Types 5 (Ranged Transaction with ASCII addressing) and 9 (Ranged Transaction with binary addressing):
Unlike Typed operations that automatically adjust the memory address to accommodate the defined element type, the Ranged operations use word address exclusively. It performs consecutive memory word read and write. The driver takes care of address adjustment for floating point file type, making it transparent to the user and DeltaV. Therefore, the Ranged operation on integer, binary, and floating point file types are the same as the Typed operation.
Both single and block output modes are supported for integer, binary, and floating point file type.
Unlike the Typed read which only accesses the accumulator or position attribute, the Ranged read always starts at the first attribute and includes all three attributes in the data file.
Types 7
When communicating with a
RMW is for output only. The data direction parameter in the Dataset configuration must be “output”. Configuring RMW as input to PSIC will cause error and undesirable results.
Type 11 (SLC 500, SLC 5/03 and SLC 5/04 Protected Typed Logical Read/Write with three address fields):
This DeviceDataType is used to read/write all available tables (including the Input and Output tables) of the SLC processors listed. The reads and writes are from/to the logical address generated based on the starting address of the dataset. The following describes the parameters and their usage:
Input, Output, and Binary tables can be defined as Boolean, Discrete or
Input tables are read only. Output tables can be read and written. When performing reads/writes to the Output table, the driver will access the SLC on a