Moxa Technologies NPort 6110 user manual

Page 32

when Auto Slave Unit ID is “Disabled.”

2.When the Modbus serial protocol is set to Modbus/RTU, each message packet is determined by a character timeout. An incorrect character timeout might cause a CRC checksum error. NPort Modbus Gateway allows a variable character time out setting, ranging from 10 to 3000 ms, when the attached serial device is set to Modbus/RTU.

3.This setting is in effect when the Modbus Gateway connects a Modbus/TCP Master with Modbus serial slave devices. When the Modbus Gateway can’t get a response from Modbus serial devices, the Modbus serial protocol will not respond to the master device. However, the TCP protocol has a longer waiting time, which could cause a network traffic problem for Modbus/TCP. For this reason, Modbus Gateway can automatically send a Modbus Exception Code 16 to the Modbus/TCP master device when there is no response from the Modbus serial slave devices, making overall network communication much more efficient.

Yes:

default.

No:

No Modbus/TCP exception handling.

4-11

Image 32
Contents NPort 6110 Modbus/TCP To Serial Communication Gateway NPort 6110 Modbus/TCP To Serial Communication Gateway Moxa Internet Services Table of Contents Page Introduction OverviewFeatures Powerful operation modes for versatile Modbus applicationsProduct Specifications LANPackage Checklist EnvironmentalFront/Top/Rear/Bottom Panel Views Getting Started Power ConnectionSerial Installation Ethernet Installation Software InstallationPage Page Page Page Housing DIN-RailWall Mount Typical Modbus Applications Connect all Modbus devices over the Ethernet network… Link the Serial Master device with Ethernet Slave devices… Configuring Modbus Gateway Starting Modbus Gateway Configurator Specify by IP Address Searching for NPortBroadcast Search Modify Configuration Network Settings Modbus Settings AlphanumericPage Page Advanced Modbus Settings IP address Page Modbus Serial Settings RTS/CTS Uart Fifo Password Unlock Upgrade FirmwareOther Functions Page Remote Monitoring and Management Start Log MonitorPage Troubleshooting ID No. mismatchPin Assignments DB9 Male PinoutsDeclaration of Conformity Problem Report Form NPort 6110 Modbus GatewayReturn Procedure