turns the UPS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

inverter on. To turn the UPS inverter

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7

 

 

 

 

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

on, simultaneously press the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8

 

 

 

 

 

 

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ON and ￿ buttons and hold for 3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

seconds before releasing.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF Button: This button, when used

 

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

with the ￿ button, turns the UPS

 

 

4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

inverter off. To turn the inverter off,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

9

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

simultaneously press the OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

and ￿ buttons and hold for 3 seconds

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

before releasing.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13￿ , ￿ and ￿ Buttons: These buttons

control the LCD Display and setting

10

parameters.

 

11

 

12

 

13

CONTROL PANEL

3

Image 3
Contents Español Safety Warnings Important Safety WarningsControl Panel Breakers, Switches and Fuses 50kVA-120kVA Power Module160kVA-200kVA Power Module Communication Interface Installation ChecklistParallel Wiring Diagrams Connection ChecklistOperational Modes Start-Up Procedure Manual Maintenance Bypass Procedure Shutdown ProcedureMultiple UPS Operation Parallel Multiple UPS Operation Parallel Multiple UPS Operation Parallel Start-Up Procedure Shutdown Procedure Main Menu Parameter Setting Sub-Menu Event Log Sub-Menu System Control Sub-MenuOther Information Sub-Menu Dry-Contacts Remote Emergency Power Off EPO Ethernet Power RS-232 Port/Ethernet Port/SNMP Card SlotGenerator Contact UPS Parallel Communication Ports RS-485 PortsLimited Warranty Manual del propietario Advertencias sobre la conexión de equipos Advertencias de seguridad importantesAdvertencias sobre la ubicación del no-break Advertencias sobre la conexión del no-breakPanel de Control Advertencias de seguridad importantes continúaCaracterísticas del módulo de potencia continuación Modulo DE Energia DE 50kVA-120kVAModulo DE Energia DE 160kVA-200kVA Lista de verificación de la instalación Interfaz de comunicaciónLista de verificación de la conexión Carga Operación de un no-break continuación Operación de un no-break continuación Interruptor automático de Derivación manual Modos de operaciónFlujo de energía Interruptor automático de Operación de varios no-break En paralelo continuaciónSalida no-break ¡NOTA ¡ADVERTENCIA Menú principal Modo NormalNavegación en pantalla LCD continuación Submenú Configuración de parámetrosSubmenú Registro de eventos Submenú Control del sistemaAÑO 5 DÍA 13 Hora 5 MIN Submenú Otra informaciónDesconexión remota de emergencia EPO Contactos secosContacto del generador Comunicaciones continuaciónRanura de tarjeta de Puerto RS-232/Puerto Ethernet/SNMP Alimentación EthernetPuertos paralelos de comunicación del no-break Puertos RS-485Garantía Limitada Phase UPS Specifications Addendum-50kVA & Above Battery+ Terminal Wiring DiagramsRectifier Reserve Breaker Breaker Input Output Ground Battery Cabinet Ground Page Input Battery Output Ground Cabinet English Tierra De la Batería Batería a Diagramas de cableado de terminalesInterruptor Interruptor Del de reserva rectificador Entrada Salida Tierra Batería Gabinete De la batería a Conexión eléctrica continúa Entrada Bateria Reserva Salida Tierra

220/380V, 277/480V AC, 230/400V, 240/415V AC specifications

Tripp Lite is a renowned manufacturer in the field of power solutions, offering a wide range of products designed to meet various electrical and connectivity requirements. Among its extensive portfolio, Tripp Lite provides effective AC power distribution units (PDUs) that support multiple voltage configurations, including 240/415V AC, 230/400V AC, 277/480V AC, and 220/380V. These PDUs are essential for managing power within industrial, commercial, and data center environments.

One of the main features of Tripp Lite's AC PDUs is their versatility in handling different voltage inputs, which allows them to cater to a wide range of global electrical standards. This feature is crucial for businesses operating in multiple regions or those with diverse electrical equipment that require specific voltage levels. The PDUs are equipped with multiple outlet configurations, ensuring compatibility with various types of plugs used in different countries.

Safety is another critical aspect of Tripp Lite’s design, with built-in protections such as surge protection and circuit breakers. These enhancements help safeguard connected devices from power surges, spikes, and overloads, ultimately reducing the risk of damage and downtime. Additionally, the units are constructed with high-quality materials to ensure durability and reliable performance, even under demanding conditions.

Tripp Lite also integrates advanced technologies into its PDUs to enhance functionality and user experience. Features such as remote monitoring capabilities allow users to track power usage, load balance, and environmental conditions in real time. This data is invaluable for optimizing energy management and ensuring that power distribution is both efficient and effective.

The compact design of Tripp Lite PDUs makes them easy to install in various spaces, including server racks and telecommunications closets. With options for vertical or horizontal mounting, users can customize their setup to best fit their needs. In terms of cooling efficiency, many of these PDUs are designed to facilitate optimal airflow, further enhancing the lifespan of connected equipment.

Tripp Lite’s commitment to delivering high-quality power solutions is evident in their warranty and customer support services. With years of industry experience, Tripp Lite stands out as a reliable partner for businesses looking to enhance their power management systems. The combination of advanced features, robust safety mechanisms, and versatile voltage compatibility makes Tripp Lite PDUs an excellent choice for any organization seeking dependable AC power solutions.