Modbus Settings
Setting | Value | Notes | |
| Modbus RTU Slave1 | Set the Modbus type of the | |
| 2 | ||
Attached Serial Device type | Modbus ASCII Slave | serial device attached to | |
Modbus RTU Master3 | |||
| NPort 6110’s serial port. | ||
| Modbus ASCII Master4 |
| |
|
| NPort Modbus Gateway | |
| 100 to 3276 ms; | provides this setting for | |
Initial delay time | those PLCs that need a | ||
default = 100 ms | |||
| longer time for their | ||
|
| ||
|
| system to be initialized. | |
Modbus/TCP Slave device setting |
| ||
| IP address assigned to | Valid when the attached | |
Remote Modbus Slave IP | the remote Modbus | serial device is a Modbus | |
| slave device. | RTU/ASCII Master. | |
| default = 502 | Set this value to 0 (zero) to | |
TCP Port No. | disable the corresponding | ||
|
| Modbus/TCP slave device. | |
| 1 to 247 | The unique Modbus ID | |
ID No. Range | number assigned to the | ||
|
| Modbus device.5 |
Additional Information
1.When the serial Modbus device is running in Modbus/RTU Slave mode, the NPort Modbus Gateway is ready to connect automatically to Modbus/TCP Master devices. Up to 7 Modbus/TCP master devices can connect to one serial Modbus slave device.
2.Modbus ASCII Slave mode works the same as Modbus/RTU slave mode, except that the data format is Modbus/ASCII.
3.When the serial Modbus device is running in Modbus/RTU Master mode, the NPort Modbus Gateway is ready to connect automatically to Modbus/TCP slave devices. You will also need to configure the IP address for up to 4 Modbus/TCP slave devices that can be connected to over the Ethernet network.