Delta PLC-5, SLC-500, 1770-KF2 Verify Hardware and Software Version Number, Verify Configuration

Page 19

Powerful Solutions for Digital Plants

 

￿￿ Stop Bits

1 or 2

5

Operational Check

 

5.1Scope

The following sections provide some assistance to ensure the interface is working properly.

5.2Verify Hardware and Software Version Number

The user can verify that the AB driver has been installed using the DeltaV Diagnostics tool. The Diagnostics tool will show the Hardware Revision No. (HwRev) and the Software Revision No. (SwRev).

To begin the DeltaV Diagnostic tool select Start-> DeltaV-> Operator-> Diagnostics. In the Diagnostics tool expand the Controller, I/O and then double click on the Programmable Serial Interface Card that has the Allen-Bradley driver installed.

The following information will be displayed:

 

 

:

:

:

 

HwRev

Hardware Revision

1.1

(or later)

SwRev

Software Revision

P1.0

(or later)

5.3Verify Configuration

￿￿Verify port configuration: The serial port must be enabled. User needs to make sure communication settings such as baud rate, parity, and number of data bits match the Allen-Bradley device settings.

￿￿Verify device configuration: User must check for the proper device address is entered. The Allen-Bradley device address is an octal-based number. This number must be converted to a decimal number.

￿￿Verify Dataset configuration: The RMW operations are output-only commands. Do not configure input Dataset with RMW. The DeltaV data type also needs to match with Allen-Bradley data types. For example, user should not match a DeltaV 16-bit unsigned integer with a PLC-5 floating point file data. Unpredictable results will occur if there is a mismatch between the two data types. The starting address should always be an even number to ensure proper word boundary is assigned. For Special Data 2, number 0 through 8 must match the default Allen-Bradley file types.

5.4Verify I/O Communication With Control Studio

￿￿User can create I/O modules in the control studio to verify correct values are read and written between the foreign device into the PSIC. For input data, the values should be changed in the foreign device and verified that the new data are correctly reported. For output data, change the values in the controller and then verify that the values are transferred to the foreign device.

MYNAH Technologies ￿ 504 Trade Center Blvd. ￿ Chesterfield, MO 63005 ￿ Telephone 636 681-1555 ￿ Fax 636 681-1660

www.mynah.com

18

Image 19
Contents May Rev. P1.7 Scope IntroductionDocument Format System SpecificationsFirmware Protocol Compatibility Software Requirements Related DocumentsTheory of Operation Powerful Solutions for Digital Plants Downloading the firmware Channel Attributes Block of Psic Configuration InformationDeviceDataType SpecialData4 Device And Dataset ConfigurationDeviceDataType Types 0 3 Basic Commands Powerful Solutions for Digital Plants Powerful Solutions for Digital Plants Dataset Configuration Display Powerful Solutions for Digital Plants Powerful Solutions for Digital Plants Serial Port Configuration for DeltaV Psic Verify Hardware and Software Version Number Verify ConfigurationVerify I/O Communication With Control Studio LED Indication Using DiagnosticsDeltaV PLC/SLC Electrical Interface Port 1 Half Duplex Data+/Full GND TXD RXD DTR DSR DCD RTS CTS Wiring Connections for RS-232 CommunicationsGND TXD RXD DTR DSR RTS CTS KE Module Series B Switch Settings KE Module Series a Switch Settings1770-KF2 Module Switch Settings