TP-Link TL-SG1016D/TL-SG1008, TL-SG1204D/TL-SG1016 manual Requirements for Cabling Indoors

Page 16

Gigabit Unmanaged Switch

Requirements for Cabling Indoors

When cabling indoors, keep a certain distance away from the devices that may cause high-frequency interferences, such as down-conductor cable, powerline, power transformer and electromotor.

The main cable should be paved in the metal raceway of the access shaft. When cabling, keep the loop area formed by the cable itself as small as possible.

Requirements for the distance between Ethernet cable and other pipelines are shown in the table.

 

Ethernet Cable

 

Other Pipelines

 

 

Min Parallel Net Length L

Min Parallel-overlapping

 

(mm1

Net Height H (mm1

 

 

 

Down-conductor

1000

300

 

 

 

PE

50

20

 

 

 

Service pipe

150

20

 

 

 

Compressed air pipe

150

20

 

 

 

Thermal pipe (not wrapped1

500

500

 

 

 

Thermal pipe (wrapped1

300

300

 

 

 

Gas pipe

300

20

 

 

 

The two diagrams below demonstrate parallel net length and parallel-overlapping net height.

Note: The above minimum net length/height is required when metal raceway is not used. If any requirements cannot be met, you can add a steel tube or metal raceway for shielding.

Requirements for the distance between Ethernet cable and high-power electric devices are in following tables.

Cable

Pave Way

Min Parallel

Length (mm1

 

 

 

 

 

 

Parallel cabling

130

<2kVA

 

 

One is in the grounded metal raceway or metal pipe

F0

powerline

 

 

The both are in the grounded metal raceway or metal

10

 

 

pipe

 

 

 

 

 

11 Lightning Protection

Image 16
Contents Installation Guide Page Copyright & Trademarks FCC Statement CE Mark WarningAudience Related Document About this Installation GuideConventions Contents Cccccccccc Introduction FeaturesProduct Overview Appearance Front PanelRear Panel LEDsPower Socket Package Contents CCCCCCCCCCInstallationSafety Precautions Temperature/Humidity Site RequirementsInstallation Tools Lightening ProtectionDesktop Installation Product InstallationRack Installation Fffffffffff Rack Installation Cabling Reasonably Cccccccccc Lightning ProtectionRequirements for Cabling Outdoors Requirements for Cabling Indoors Connecting to the Grounding Bar Connect to GroundConnecting to the Ground via the Power Supply Equipotential BondingUse Lightning Arrester Lightning Protection Verify Installation Power OnCCCCCCCCCCConnection Ethernet PortInitialization Appendix a Troubleshooting Qqqq The Power LED is not litAppendix B Specifications FCC, CEAppendix C Technical Support Gigabit Unmanaged Switch Page F106503774\ Rev