•Listed fastening hardware must be compatible with the materials being joined and must be preclude loosening, deterioration and electrochemical corrosion of the hardware and joint materials.
Connecting the RMX 4000 to AC Power
• Do not connect the green or
• Customers are required to only use AC power cables supplied by Polycom.
• The size of the protective earthing conductor should be a minimum of 10AWG.
• All three outlets intended for connection of the three power cords must be protected with an external overcurrent protection device either in building or in the rack with the rating not higher than 20Amp.
• Do not use an Extension cords with any of the cables.
1 Make sure that the power button is switched OFF on the RMX 4000.
ESD
connector
Ground
connector
|
|
|
Off/On switch | Power Entry Modules |
2Insert the power cables into the power connectors on the rear panel of the RMX 4000.