| Switch Mode Power Supply |
|
| DRP024V060W1BA | |
|
|
|
|
|
|
| |
| General Data |
|
|
|
|
| |
| Isolation voltage: |
|
|
|
|
| |
| Input / output |
| type test/routine test |
| 4 KVAC / 3 KVAC | ||
| Input / PE |
| type test/routine test |
| 1.5 KVAC / 1.5 KVAC | ||
| output / PE |
| type test/routine test |
| 1.5 KVAC / 500 VAC | ||
| Degree of protection |
|
| IP20 |
| ||
| Class of protection |
|
| Class I with PE connection | |||
| MTBF |
|
|
| > 1,000,000hrs. | ||
| Type of housing |
|
|
| Aluminium (AI5052) | ||
| Dimensions (L / W / H ) |
|
| 121mmx32mmx125mm | |||
| Weight |
|
|
| 0.37Kg | ||
| STATUS Indicator |
|
|
|
| ||
| LED (6) DC OUTPUT OK |
|
| YES (GREEN LED) | |||
| Climatic Data |
|
|
|
|
| |
| Ambient temperature (Operating) |
|
| to 80°C (> 50°C | |||
| Ambient temperature (Storage) |
|
| to 85°C | |||
| Humidity at 25°C, |
|
| < 95% RH | |||
|
|
|
|
|
| 10Hz to 500Hz @ 30 m/ S2 (3G peak); displacement of 0.35mm; | |
| Vibration |
|
| 60min per axis for all X, Y, Z direction. in acc. with IEC | |||
|
|
|
|
| |||
| Shock (in all directions) |
|
| 30G (300m/S2) in all directions according to | |||
| Pollution degree |
|
|
| 2 according to EN50178 | ||
| Climatic class |
|
|
| 3K3 according to EN 60721 | ||
|
| In conformance with EMC guideline 89/336/EEC and low |
|
|
| ||
|
| voltage directive 73/23/EEC |
|
| DINRAIL 1AC / 24V DC / 2.5A (EOE11010248) | ||
| EMC (electromagnetic compatibility) |
|
|
|
| ||
| Immunity to interference according to EN |
|
|
| |||
| ∙ | EN | Housing |
| LEVEL 4 | ||
|
| Discharge of static electricity (ESD) | Contact discharge: |
| 8 KV |
| |
|
|
|
| Air Discharge: |
| 15 KV |
|
| ∙ | EN | Housing |
| LEVEL 3 | ||
|
| Radiate Field Immunity | Frequency/Field intensity: |
| 80MHz - 1GHz / 10V/M with 1kHz tone / 80% modulation | ||
| ∙ | EN |
|
| 2KV4) |
| |
|
| Fast transients (Burst): |
|
|
|
| |
|
|
|
|
|
|
| |
| ∙ | EN |
|
| 2KV3) | / 2KV4) (Level 3) | |
|
| Surge voltage Immunity (Surge): |
|
|
|
| |
| ∙ |
|
|
|
|
|
|
|
|
|
|
|
| ||
| ∙ | EN | I/O: |
| Level 3 | ||
| ∙ | Conducted Immunity | Frequency / Uo: |
| 0.15MHz - 80MHz / 10Vrms. | ||
| ∙ | EN |
|
| Input: Main Buffering > 20ms. | ||
|
| Voltage dips |
|
|
|
|
|
| Noise emission according to EN |
| EN55011 (EN55022) CLASS B5 | ||||
| ∙ | Emitted radio interface |
|
| |||
| ∙ | Radio interference voltage |
|
| EN55011 (EN55022) CLASS B5 | ||
|
|
| |||||
| EN55011 corresponds to CISPR11 / EN55022 corresponds to CISPR22 / EN 61000 corresponds to IEC 61000 | ||||||
| 1) Criterion A: | Normal operating behavior within the defined limits. |
|
|
| ||
| 2) Criterion B: | Temporary impairment to operational behavior that is corrected by the device itself. | |||||
| 3) Symmetrical: Conductor to conductor. |
|
|
|
| ||
| 4) Asymmetrical: Conductor to ground. |
|
|
|
| ||
| 5) Class B: | Area of application industry and residential. |
|
|
| ||
|
|
|
|
|
|
|
|
3/13 | Rev: 00, |
1/10/2011 |
|