Advanced Modbus Settings

Setting

Value

Notes

 

Enable (Default)

Select Enable when

Auto Slave Unit ID

multiple Modbus devices

 

 

are accessible at the same

Disable

 

 

IP address.

1

 

 

 

 

10 to 3000 ms

This parameter is active

Character Timeout

when the attached serial

(default = 100 ms)

device is set to

 

 

Modbus/RTU.2

 

 

Allows you to configure

 

10 to 3000 ms

the message timeout for

Message Timeout

communication between

(default = 1000 ms)

 

connected Ethernet or

 

 

 

 

serial Modbus devices.

 

 

This parameter is active

 

 

when the Modbus

Modbus/TCP Exception

default = 502

Gateway connects a

Modbus/TCP Master with

 

 

 

 

Modbus serial slave

 

 

devices.3

 

Additional Information

1.Modbus/TCP protocol contains a “Unit ID” field to identify multiple Modbus slave devices accessible at a single IP address. When the Modbus/TCP command contains a Unit ID, the Modbus Gateway can pass the Unit ID to Modbus serial devices. This allows you to link to multiple serial devices with a Modbus Gateway. Some PLCs assume that each IP connects to only one device. In these cases, the Unit ID can be set “0,” but you must manually assign a Unit ID (between 1 and 247) to the connected serial device. However, each Modbus Gateway can connect to only one serial device.

This setting is valid when [Attached Serial Device type] is set to [Modbus RTU Slave ] or [Modbus ASCII Slave].

Enable: Uses the Unit ID in the Modbus/TCP packet. This is the default

 

setting.

Disable: Uses the predefined Unit ID instead of Modbus/TCP’s.

ID:

The predefined Unit ID value, ranging from 1 to 247, which is valid

4-10

Image 31
Contents NPort 6110 Modbus/TCP To Serial Communication Gateway NPort 6110 Modbus/TCP To Serial Communication Gateway Moxa Internet Services Table of Contents Page Overview IntroductionPowerful operation modes for versatile Modbus applications FeaturesLAN Product SpecificationsEnvironmental Package ChecklistFront/Top/Rear/Bottom Panel Views Serial Installation Power ConnectionGetting Started Software Installation Ethernet InstallationPage Page Page Page DIN-Rail HousingWall Mount Typical Modbus Applications Connect all Modbus devices over the Ethernet network… Link the Serial Master device with Ethernet Slave devices… Configuring Modbus Gateway Starting Modbus Gateway Configurator Broadcast Search Searching for NPortSpecify by IP Address Modify Configuration Network Settings Alphanumeric Modbus SettingsPage Page Advanced Modbus Settings IP address Page Modbus Serial Settings RTS/CTS Uart Fifo Password Other Functions Upgrade FirmwareUnlock Page Start Log Monitor Remote Monitoring and ManagementPage ID No. mismatch TroubleshootingDB9 Male Pinouts Pin AssignmentsDeclaration of Conformity NPort 6110 Modbus Gateway Problem Report FormReturn Procedure